KLV-60HWS-SF 302417 EATON ELECTRIC Hollow wall compact distribution board 5-rows 60MU super-flat sheet steel.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

KLV-60HWS-SF 302417 EATON ELECTRIC Hollow wall compact distribution board 5-rows 60MU super-flat sheet steel..

KLV-60HWS-SF

302417

Y7-302417

EATON-MOELLER

KLV-60HWS-SF

Eaton xComfort KLV LV systems Final Distribution Boards. Hollow wall compact distribution board, 5-rows, 60MU, super-flat sheet steel door, SK screw terminal

More details


Compact Distribution Boxes

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $180.73
Unit price: $180.73

Quantity Price
1+$180.73
2+$168.42
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Viewed products


Best sellers

More info



General specifications

Product Name
Eaton xComfort KLV energy distribution board
Catalog Number
302417
Model Code
KLV-60HWS-SF
EAN
9010238160859
Product Length/Depth
100 mm
Product Height
840 mm
Product Width
360 mm
Product Weight
6.92 kg
Compliances
RoHS conform
Certifications
IEC/EN 62208
IEC/EN 60670-24 (PD)

Delivery program

Type
Basic deviceInstallation distribution boardsKLV energy
Application
Indoor
Color
Traffic white (RAL 9016)
White

Technical data - electrical

Voltage rating at AC
400 V AC
Frequency rating of contacts
50 Hz

Technical data - mechanical

Closure type
Other
Enclosure material
Plastic
Width in number of modular spacings
12
Mounting method
Hollow-wall mounting
Hollow wall
DIN-rail
Material
Polystyren (plastic)
Sheet steel, powder-coated
Number of module space units per row
12
Number of rows
5
Terminal type
Screw terminals
PE and N terminal number and cross section
N - Fi: 2 x (0.75 mm² - 16 mm²) + 2 x (0.75 mm² - 25 mm²)
N: 25 x (0.75 mm² - 16 mm²)
PE: 25 x (0.75 mm² - 16 mm²)
Built-in depth
80 mm
Built-in height
0 mm
Built-in width
0 mm
Internal depth
80 mm
Cable entry postion
Cable entries on top and bottom, side, back plate
Cover/door color
White
Cover/door model
With notch
Cover/door type
Door
Single
Module rack type
Rail frame
Protective shrouding material
Plastic

Temperature-rise verification as per IEC 60890

Heat diss. ambient 35°C delta T:20°C flush mount individ. encl. top(IEC 60890)
28 W
Heat diss. ambient 35°C delta T:35°C flush mount individ. encl. top(IEC 60890)
58 W

Design verification as per IEC/EN 61439 - technical data

Ambient operating temperature details
-5 °C - 40 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
850 °C; meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2.6 Mechanical impact
IK05
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP30
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 400 V AC
10.9.3 Impulse withstand voltage
4 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.

Additional information

Fitted with:
Installation instructions
Cable retainer
Spirit level for leveling
Front cover
Imprintable sheet
Wall trough
Device support rails
Door/Frame
3D adjustment element for mounting designed to adjust the mounting depth by up to 18 mm
Neutral and protective conductor terminals with SK screw terminal technology
Hollow-wall anchor
Functions
Basic device
Extension possible
Protection class
II (totally insulated)
RAL-number
9016
Special features
IP30Protection Class IIPlastic enclosure with sheet steel door, white (RAL 9016)
Used with
Installation distribution boards
KLV energy
Basic device

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.