LN2-200-I 112003 EATON ELECTRIC Switch-disconnector, 3 p, 200A, frame size 2 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

LN2-200-I 112003 EATON ELECTRIC Switch-disconnector, 3 p, 200A, frame size 2

LN2-200-I

112003

EATON-MOELLER

Switch-disconnector, 3 p, 200A, frame size 2

LN2-200-I

More details


Circuit Breakers LZM

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $307.98
Unit price: $307.98

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Switch-disconnector, 3 p, 200A, frame size 2

Delivery program

Product range
Switch-disconnectors
Protective function
Disconnectors/main switches
Standard/Approval
IEC
Installation type
Fixed
Construction size
LN2
Description
Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
Isolating characteristics to IEC/EN 60947-3 and VDE 0660.
Busbar tag shroud to VDE 0160 Part 100.
Number of poles
3 pole
Standard equipment
Screw connection
Switch positions
I, +, 0
Rated current = rated uninterrupted current [In= Iu]
200 A
Short-circuit protection max. fuse gL-characteristic
250 A gL

Technical data

Switch-disconnectors
Rated surge voltage invariability [Uimp]Main contacts
8000 V
Rated surge voltage invariability [Uimp]Auxiliary contacts
6000 V
Rated operational voltage [Ue]
690 V AC
Rated operating frequency [f]
50/60 Hz
Rated current = rated uninterrupted current [In= Iu]
200 A
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
690 V
Use in unearthed supply systems
≦ 690 V
Rated short-circuit making capacity [Icm]
690 V 50/60 H [Ic]
5.5 kA
Rated short-time withstand current
t = 0.3 s [Icw]
3.5 kA
t = 1 s [Icw]
3.5 kA
Rated conditional short-circuit current [kA]
With back-up fuse
PN2(N2)-160…250: 250 A gG/gL
400 … 415 V
100 kA
690 V
80 kA
With downstream fuse
PN2(N2)-160…250: 250 A gG/gL
400 … 415 V
100 kA
690 V
80 kA
Rated making and breaking capacity
Rated operational current [Ie]415 V [Ie]
250 A
Rated operational current [Ie]690 V [Ie]
250 A
Rated operational current [Ie]415 V [Ie]
250 A
Rated operational current [Ie]690 V [Ie]
250 A
Lifespan, mechanical [Operations]
20000
Max. operating frequency
120 Ops/h
Lifespan, electrical
400 V 50/60 Hz [Operations]
10000
415 V 50/60 Hz [Operations]
10000
690 V 50/60 Hz [Operations]
7500
400 V 50/60 Hz [Operations]
7500
415 V 50/60 Hz [Operations]
7500
690 V 50/60 Hz [Operations]
5000
Total break time at short-circuit
< 10 ms
Terminal capacity
Standard equipment
Screw connection
Round copper conductorBox terminalSolid
1 x (4 - 16)
2 x (4 - 16) mm2
Round copper conductorBox terminalStranded
1 x (25 - 185)
2 x (25 - 70) mm2
Round copper conductorTunnel terminalSolid
1 x (16 - 185) mm2
Round copper conductorTunnel terminalStrandedStranded
1 x (25 - 185) mm2
Round copper conductorBolt terminal and rear-side connectionDirect on the switchSolid
1 x (4 - 16)
2 x (4 - 16) mm2
Round copper conductorBolt terminal and rear-side connectionDirect on the switchStranded
1 x (25 - 185)
2 x (25 - 70) mm2
Al conductors, Cu cableTunnel terminalSolid
1 x 16 mm2
Al conductors, Cu cableTunnel terminalStrandedStranded
1 x (25 - 185) mm2
Al conductors, Cu cableBolt terminal and rear-side connectionFlat copper strip, with holes [min.]
2 x 16 x 0.8 mm
Al conductors, Cu cableBolt terminal and rear-side connectionFlat copper strip, with holes [max.]
10 x 16 x 0.8 mm
Cu strip (number of segments x width x segment thickness)Box terminal [min.]
2 x 9 x 0.8 mm
Cu strip (number of segments x width x segment thickness)Box terminal [max.]
10 x 16 x 0.8 mm
Cu strip (number of segments x width x segment thickness)Bolt terminal and rear-side connectionFlat copper strip, with holes [min.]
2 x 16 x 0.8 mm
Cu strip (number of segments x width x segment thickness)Bolt terminal and rear-side connectionFlat copper strip, with holes [max.]
10 x 16 x 0.8 mm
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionScrew connection
M8
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionDirect on the switch [min.]
16 x 5 mm
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionDirect on the switch [max.]
20 x 5 mm
Control cables
1 x (0.75 - 2.5)
2 x (0.75 - 1.5) mm2

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
200 A
Equipment heat dissipation, current-dependent [Pvid]
30.72 W
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Switch disconnector (EC000216)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Switch disconnector ([email protected] [AKF060013])
Version as main switch
Yes
Version as maintenance-/service switch
Yes
Version as safety switch
No
Version as emergency stop installation
Yes
Version as reversing switch
No
Number of switches
Max. rated operation voltage Ue AC
400 V
Rated operating voltage
690 - 690 V
Rated permanent current Iu
200 A
Rated permanent current at AC-23, 400 V
A
Rated permanent current at AC-21, 400 V
0 A
Rated operation power at AC-3, 400 V
0 kW
Rated short-time withstand current lcw
3.5 kA
Rated operation power at AC-23, 400 V
110 kW
Switching power at 400 V
0 kW
Conditioned rated short-circuit current Iq
100 kA
Number of poles
3
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Motor drive optional
Yes
Motor drive integrated
No
Voltage release optional
Yes
Device construction
Built-in device fixed built-in technique
Suitable for ground mounting
Yes
Suitable for front mounting 4-hole
No
Suitable for front mounting centre
No
Suitable for distribution board installation
Yes
Suitable for intermediate mounting
Yes
Colour control element
Grey
Type of control element
Rocker lever
Interlockable
Yes
Type of electrical connection of main circuit
Screw connection
Degree of protection (IP), front side
IP20
Degree of protection (NEMA)

Dimensions

123X312
① Blow out area, minimum clearance to other parts
② Minimum clearance to adjacent parts
123X341

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.