Standards
IEC/EN 60947-4-2
UL 508
CSA22.2-14
Approvals
UL
CSA
C-Tick
UkrSEPRO
Climatic proofing
Damp heat, constant, to IEC 60068-2-3
Damp heat, cyclic, to IEC 60068-2-10
Ambient temperatureOperation [ϑ]
-5 - +40
up to 60 at 2% derating per Kelvin temperature rise °C
Ambient temperatureStorage [ϑ]
-25 - +60 °C
Altitude
0 - 1000 m, above that 1 % derating per 100 m , up to 2000 m m
Mounting position
Vertical
Degree of protectionDegree of Protection
IP20
Protection against direct contact
Finger- and back-of-hand proof
Overvoltage category/pollution degree
II/2
Shock resistance
8 g/11 ms
Vibration resistance to EN 60721-3-2
2M2
Radio interference level (IEC/EN 55011)
B
Static heat dissipation, non-current-dependent [Pvs]
0.2 W
Rated operating voltage [Ue]
200 - 480 V AC
Supply frequency [fLN]
50/60 Hz
Rated operational current [Ie]AC-53 [Ie]
4 A
Assigned motor rating (Standard connection, In-Line)at 230 V, 50 Hz [P]
0.75 kW
Assigned motor rating (Standard connection, In-Line)at 400 V, 50 Hz [P]
1.5 kW
Assigned motor rating (Standard connection, In-Line)at 200 V, 60 Hz [P]
0.75 HP
Assigned motor rating (Standard connection, In-Line)at 230 V, 60 Hz [P]
1 HP
Assigned motor rating (Standard connection, In-Line)at 460 V, 60 Hz [P]
2 HP
Overload cycle to IEC/EN 60947-4-2AC-53a
4 A: AC-53a: 3 - 5: 75 - 10
Overload cycle to IEC/EN 60947-4-2Internal bypass contacts
✓
Short-circuit ratingType “1” coordination
PKM0-4 (+ CL-PKZ0)
Short-circuit ratingType „2“ coordination (additional with the fuses for coordination type „1“)
3 x 170M1359
Fuse base (number x part no.)
3 x 170H1007
Cable lengthsSolid
1 x (0.75 - 4)
2 x (0.75 - 2.5) mm2
Cable lengthsFlexible with ferrule
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Cable lengthsSolid or stranded
18 - 10 AWG
Cable lengthsTightening torque
1.2 Nm
Cable lengthsScrewdriver (PZ: Pozidriv)
PZ2; 1 x 6 mm mm
Control cablesSolid
1 x (0.75 - 4)
2 x (0.75 - 2.5) mm2
Control cablesFlexible with ferrule
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Control cablesSolid or stranded
18 - 10 AWG
Control cablesTightening torque
1.2 Nm
Control cablesScrewdriver
0,8 x 5,5
1 x 6 mm
Digital inputsControl voltageDC-operated
24 V DC +10 %/- 15 % V DC
Digital inputsControl voltageAC operated
24 V AC +10 %/- 15 % V AC
Digital inputsCurrent consumption 24 VExternal 24 V
1.6 mA
Digital inputsPick-up voltageDC-operated
17.3 - 27 V DC
Digital inputsPick-up voltageAC operated
17.3 - 27 V AC
Digital inputsDrop-out voltage [x Us]DC operated
0 - 3 V DC
Digital inputsDrop-out voltage [x Us]AC operated
0 - 3 V AC
Digital inputsPick-up timeDC operated
250 ms
Digital inputsPick-up timeAC operated
250 ms
Digital inputsDrop-out timeDC operated
350 ms
Regulator supplyVoltage [Us]
24 V AC/DC +10 %/- 15 % V
Regulator supplyCurrent consumption [Ie]
50 mA
Regulator supplyNotes
External supply voltage
Relay outputsNumber
1 (TOR)
Relay outputsVoltage range
=UsV AC
Relay outputsAC-11 current range
1 A, AC-11 A
Ramp timesAcceleration
1 - 30 s
Ramp timesDeceleration
0 - 30 s
Start voltage (= turn-off voltage)
30100 %
Start pedestal
30 - 100 %
Fields of applicationFields of application
Soft starting of three-phase asynchronous motors
Fields of application1-phase motors
●
Fields of application3-phase motors
✓
Fast switching (semiconductor contactor)
- (minimum ramp time 1s)
Reversing starter
External solution required
Suppression of closing transients
✓
Suppression of DC components for motors
✓
Potential isolation between power and control sections
✓
Rated impulse withstand voltage:
- 1.2 µs/50 µs (rise time/fall time of the pulse to IEC/EN 60947‐2 or ‐3)
- Applies for control circuit/power section/enclosure