Product successfully added to your shopping cart
ELR H3-IES-SC- 24DC/500AC-0,6
2900566
PHOENIX_CONTACT
1
Hybrid motor starter for starting 3~ AC motors up to 500 V AC and 0.6 A output current, with 24 V DC control voltage, adjustable overload shutdown and emergency stop function to SIL3 /PL e, and screw connection.
INTERFACE Components (IF)
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Input name | Device supply |
---|---|
Rated control circuit supply voltage US | 24 V DC |
Rated control supply current IS | 40 mA |
Protective circuit | Protection against polarity reversal Parallel polarity protection diode |
Surge protection | |
Operating voltage display | Green LED |
Status display | Yellow LED |
Indication | Red LED |
Input name | Control input right/left |
Rated actuating voltage UC | 24 V DC |
Rated actuating current IC | 5 mA |
Switching threshold | 9.6 V (“0” signal) |
19.2 V (“1” signal) | |
Switching level | < 5 V DC (For EMERGENCY STOP) |
Protective circuit | Protection against polarity reversal |
Typical turn-off time | < 30 ms |
Rated operating voltage Ue | 500 V AC |
---|---|
Operating voltage range | 42 V AC ... 550 V AC |
Load current range | 75 mA ... 600 mA (see to derating) |
Trigger characteristic in acc. with IEC 60947 | Class 10A |
Rated operating current at AC-51 | 0.6 A |
Rated operating current at AC-53a | 0.6 A |
Leakage current | 0 mA |
Protective circuit | Surge protection Varistor |
Note | Confirmation: floating change-over contact, signal contact |
---|---|
Contact type | 1 PDT |
Connection name | Control circuits |
---|---|
Connection method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Torque | 0.5 Nm ... 0.6 Nm |
Switching frequency | ≤ 2 Hz (Load-dependent) |
---|---|
Mounting position | vertical (horizontal DIN rail, motor output below) |
Assembly instructions | alignable, for spacing see derating |
Operating mode | 100% operating factor |
Designation | Standards/regulations |
Standards/regulations | IEC 60947-1 |
EN 60947-4-2 | |
IEC 61508 | |
ISO 13849 | |
Safety Integrity Level according to IEC 61508 | SIL 3 (safe shutdown) |
SIL 2 (motor protection) | |
Category acc. to EN ISO 13849 | 3 (Safe shutdown) |
Performance level according to ISO 13849 | e (Safe shutdown) |
Width | 22.5 mm |
---|---|
Height | 99 mm |
Depth | 114.5 mm |
Ambient temperature (operation) | -25 °C ... 70 °C (observe derating) |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Degree of protection | IP20 |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX INTERFACE TECHNOLOGY AND SWITCHING DEVICES EN.pdf | 27 Mbytes | |
PHOENIX CONTACT-2900566-ELR H3-IES-SC- 24DC/500AC-0,6 | 151 Kbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.