ANUNCIAR

XSDMC-2004 193281 Y7-193281 EATON ELECTRIC Variable frequency drive, 500 V AC, 3-phase, 13.5 A, 7.5 kW, IP21..

XSDMC-2004

193281

Y7-193281

EATON-MOELLER

Variable frequency drive, 500 V AC, 3-phase, 13.5 A, 7.5 kW, IP21/NEMA1, Brake chopper, DC link choke

XSDMC-2004

Door to switchgear area, closed, IP55, HxW=500x425mm

More details


Cabinet enclosures > Door/operating panel (switchgear cabinet)

Enclosures

Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total: $195.89
Unit price: $195.89
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Delivery program
Product range
Variable frequency drives
Part group reference (e.g. DIL)
DG1
Rated operational voltage
Ue 600 V AC, 3-phase
Output voltage with Ve
U2 600 V AC, 3-phase
Mains voltage (50/60Hz)
ULN V 500 (-10%) - 600 (+10%)
Rated operational current
At 150% overload
Ie A 13.5
At 110% overload
Ie A 18
Note
Rated operational current for a switching frequency of 1 - 6 kHz and an ambient temperature of +50 °C for a 150% overload and +40 °C for a 110% overload
Assigned motor rating
Note
for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1at 50 Hz or 1800 min-1at 60 Hz
Note
Overload cycle for 60 s every 600 s
Note
at 525 V, 50 Hz
150 % Overload
P kW 7.5
110 % Overload
P kW 11
150 % Overload
IM A 12.1
110 % Overload
IM A 17.4
Note
at 600 V, 50 Hz
150 % Overload
P kW 7.5
110 % Overload
P kW 11
150 % Overload
IM A 10.6
110 % Overload
IM A 15.1
Note
at 600 V, 60 Hz
150 % Overload
P HP 10
110 % Overload
P HP 15
150 % Overload
IM A 11
110 % Overload
IM A 17
Degree of Protection
IP21/NEMA1
Interface/field bus (built-in)
Modbus RTU
Modbus TCP
BACnet MS/TP
Ethernet IP
Fieldbus connection (optional)
PROFIBUS
CANopen®
DeviceNet
SmartWire-DT
Fitted with
Radio interference suppression filter
Additional PCB protection
Multi-line graphic display
Brake chopper
DC link choke
Frame size
FS2
Connection to SmartWire-DT
yes
in conjunction with DXG-NET-SWD SmartWire DT module
Technical data
General
Standards
Specification for general requirements: IEC/EN 61800-2
EMC requirements: IEC/EN 61800-3
Safety requirements: IEC/EN 61800-5
Certifications
CE, UL, cUL, c-Tick, UkrSEPRO, EAC
Production quality
RoHS, ISO 9001
Climatic proofing
ρw % < 95%, average relative humidity (RH), non-condensing, non-corrosive
Air quality
3C2, 3S2
Ambient temperature
operation (150 % overload)
ϑ °C -30 - +50 (max. +60 with 1 % derating per Kelvin temperature rise)
operation (110 % overload)
ϑ °C -30 - +40 (max. +55 mit 1 % Derating pro Kelvin Temperaturerhöhung)
Storage
ϑ °C -40 - +70
Overvoltage category
III
Pollution degree
2
Radio interference level
Radio interference class (EMC)
C1 (with external filter, for conducted emissions only), C2, C3, depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Environment (EMC)
1st and 2nd environments as per EN 61800-3
maximum motor cable length
I m C3 ≤ 10 m
Mechanical shock resistance
g EN 61800-5-1, EN 60068-2-27
UPS drop test (for weights inside the UPS frame)
Storage and transportation: maximum 15 g, 11 ms (inside the packaging)
Vibration
EN 61800-5-1, EN 60068-2-6: 5 - 150 Hz
Amplitude: 1 mm (peak) at 5 - 15.8 Hz
Maximum acceleration amplitude: 1 g at 15.8 – 150 Hz
Mounting position
Vertical
Altitude
m 0 - 1000 m above sea level
Above 1000 m: 1% derating for every 100 m
max. 2000 m
Degree of Protection
IP21/NEMA1
Protection against direct contact
BGV A3 (VBG4, finger- and back-of-hand proof)
Main circuit
Supply
Rated operational voltage
Ue 600 V AC, 3-phase
Mains voltage (50/60Hz)
ULN V 500 (-10%) - 600 (+10%)
Input current (150% overload)
ILN A 12.5
Input current (110% overload)
ILN T 16.7
System configuration
TN-S, TN-C, TN-C-S, TT, IT
Supply frequency
fLN Hz 50/60
Frequency range
fLN Hz 45 - 66
Mains switch-on frequency
Maximum of one time every 60 seconds
Mains current distortion
THD % 36.7
Rated conditional short-circuit current
Iq kA < 100
Power section
Function
Variable frequency drive with internal DC link, DC link choke and IGBT inverter
Overload current (150% overload)
IL A 20.25
Overload current (110% overload)
IL A 19.8
max. starting current (High Overload)
IH % 200
Note about max. starting current
for 2 seconds every 20 seconds
Output voltage with Ve
U2 600 V AC, 3-phase
Output Frequency
f2 Hz 0 - 50/60 (max. 400)
Switching frequency
fPWM kHz 1.5
adjustable 1 - 6
Operation Mode
U/f control
Speed control with slip compensation
sensorless vector control (SLV)
Torque regulation
Frequency resolution (setpoint value)
Δf Hz 0.01
Rated operational current
At 150% overload
Ie A 13.5
At 110% overload
Ie A 18
Note
Rated operational current for a switching frequency of 1 - 6 kHz and an ambient temperature of +50 °C for a 150% overload and +40 °C for a 110% overload
Motor current limit
I A 0.1 - 2 x IH(CT)
Power loss
Heat dissipation at rated operational current Ie=150 %
PV W 221
Heat dissipation at rated operational current Ie=110%
PV W 303
Efficiency
η % 98.2
Maximum leakage current to ground (PE) without motor
IPE mA 9.8
Fan
temperature controlled
Tool-less swapping
Internal fan delivery rate
m3/h 94
Fitted with
Radio interference suppression filter
Additional PCB protection
Multi-line graphic display
Brake chopper
DC link choke
Safety function
STO (Safe Torque Off, SIL1, PLc Cat 1)
Frame size
FS2
Motor feeder
Note
for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1at 50 Hz or 1800 min-1at 60 Hz
Note
Overload cycle for 60 s every 600 s
Note
at 525 V, 50 Hz
150 % Overload
P kW 7.5
110 % Overload
P kW 11
Note
at 600 V, 50 Hz
150 % Overload
P kW 7.5
110 % Overload
P kW 11
Note
at 600 V, 60 Hz
150 % Overload
P HP 10
110 % Overload
P HP 15
maximum permissible cable length
I m screened: 150
Apparent power
Apparent power at rated operation 600 V
S kVA 18.7
Braking function
Standard braking torque
max. 30 % MN
DC braking torque
adjustable to 150 %
Braking torque with external braking resistance
Max. 100% of rated operational current Iewith external braking resistor
minimum external braking resistance
Rmin 30
Switch-on threshold for the braking transistor
UDC V Supply voltage UAUX 1050 V DC
DC braking
% I/Ie ≦ 150, adjustable
Control section
External control voltage
Uc V 24 V DC (max. 250 mA options incl.)
Reference voltage
Us V 10 V DC (max. 10 mA)
Analog inputs
2, parameterizable, 0 - 10 V DC, 2 - 10 V DC, -10 - +10 V DC, 0/4 - 20 mA
Analog outputs
2, parameterizable, 0 - 10 V, 0/4 - 20 mA
Digital inputs
8, parameterizable, max. 30 V DC
Digital outputs
1, parameterizable, 24 V DC
Relay outputs
3, parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 VAC) / 6 A (24 VDC)
Interface/field bus (built-in)
Modbus RTU
Modbus TCP
BACnet MS/TP
Ethernet IP
Expansion slots
2
Assigned switching and protective elements
Power Wiring
Safety device (fuse or miniature circuit-breaker)
IEC (Type B, gG), 150 %
PKZM0-16
IEC (Type B, gG), 110 %
PKZM0-20
UL (Class CC or J)
A 30
Mains contactor
150 % overload (CT/IH, at 50 °C)
DILM7
110 % overload (VT/IL, at 40 °C)
DILM7
Main choke
150 % overload (CT/IH, at 50 °C)
Integrated DC link choke, uk = 5%
110 % overload (VT/IL, at 40 °C)
Integrated DC link choke, uk = 5%
Note regarding radio interference suppression filter
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
DC link connection
Braking resistance
10 % duty factor (DF)
DX-BR040-3K1
20 % duty factor (DF)
DX-BR040-5K1
40 % duty factor (DF)
DX-BR047-9K2
Notes concerning braking resistances:
PnRm: = Connect every "n" resistors in parallel, then connect the resulting combinations "m" times in series. A total of "n" x "m" resistors will be needed.
Motor feeder
motor choke
150 % overload (CT/IH, at 50 °C)
DX-LM3-016
110 % overload (VT/IL, at 40 °C)
DX-LM3-035
Sine filter
150 % overload (CT/IH, at 50 °C)
DX-SIN3-016
110 % overload (VT/IL, at 40 °C)
DX-SIN3-023
All-pole sine filter
150 % overload (CT/IH, at 50 °C)
DX-SIN3-024-A
110 % overload (VT/IL, at 40 °C)
DX-SIN3-024-A
Approvals
Product Standards UL508C, CSA-C22.2 No. 274-13; IEC/EN61800-3; IEC/EN61800-5; CE marking
UL File No. E134360
UL Category Control No. NMMS, NMMS7
CSA File No. UL report applies to both US and Canada
North America Certification UL listed, certified by UL for use in Canada
Suitable for Branch circuits
Max. Voltage Rating 3~600 V AC IEC: TN-S UL/CSA: 'Y' (Solidly Grounded Wey)
Degree of Protection IP21/NEMA1
Technical data ETIM 7.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Frequency converter =< 1 kV (EC001857)
Electric engineering, automation, process control engineering / Electrical drive / Static frequency converter / Static frequency converter = < 1 kV ([email protected] [AKE177014])
Mains voltage
V 525 - 600
Mains frequency
50/60 Hz
Number of phases input
3
Number of phases output
3
Max. output frequency
Hz 400
Max. output voltage
V 575
Nominal output current I2N
A 13.5
Max. output at quadratic load at rated output voltage
kW 11
Max. output at linear load at rated output voltage
kW 15
Relative symmetric net frequency tolerance
% 10
Relative symmetric net voltage tolerance
% 10
Number of analogue outputs
Number of analogue inputs
Number of digital outputs
Number of digital inputs
With control unit
Yes
Application in industrial area permitted
Yes
Application in domestic- and commercial area permitted
Yes
Supporting protocol for TCP/IP
Yes
Supporting protocol for PROFIBUS
Yes
Supporting protocol for CAN
Yes
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for KNX
No
Supporting protocol for MODBUS
Yes
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
Yes
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
Yes
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
No
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for BACnet
Supporting protocol for other bus systems
Yes
Number of HW-interfaces industrial Ethernet
1
Number of interfaces PROFINET
1
Number of HW-interfaces RS-232
0
Number of HW-interfaces RS-422
0
Number of HW-interfaces RS-485
1
Number of HW-interfaces serial TTY
0
Number of HW-interfaces USB
0
Number of HW-interfaces parallel
0
Number of HW-interfaces other
1
With optical interface
No
With PC connection
Yes
Integrated breaking resistance
Yes
4-quadrant operation possible
Yes
Type of converter
U converter
Degree of protection (IP)
IP21
Degree of protection (NEMA)
Height
mm 419
Width
mm 169
Depth
mm 244

ETIM for 193281 Cabinets and enclosures (EC000747)
Feature Name Feature Value
Model (EF000010) Other
Version as glazed door (EF006966) No
Version as door for disconnecting switch interlocking (EF006967) No
Width (EF000008) 595 mm
Height (EF000040) 497 mm
Depth (EF000049) 82 mm
EMC-version (EF001062) No
Material (EF002169) Other
Surface finishing (EF006569) Powder coated
Colour (EF000007) Grey
Degree of protection (IP) (EF005474) IP55

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.