QSA100N1-00/3 1318546 EATON ELECTRIC Switch-disconnector-fuse, 3 pole, 100 A, rear mounting, NH00 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

QSA100N1-00/3 1318546 EATON ELECTRIC Switch-disconnector-fuse, 3 pole, 100 A, rear mounting, NH00

QSA100N1-00/3

1318546

EATON-MOELLER

Switch-disconnector-fuse, 3 pole, 100 A, rear mounting, NH00

QSA100N1-00/3

Fuse switch-disconnector, 3 pole, rear mounting, 100 A, NH000/NH00

More details


Low-voltage industrial components > Fuse switch disconnector

DUMECO Switch-Disconnectors

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $252.96
Unit price: $252.96

Quantity Price
1+$252.96
2+$247.54
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Fuse switch-disconnector, 3 pole, rear mounting, 100 A, NH000/NH00
Fuse switch-disconnector QSA100N1-00/3, ?frame size 1 suitable for DIN fuse-links (blade contacts type).

Delivery program

Product range
Fuse-switch-disconnector
Main switch
maintenance switch
Part group reference
QSA
Stop Function
optional
Notes
Suitable for DIN fuse-links (blade contacts type)
Information about equipment supplied
Auxiliary contact or neutral conductor fitted by user.
Number of poles
3 pole
Auxiliary contacts
0 N/O
0 N/C
Degree of Protection
IP00
IP20 with terminal cover
Design
rear mounting
000Z429
Contact sequence
115S262
Rated uninterrupted current [Iu]
100 A
Note on rated uninterrupted current !u
Rated uninterrupted current Iuis specified for max. cross-section.
Fuse cartridge
NH000/NH00 Size

Technical data

General
Standards
IEC/EN 60947, VDE 0660, IEC/EN 60204
Switch-disconnector according to IEC/EN 60947-3
Certifications
CE, RoHs
Ambient temperatureOperation [ϑ]
-25 - +55 °C
Ambient temperatureStorage [ϑ]
-30 - +80 °C
Overvoltage category/pollution degree
III/3
Rated impulse withstand voltage [Uimp]
6 kV
Rated insulation voltage [Ui]
690 V
Mounting position
As required
Contacts
Mechanical variablesNumber of poles
3 pole
Mechanical variablesAuxiliary contacts
0 N/O
Mechanical variablesAuxiliary contacts
0 N/C
Electrical characteristicsRated operational voltage [Ue]
690 V AC
Electrical characteristicsRated uninterrupted current [Iu]
100 A
Electrical characteristicsNote on rated uninterrupted current !u
Rated uninterrupted current Iuis specified for max. cross-section.
Heat dissipation per pole, current-dependent [Pvid]
6 W

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
100 A
Heat dissipation per pole, current-dependent [Pvid]
6 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
0 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+55 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Fuse switch disconnector (EC001040)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Fuse switch disconnector ([email protected] [AKF058013])
Version as main switch
Yes
Version as safety switch
No
Max. rated operation voltage Ue AC
690 V
Rated permanent current Iu
100 A
Rated operation power at AC-23, 400 V
55 kW
Conditioned rated short-circuit current Iq
50 kA
Rated short-time withstand current lcw
0 kA
Suitable for fuses
NH00
Number of poles
3
With error protection
No
Type of electrical connection of main circuit
Screw connection
Cable entry
Other
Equipped with connectors
Yes
Suitable for ground mounting
Yes
Suitable for front mounting 4-hole
No
Suitable for busbar mounting
No
Type of control element
Other
Position control element
Front side
Motor drive optional
No
Motor drive integrated
No
Version as emergency stop installation
No
Degree of protection (IP), front side
IP00

Dimensions

1150DIM-91

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.