Spark path EX ISG N, Indirect equipotential junction 215x47x35
Spark pathway Indirect equipotential junction ISG N
EX ISG N spark gap. Spark gap for potentially explosive areas, Zone 1/21 and 2/22, for indirect bridging of insulating flanges and insulating threaded joints, e.g. in cathodically corrosion-protected (CCP) systems. For indirect connection of operationally separated system sections during lightning impact. Use according to lightning protection equipotential bonding in accordance with DIN EN 62305/VDE 0185. Suitable for installation in interior and exterior areas and in wet rooms. Particularly low rated contact surge voltage.• Spark gap to VDE 0185-561-3 (IEC 62561-3)• Ex certificate to ATEX• Labelling to EN IEC 60079-0 / EN 60079-1: II 2G Ex db IIC T6 Gb• Labelling to EN IEC 60079-0 / IEC 60079/31: II 2 D Ex td IIIC T80 °C Db IP67• Ex certificate to IECEx• Labelling to IEC 60079-0 / -1: E
TBS Transient and lightning protection systems - OBO BETTERMANN
Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| CO2 Footprint (GWP) Cradle-to-Gate | 1,7553 kg CO2e / 1 Piece |
|---|---|
| Colour | Black |
| Connection | Rd 10 mm |
| Dimension | 215x47x35 |
| Dimension | 215x47x35 |
| Lightning current carrying capacity | N/50 kA |
| Lightning impulse current | 50 kA |
| Material of the connection | Stainless steel, rustproof |
| Nominal discharge surge current | 100 kA |
|---|---|
| Permitted temperature range, max. | 80 °C |
| Permitted temperature range, min. | -20 °C |
| Power frequency spark-over voltage | 0,64 kV |
| Protection rating | IP65/67 |
| Rated DC withstand voltage | 425 V |
| Rated impulse sparkover voltage | 1,5 kV |
| Rated power frequency withstand voltage | 300 V |
| Feature Name | Feature Value |
|---|---|
| Rated impulse sparkover voltage (EF012270) | 1.5 kV |
| Rated power-frequency withstand voltage (EF012271) | 300 V |
| Connection (EF000443) | Round 10 mm |
| Material of connection (EF004250) | Stainless steel 304 |
| Degree of protection (IP) (EF005474) | IP67 |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE SURGE PROTECTION OBO EN.pdf | 24 Mbytes |
|
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.