Product name
Eaton Moeller® series CI-K Insulated enclosure
Product Length/Depth
181 millimetre
Product height
145 millimetre
Product width
100 millimetre
Product weight
0.43 kilogram
Certifications
IEC/EN 60947-3
UL
UL File No.: E54120
UL Category Control No.: MITW2
CSA
CSA Class No.: 3211-07
UL 508
CSA-C22.2 No. 94
CE
CSA File No.: 012528
CSA-C22.2 No. 14-05
Product Type
Insulated enclosure
Catalog Notes
Approved for UL, CSA
Enclosure color
Black (RAL 9005)
Light gray, Operator (RAL 7035)
Enclosure material
Plastic
Knockouts
4 x ½ inch knockouts
Degree of protection
IP65
NEMA 12
Degree of protection (front side)
IP65
Product category
Basic enclosures
Surface treatment
Resistant to corrosion
Ambient conditions, mechanical
Temperature resistance
-40 - 80 °C (gasket)
-40 - 120 °C (enclosure)
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
18.5 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Not applicable.
10.2.6 Mechanical impact
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Is the panel builder's responsibility.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.