ANUNCIAR
P1-40/V/SVB 199952 Y7-199952 EATON ELECTRIC P1-40/V/SVB View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

P1-40/V/SVB 199952 Y7-199952 EATON ELECTRIC P1-40/V/SVB

P1-40/V/SVB

199952

Y7-199952

EATON-MOELLER

P1-40/V/SVB

Main switch, P1, 40 A, rear mounting, 3 pole, Emergency switching off function, With red rotary handle and yellow locking ring, Lockable in the 0 (Off) position

Main switch, P1, Rated uninterrupted current (Iu): 40 A, Functions: Emergency switching off function, Interlockable, Fitted with: Red rotary handle and yellow locking ring, Auxiliary contact, Mounting method: Rear mounting, Number of poles: Three-pole, Locking facility: Lockable in the 0 (Off) position, Degree of Protection: IP65

More details


Low-voltage industrial components > Switch disconnector

Disconnectors and Cam Switches

Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total: $125.49
Unit price: $125.49
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Main switch, P1, 40 A, rear mounting, 3 pole, Emergency switching off function, With red rotary handle and yellow locking ring, Lockable in the 0 (Off) position
Main switch, P1, Rated uninterrupted current (Iu): 40 A, Functions: Emergency switching off function, Interlockable, Fitted with: Red rotary handle and yellow locking ring, Auxiliary contact, Mounting method: Rear mounting, Number of poles: Three-pole, Locking facility: Lockable in the 0 (Off) position, Degree of Protection: IP65

General specifications
Product name
Eaton Moeller® series P1 Main switch
Part no.
P1-40/V/SVB
EAN
4015082953027
Product Length/Depth
90 millimetre
Product height
70 millimetre
Product width
54 millimetre
Product weight
0.265 kilogram
Compliances
UKCA
CE
Certifications
IEC/EN 60204
IEC/EN 60947
IEC/EN 60947-3
Product Tradename
P1
Product Type
Main switch
Product Sub Type
None
Catalog Notes
Rated Short-time Withstand Current (Icw) for a time of 1 second
Features & Functions
Features
Version as main switch
Version as maintenance-/service switch
Version as emergency stop installation
Fitted with:
Red rotary handle and yellow locking ring
Auxiliary contact
Functions
Emergency switching off function
Interlockable
Locking facility
Lockable in the 0 (Off) position
Number of poles
3
General information
Degree of protection
IP65
Degree of protection (front side)
IP65
Lifespan, mechanical
300,000 Operations
Mounting method
Rear mounting
Mounting position
As required
Operating frequency
50 Operations/h
Overvoltage category
III
Pollution degree
3
Rated impulse withstand voltage (Uimp)
6000 V AC
Safe isolation
440 V AC, Between the contacts, According to EN 61140
Shock resistance
15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Switching angle
90 °
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
50 °C
Ambient operating temperature (enclosed) - min
-25 °C
Ambient operating temperature (enclosed) - max
40 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
Terminal capacity
1 x (1 - 4) mm², flexible with ferrules to DIN 46228
2 x (1 - 4) mm², flexible with ferrules to DIN 46228
1 x 10 mm² with fork terminal
2 x 10 mm² with fork terminal
Screw size
M4, Terminal screw
Tightening torque
1.6 Nm, Screw terminals
Electrical rating
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)
290 kA
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)
130 kA
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V
30 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
30 A
Rated operational current (Ie) at AC-3, 660 V, 690 V
17 A
Rated operational current (Ie) at AC-21, 440 V
40 A
Rated operational current (Ie) at AC-23A, 230 V
40 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V
40 A
Rated operational current (Ie) at AC-23A, 690 V
20 A
Rated operational power at AC-3, 380/400 V, 50 Hz
15 kW
Rated operational power at AC-3, 415 V, 50 Hz
15 kW
Rated operational power at AC-3, 690 V, 50 Hz
15 kW
Rated operational power at AC-23A, 220/230 V, 50 Hz
11 kW
Rated operational power at AC-23A, 400 V, 50 Hz
22 kW
Rated operational power at AC-23A, 690 V, 50 Hz
18.5 kW
Rated operational voltage (Ue) at AC - min
690 V
Rated operational voltage (Ue) at AC - max
690 V
Rated uninterrupted current (Iu)
40 A
Uninterrupted current
Rated uninterrupted current Iu is specified for max. cross-section.
Short-circuit rating
Rated conditional short-circuit current (Iq)
80 kA
Rated short-time withstand current (Icw)
0.64 kA
640 A, Contacts, 1 second
Short-circuit protection rating
50 A gG/gL, Fuse, Contacts
Switching capacity
Load rating
1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor)
1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor)
2 x Iₑ (with intermittent operation class 12, 25 % duty factor)
Contacts
Control circuit reliability
1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Actuator
Actuator color
Red
Actuator type
Door coupling rotary drive
Design verification
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
1.9 W
Rated operational current for specified heat dissipation (In)
40 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
UV resistance only in connection with protective shield.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Switch disconnector (low voltage) (EC000216)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Switch disconnector (ecl@ss13-27-37-14-03 [AKF060018])
Version as main switch
Yes
Version as maintenance-/service switch
Yes
Version as safety switch
No
Version as emergency stop installation
Yes
Version as reversing switch
No
Number of switches
1
Max. rated operation voltage Ue AC
690 V
Rated operating voltage
690 V
Rated permanent current Iu
40 A
Rated permanent current at AC-23, 400 V
40 A
Rated permanent current at AC-21, 400 V
40 A
Rated operation power at AC-3, 400 V
15 kW
Rated short-time withstand current lcw
0.64 kA
Rated operation power at AC-23, 400 V
22 kW
Switching power at 400 V
22 kW
Conditioned rated short-circuit current Iq
80 kA
Number of poles
3
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Motor drive optional
No
Motor drive integrated
No
Voltage release optional
No
Device construction
Built-in device fixed built-in technique
Suitable for floor mounting
No
Suitable for front mounting 4-hole
No
Suitable for front mounting centre
No
Suitable for distribution board installation
No
Suitable for intermediate mounting
No
Colour control element
Red
Type of control element
Door coupling rotary drive
Interlockable
Yes
Type of electrical connection of main circuit
Screw connection
With pre-assembled cabling
No
Degree of protection (IP), front side
IP65
Degree of protection (NEMA)
Width
54 mm
Height
70 mm
Depth
90 mm
Width in number of modular spacings

ETIM for 199952 Low-voltage industrial controls and switchgear (EC000216)
Feature Name Feature Value
Version as main switch (EF006981) Yes
Version as maintenance-/service switch (EF006986) Yes
Version as safety switch (EF006985) No
Version as emergency stop installation (EF006959) Yes
Version as reversing switch (EF009408) No
Number of switches (EF005586) 1
Max. rated operation voltage Ue AC (EF007355) 690 V
Rated operating voltage (EF001435) 690 V
Rated permanent current Iu (EF001389) 40 A
Rated permanent current at AC-23, 400 V (EF011777) 40 A
Rated permanent current at AC-21, 400 V (EF009165) 40 A
Rated operation power at AC-3, 400 V (EF001364) 15 kW
Rated short-time withstand current lcw (EF007050) 0.64 kA
Rated operation power at AC-23, 400 V (EF007027) 22 kW
Switching power at 400 V (EF009166) 22 kW
Conditioned rated short-circuit current Iq (EF001444) 80 kA
Number of poles (EF001391) 3
Number of auxiliary contacts as normally closed contact (EF001377) 0
Number of auxiliary contacts as normally open contact (EF001376) 0
Number of auxiliary contacts as change-over contact (EF003531) 0
Motor drive optional (EF007386) No
Motor drive integrated (EF006697) No
Voltage release optional (EF007491) No
Device construction (EF008240) Built-in device fixed built-in technique
Suitable for front mounting 4-hole (EF007247) No
Suitable for front mounting centre (EF007248) No
Suitable for distribution board installation (EF007262) No
Suitable for intermediate mounting (EF007264) No
Colour control element (EF007167) Red
Type of control element (EF006976) Door coupling rotary drive
Interlockable (EF006281) Yes
Type of electrical connection of main circuit (EF006819) Screw connection
With pre-assembled cabling (EF016444) No
Degree of protection (IP), front side (EF003118) IP65
Width (EF000008) 54 mm
Height (EF000040) 70 mm
Depth (EF000049) 90 mm

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.