ILB PB 24 DI32 2862398 PHOENIX CONTACT Inline Block IO digital input module, PROFIBUS, 32 inputs, 24 V DC, 2.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

ILB PB 24 DI32 2862398 PHOENIX CONTACT Inline Block IO digital input module, PROFIBUS, 32 inputs, 24 V DC, 2..

ILB PB 24 DI32

2862398

PHOENIX_CONTACT

Available

Ship on today

Inline Block IO digital input module, PROFIBUS, 32 inputs, 24 V DC, 2, 3-wire connection technology

More details


Programmable Logic Controllers Plcs

AUTOMATION Industrial Automation - PHOENIX CONTACT

I/O systems. Connectors - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+277,13 €
2+270,49 €
3+267,21 €
4+265,97 €
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Width156 mm
Height141 mm
Depth57 mm
Note on dimensionsSpecfications with connectors

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)85 % (non-condensing)
Permissible humidity (storage/transport)95 % (non-condensing)
Air pressure (operation)80 kPa ... 108 kPa (up to 2000 m above mean sea level)
Air pressure (storage/transport)66 kPa ... 108 kPa (up to 3500 m above mean sea level)
Degree of protectionIP20

General

Net weight510 g
Note on weight specificationswith connectors
Mounting typeDIN rail
NS 35/7,5

Interfaces

Fieldbus systemPROFIBUS DP
DesignationPROFIBUS DP
Connection methodD-SUB-9 female connector
Transmission speed9,6 kBit/s ... 12 MBit/s
Number of positions9

Power supply for module electronics

Supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply current50 mA
Current consumptionapprox. 50 mA

Digital inputs

Input nameDigital inputs
Connection methodSpring-cage connection
2, 3-wire
Number of inputs32 (EN 61131-2 type 1)
Typical response timeapprox. 500 µs
Protective circuitShort-circuit protection, overload protection of the sensor supply
Input voltage24 V DC
Input voltage range "0" signal-30 V DC ... 5 V DC
Input voltage range "1" signal15 V DC ... 30 V DC
Nominal input current at UIN5 mA