LS-S11-120AMT-ZBZ/X 106826 LS-S11-120AMT-ZBZ-X EATON ELECTRIC Position switch, 1N/O+1N/C, basic, magnet-powe.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

LS-S11-120AMT-ZBZ/X 106826 LS-S11-120AMT-ZBZ-X EATON ELECTRIC Position switch, 1N/O+1N/C, basic, magnet-powe..

LS-S11-120AMT-ZBZ/X

106826

LS-S11-120AMT-ZBZ-X

EATON-MOELLER

Position switch, 1N/O+1N/C, basic, magnet-powered interlock

LS-S11-120AMT-ZBZ/X

More details


Sensors > End switch

Position Switches

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $178.62
Unit price: $178.62

Quantity Price
1+$178.62
2+$167.38
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Position switch, 1NO+1NC, base, magnetic interlock
Position switch, basic Function: position switch, position Switches, safety Detector type: LS...ZBZ/X, product Range: basic device with magnetic interlock (operation excitation), Degree of protection: IP65 Accessories: basic Unit, expandable, ambient Temperature: -25 - +40 °C, Description: with monitoring interlock, Control, door position: permanent, Command timed unlocking is possible with ESR5-NV3-30, Equipment, contacts NA = norm. open: 1 no contact, Equipment, contact NC = norm. closed: 1 NC contact, Note: = safety Function by positive opening according to IEC/EN 60947-5-1, rated Voltage of the drive, the command magnet: Us= 120 V 50/60 Hz V, Enclosures: insulation material Type of connection: Clamp, bolt, Conformity with standards: IEC/EN 60947

Delivery program

Basic function
position switch
Position switches safety
Detector type
LS...ZBZ/X
Assortment
Basic device with magnetic interlock (operation in excitation)
Degree of protection
IP65
Accessories
The base unit, expandable
Ambient temperature
-25 - +40 °C
Description
with monitoring interlock
Control of door position: permanent
Command timed unlocking is possible with ESR5-NV3-30
Brand control
0000SPC-471
Equipment contacts
NA = norm. open
1 contact NA
NC = norm. closed
1 NC contact
Note
= Safety function by positive opening according to IEC/EN 60947-5-1
Circuit symbol
131S022
The nominal voltage of the drive, the command magnet [Us]
120 V 50/60 Hz V
Enclosures
insulating material
Type of connection
Clamp bolt
Notes
Do not use the switch as a mechanical stop.
The head of the drive is rotatable 90 without the need for tools to fit better to the plan of operation established.
In the case of the actuator inserted, the no contact is open and the NC contact is closed.
For the protection degree IP65 using cable glands V-M20 (206910) with max 9 mm of thread of the fitting.

Technical data

General
Compliance with the standards
IEC/EN 60947
Suitability to the climates
Moist heat, constant according to IEC 60068-2-78Caldo damp, cyclic according to IEC 60068-2-30
Ambient temperature
-25 - +40 °C
Mounting position
optional
Degree of protection
IP65
Connection cross-sectionsHard
1 x (0.75 - 2.5)
2 x (0.75 - 1.5) mmTwo
Connection cross-sectionsFlexible with ferrule
1 x (0.5 - 1.5)
2 x (0.5 - 1.5) mmTwo
Precision, reproducibility
0.02 mm
Contacts/power interruption
Rated voltage impulse withstand [Uimp]
4000 V AC
Rated insulation voltage [Uthe]
400 V
Overvoltage category/pollution degree
III/3
The nominal current of use [Iand]AC-1524 V [Iand]
6 To
The nominal current of use [Iand]AC-15220 V 230 V 240 V [Iand]
6 To
The nominal current of use [Iand]AC-15380 V 400 V 415 V [Iand]
4 To
The nominal current of use [Iand]DC-1324 V [Iand]
Three
The nominal current of use [Iand]DC-13110 V [Iand]
0.8 To
The nominal current of use [Iand]DC-13220 V [Iand]
0.3 To
Network frequency
max. 400 Hz
Short-circuit resistance according to IEC/EN 60947-5-1Max fuse
6 A gG/gL
Short-circuit current limited
1 kA
Mechanical values
Mechanical life [Operations]
1 x 10Six
Resistance (shock, sinusoidal 20 ms)Contact in slow motion
10 g
Switching frequency [op/h]
≦ 800
Drive
mechanicalDrive force of the beginning/end of stroke
25/15 (insert/extract) NET
mechanicalThe force of the mechanical seal according to GS-ET-19 (04/2004)XG, XW, XNG
1700 NET
mechanicalThe force of the mechanical seal according to GS-ET-19 (04/2004)XWA, XFG, XF
1600 NET
mechanicalThe force of the mechanical seal according to GS-ET-19 (04/2004)XNW
1200 NET
ElectromechanicalMagnetPower consumptionto 120 V AC
8 it should BE
ElectromechanicalMagnetPower consumption230 V AC
11 VA
ElectromechanicalMagnetPower consumption24 V DC
8 W
ElectromechanicalSafety voltage
0.85 - 1.1 x Us
ElectromechanicalContinuous service
100 % duty cycle

Design checks according to IEC/EN 61439

Technical data for design checks
The nominal current of use for the data related to dissipation [Then]
6 To
Dissipation per pole, as a function of the current [Pvid]
0.13 W
Dissipation of the device, as a function of the current [Pvid]
0 W
Static dissipation, independent from the current [Pvs]
0 W
Power dissipation [Pve]
0 W
Temperature service environment min.
-25 °C
Ambient temperature max service.
+40 °C
Design checks per IEC/EN 61439
10.2 the Suitability of materials and components10.2.2 Resistance to corrosion
The requirements of the product standard are met.
10.2 the Suitability of materials and components10.2.3.1 Resistance of the housing to the heat
The requirements of the product standard are met.
10.2 the Suitability of materials and components10.2.3.2 Resistance of insulating materials to heat levels normal
The requirements of the product standard are met.
10.2 the Suitability of materials and components10.2.3.3 Resistance of insulating materials to heat levels extraordinary
The requirements of the product standard are met.
10.2 the Suitability of materials and components10.2.4 Resistance to UV irradiation
The requirements of the product standard are met.
10.2 the Suitability of materials and components10.2.5 Lifting
Not applicable since the entire electrical panel should be evaluated.
10.2 the Suitability of materials and components10.2.6 Proof
Not applicable since the entire electrical panel should be evaluated.
10.2 the Suitability of materials and components10.2.7 Labeling
The requirements of the product standard are met.
10.3 Degree of protection provided by enclosures
Not applicable since the entire electrical panel should be evaluated.
10.4 Pathways of dispersion-air and surface
The requirements of the product standard are met.
10.5 Protection against electric shock
Not applicable since the entire electrical panel should be evaluated.
10.6 flush Mounting of appliances
Not applicable since the entire electrical panel should be evaluated.
10.7 internal Circuits and connections
Is the responsibility of the manufacturer of the electrical panel.
10.8 Connections for conductors introduced from the outside
Is the responsibility of the manufacturer of the electrical panel.
10.9 insulation properties10.9.2 dielectric strength at network frequency
Is the responsibility of the manufacturer of the electrical panel.
10.9 insulation properties10.9.3 Voltage impulse
Is the responsibility of the manufacturer of the electrical panel.
10.9 insulation properties10.9.4 Testing of enclosures of insulating material
Is the responsibility of the manufacturer of the electrical panel.
10.10 Heating
The calculation of the overheating is the responsibility of the manufacturer of the electrical panel. Eaton provides data on the dissipation of the equipment.
10.11 Resistance to short circuit
Is the responsibility of the manufacturer of the electrical panel. Respect the default values of the equipment.
10.12 EMC
Is the responsibility of the manufacturer of the electrical panel. Respect the default values of the equipment.
10.13 mechanical Function
For the unit requirements are met while respecting the directions of the assembly instructions (THE).

Technical data according to ETIM 7.0

sensors (EG000026) / switch to single position (EC000030)
The Technique Of Ar., Elem., Energy, Tech. Comm., Network And Proc. Pipeline / Detector / measurement Switch Position, the Mechanical / Switch position single ([email protected] [AGZ382015])
the width of the sensor
60 mm
the diameter of the sensor
0 mm
the height of the sensor
173 mm
the length of the sensor
39 mm
rated operating current Ie for AC-15, 24 V
6 To
rated operating current Ie for AC-15, 125 V
6 To
rated operating current Ie for AC-15, 230 V
6 To
rated operating current Ie for DC-13, 24 V
Three
rated operating current Ie for DC-13, 125 V
0.8 To
rated operating current Ie for DC-13, 230 V
0.3 To
switching function
body control slow
switching function with snap locking
no
electronic output
no
forced opening
yes
number of safety auxiliary contacts
One
the number of contacts of the rest
One
number of closing contacts
One
number of contacts inverters
Zero
interface type
without
execution of the interface for secure communication
without
the shape of the box
block
the material of the box
plastic
coating box
other
the execution of the drive element
other
alignment of the drive element
other
execution of the electrical connection
other
with status indicator
no
suitable for safety functions
yes
category of explosion protection for gas
without
category explosion protection for dust
without
the ambient temperature during operation
25 - 70
degree of protection (IP)
IP65
type of protection (NEMA)
Thirteen

Approvals

Product Standards
IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14; CE marking
UL File No.
E29184
UL Category Control No.
NKCR
CSA File No.
Twelve thousand five hundred twenty eight
CSA Class No.
3211-03
North America Certification
UL listed, CSA certified
Degree of Protection
IEC: IP65, UL/CSA Type 3R, 4X (indoor use only), 12, 13

Size

1310DIM-30

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.