Lightning current discharger MCF-C+FS-440 440V orange

Lightning current arrester MCF-C. Lightning current arrester, type 1+2• Protecion level < 2.5 kV• Lightning protection equipotential bonding according to VDE 0185-305 (IEC 62305)• Lightning current discharge capacity 25 kA (10/350)• Follow current quenching Ifi 50 kA• Max. pre-fuse 315 A gL/gG• Complies with the requirements for the use in the pre-meter area according to VDE-AR-N 4100• The FS version has a potential-free changeover contact for remote signallingApplication: Without exception for 400/690 V network systems and for the lightning protection classes I to IV only.* Complete = Plug-in arrester and base

More details


Home > OBO BETTERMANN

Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN

Total: $693.32
Unit price: $693.32
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Blow-outno
CO2 Footprint (GWP) Cradle-to-Gate0,6563 kg CO2e / 1 Piece
ColourOrange
Conductor cross-section, flexible (fine-wire), max.3 AWG
Conductor cross-section, flexible (fine-wire), max.25 mm²
Conductor cross-section, flexible (fine-wire), min.6 mm²
Conductor cross-section, flexible (fine-wire), min.10 AWG
Conductor cross-section, rigid (single-wire/multiwire), max.35 mm²
Conductor cross-section, rigid (single-wire/multiwire), max.2 AWG
Conductor cross-section, rigid (single-wire/multiwire), min.6 mm²
Conductor cross-section, rigid (single-wire/multiwire), min.10 AWG
Connection cross-section, FM terminals, max.1,5 mm²
Connection cross-section, FM terminals, max.16 AWG
Connection cross-section, FM terminals, min.0,5 mm²
Connection cross-section, FM terminals, min.21 AWG
DC network formno
Dimension440V
FM contactsChangeover
Follow current quenching capacity (eff) [N-PE]50 kA
Height74,5 mm
Humidity, max.95 %
Humidity, min.5 %
Installation typeDIN rail 35 mm
Integrated back-up fuseno
IT network formyes
Length150 mm
Lightning surge current (10/350 μs)25 kA
Max. mains-side overcurrent protection315 A gL/gG
Maximum back-up fuse315 A
Maximum continuous voltage (L-N)440 V
Maximum continuous voltage AC440 V
Nominal discharge current (8/20 µs)35 kA
Nominal discharge current (8/20 µs) [L-N]35 kA
Nominal voltage AC (50/60 Hz)400 V
Operating temperature, max.80 °C
Operating temperature, min.-40 °C
Other network formno
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Pole version1
Protection level [L-N]≤2,5
Protection ratingIP20
Remote signallingyes
Short-circuit resistance for max. mains-side overcurrent protection50 kA eff
Signalling on deviceVisual
SPD to EN 61643-11Type 1+2
SPD to IEC 61643-1Class I+II
Suitable for outdoor useno
Switching power AC230 V; 0,5 A
Switching power DC230 V; 0,1 A / 75 V; 0,5 A
Test class, type 1yes
TN network formyes
TN-C network formyes
TN-C-S network formyes
TN-S network formyes
TOV voltage [L-N] ‒ fail safe mode ‒ 120 min.760 V
TOV voltage [L-N] ‒ withstand mode ‒ 5 s580 V
TT network formyes
Width36 mm

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.