Q18LF-BL/WB 087860 EATON MOELLER Indicator light, flush, blue, +filament lamp, 24 V View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

Q18LF-BL/WB 087860 EATON MOELLER Indicator light, flush, blue, +filament lamp, 24 V

Q18LF-BL/WB

087860

EATON - MOELLER

10

Available

Ship on today

Indicator light, flush, blue, +filament lamp, 24 V

More details


Signaling Signalization Rotating Beacons

Pushbuttons - EATON - MOELLER

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON - MOELLER

Quantity Price
10+$9.06
20+$8.73
40+$8.47
50+$8.40
70+$8.31
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Delivery programme
Product range
    RMQ16 (drilling dimensions 16 mm)
Basic function
    Indicator lights
Single unit/Complete unit
    Single unit
Design
    Flat
Colour
     
Lens
    Blue
Lens
   
General
Standards
    IEC/EN 60947
Degree of protection, IEC/EN 60529
    IP65
Climatic proofing
    Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
     
Open
  °C -25 - +60
Enclosed
  °C - 25 - 40
Mounting position
    As required
Mechanical shock resistance
  g > 40
according to IEC 60068-2-27
Shock duration 11 ms
Sinusoidal
Terminal capacities
  mm2 0.5 - 1.0
Blade terminal
    2.8 x 0.8 mm to DIN 46244
Fast-on connectors
    2.8 x 0.8 mm to DIN 46247 and IEC 60760
Contacts
Rated impulse withstand voltage
Uimp V AC 800
Rated insulation voltage
Ui V 250
Overvoltage category/pollution degree
    III/3
Rated operational voltage
Ue V AC 24
Use of insulated ferrule ISH 2,8
    >24 V AC/DC recommended
>50 V AC or 120 V DC is mandatory, even on unused blade terminals
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
     
Rated operational current for specified heat dissipation
In A 0
Heat dissipation per pole, current-dependent
Pvid W 0
Equipment heat dissipation, current-dependent
Pvid W 0
Static heat dissipation, non-current-dependent
Pvs W 1
Heat dissipation capacity
Pdiss W 0
Operating ambient temperature min.
  °C -25
Operating ambient temperature max.
  °C 60
IEC/EN 61439 design verification
     
10.2 Strength of materials and parts
     
10.2.2 Corrosion resistance
    Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
    Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
    Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
    Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
    Please enquire
10.2.5 Lifting
    Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
    Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
    Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
    Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
    Meets the product standard's requirements.
10.5 Protection against electric shock
    Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
    Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
    Is the panel builder's responsibility.
10.8 Connections for external conductors
    Is the panel builder's responsibility.
10.9 Insulation properties
     
10.9.2 Power-frequency electric strength
    Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
    Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
    Is the panel builder's responsibility.
10.10 Temperature rise
    The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
    Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
    Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
    The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Front element for indicator light (EC000223)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Command and alarm device / Front element for warning lights ([email protected] [AKF029011])
Suitable for number of built-in signal lights
    1
Colour lens
    Blue
Construction type lens
    Square
Hole diameter
  mm 16
Width opening
  mm 16
Height meter opening
  mm 6
With front ring
    Yes
Material front ring
    Plastic
Colour front ring
    Black
Type of lens
    Flat
Degree of protection (IP), front side
    IP65
Approvals
Product Standards     IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14-05; CE marking
UL File No.     E29184
UL Category Control No.     NKCR
CSA File No.     46552
CSA Class No.     3211-03
North America Certification     UL listed, CSA certified
Degree of Protection     UL/CSA Type 1
Dimensions
IL04716016Z (AWA1160-1429) Mounting of components
 
>>

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Últimas Opiniones de Nuestros Clientes

Todas las valoraciones que recibimos de los artículos que ofrecemos son reales y están verificadas. Un pequeño gesto, pero de mucho valor. Por eso, te agradecemos ese minuto que inviertes en dejarnos tu opinión y calificación sobre los productos, porque nos ayuda a seguir mejorando y a ofrecerte un servicio de todavía mayor calidad.