Product successfully added to your shopping cart
VG-C DC-TS1000
5088660
OBO BETTERMANN
1
Surge protection device 2 PV string w. circuit breaker,
Generator connection box, type 2, up to 1,000 V DC with disconnection switch (32 A) for 1 x 1 string. System solution for circuit breaker photovoltaic inverter with 1 MPP tracker• Varistor arrester, connectable with cut-off unit in error-resistant Y circuit to VDE 0100-712 (50539-12) • Low DC protection level: < 4.0 kV (Voc max = 1,000 V DC with V2ß-B+C/0-500PV) • Circuit breaker (1,000 V; 32 A) for secure switch-off of the DC string cable• Per protection device, there is 1 terminal up to 6 mm² pre-mounted in the housing, up to 30 A DC per terminal • Pre-mounted in polycarbonate housing (IP65), UV-resistant for use outside, including cable gland kitFor DC protection of the inverter in photovoltaic systems.If there is a danger of condensation forming through wind, ice, temperature or sunl
Earthing, lightning and surge protection > Surge protection device for power supply systems
TBS Transient and lightning protection systems - OBO BETTERMANN > Surge protection, photovoltaics - OBO BETTERMANN
Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Anschlussart Generatoranschlusskasten | Tension spring terminal |
|---|---|
| CO2 Footprint (GWP) Cradle-to-Gate | 2,644 kg CO2e / 1 Piece |
| Colour | Light grey; RAL 7035 |
| Conductor cross-section, rigid (single-wire/multiwire), max. | 6 mm² |
| Conductor cross-section, rigid (single-wire/multiwire), min. | 0,5 mm² |
| DC network form | yes |
| Depth | 122 mm |
| Dimension | 1000V DC |
| Entries per MPPT | 1 |
| Equipped with load-break switch | yes |
| Exits per MPPT | 1 |
| Installation type | Pre-mounted in the housing |
| IT network form | no |
| Lightning protection zone LPZ | 1→2 |
| Max. Input current per string | 30 A |
| Max. Input voltage DC | 1000 V |
| Max. Output current | 30 A |
| Maximum continuous voltage DC | 1000 V |
| Maximum discharge current (8/20 μs) | 40 kA |
| Monitoring function | no |
| Network form | DC |
| Nominal discharge current (8/20 µs) | 20 kA |
| Number of cable entries | 16 |
| Number of inputs | 1 |
|---|---|
| Number of MPPTs | 1 |
| Number of string inputs | 1 |
| Operating temperature, max. | 80 °C |
| Operating temperature, min. | -40 °C |
| Other network form | no |
| Permitted temperature range, max. | 80 °C |
| Permitted temperature range, min. | -40 °C |
| Protection rating | IP65 |
| Remote signalling | no |
| Response time | <25 ns |
| Signalling on device | Visual |
| SPD to EN 61643-11 | Type 2 |
| SPD to IEC 61643-1 | Class II |
| String fuse | Without |
| TN network form | no |
| TN-C network form | no |
| TN-C-S network form | no |
| TN-S network form | no |
| TT network form | no |
| Type of entry | Gland |
| Version for | Type 2 and Benedikt LS32-SMA-A4 DC isolator |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE SURGE PROTECTION OBO EN.pdf | 24 Mbytes |
|
| VG-C DC-TS1000 5088660 OBO BETTERMANN Surge protection device 2 PV string w. circuit breaker, | 52 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.