SPX700A0-4A2N1 125459 EATON ELECTRIC Variable frequency drive SVX 3-/3-phase 500 kW 480 V degree of protecti.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

SPX700A0-4A2N1 125459 EATON ELECTRIC Variable frequency drive SVX 3-/3-phase 500 kW 480 V degree of protecti..

SPX700A0-4A2N1

125459

EATON-MOELLER

Variable frequency drive SVX 3-/3-phase 500 kW 480 V; degree of protection IP00; integrated EMC filter

SPX700A0-4A2N1

Variable frequency drive, 400 V AC, 3-phase, 500 kW, IP00, OLED display, FR12

More details


Low-voltage industrial components > Frequency converter el 1 kV

Eaton Frequency Converters

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

* This article is restricted. Please ask us for a quotation and we will check if there are units available or we will offer you an alternative product.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Variable frequency drive, 400 V AC, 3-phase, 500 kW, IP00, OLED display, FR12
Variable frequency drive, Part group reference (e.g. DIL): SPX, Rated operational voltage: Ue = 400 V AC, 3-phase, 480 V AC, 3-phase, 500 V AC, 3-phase, Output voltage with Ve: U2 = 400 V AC, 3-phase, 480 V AC, 3-phase, 500 V AC, 3-phase, Mains voltage (50/60Hz): ULN = 380 (-15%) - 500 (+10%) V, Rated operational current At 150% overload: Ie = 920 A, Rated operational current At 110% overload: Ie = 1030 A, Note: Overload cycle for 60 s every 600 s, Assigned motor rating Note: For AC motors with internal and external ventilation with 50 Hz / 60 Hz, Overload cycle for 60 s every 600 s, at 400 V, 50 Hz , Assigned motor rating 150 % Overload: P = 500 kW, 110 % Overload: P = 560 kW, Assigned motor rating Note: at 440 - 480 V, 60 Hz, Assigned motor rating 150 % Overload: P = 700 HP, 110 % Overload: P = 800 HP, Degree of Protection: IP00, Fieldbus connection (optional): PROFIBUS-DP, LonWorks, CANopen®, DeviceNet, Modbus-TCP, BACnet/IP, Fitted with: OLED display, Frame size: FR12, Standards: Specification for general requirements: IEC/EN 61800-2, EMC requirements: IEC/EN 61800-3, Safety requirements: IEC/EN 61800-5-1

General specifications
Product name
Eaton SPX variable frequency drive
Part no.
SPX700A0-4A2N1
EAN
4015081230655
Product Length/Depth
115 millimetre
Product height
36.2 millimetre
Product width
96 millimetre
Product weight
550 kilogram
Certifications
RoHS, ISO 9001
IEC/EN 61800-3
Safety: EN 61800-5-1: 2003
UL Category Control No.: NMMS, NMMS2, NMMS7. NMMS8
CE
CSA Class No.: 3211-06
IEC/EN61800-5
Specification for general requirements: IEC/EN 61800-2
CUL
RCM
IEC/EN61800-3
UL
UL 508C
CSA-C22.2 No. 14
DNV
Certified by UL for use in Canada
UL report applies to both US and Canada
UL File No.: E134360
Product Tradename
SPX
Product Type
Variable frequency drive
Product Sub Type
None
Catalog Notes
Assigned motor rating: For AC motors with internal and external ventilation with 50 Hz / 60 Hz
Assigned motor rating: Overload cycle for 60 s every 600 s
General information
Degree of protection
IP00
NEMA Other
Electromagnetic compatibility
1st and 2nd environments (according to EN 61800-3)
Fitted with:
Control unit
PC connection
IGBT inverter
Internal DC link
OLED display
Frame size
FR12
Functions
4-quadrant operation possible
Mounting position
Vertical
Product Category
Variable frequency drives
Protection
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
Radio interference class
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Suitable for
Branch circuits, (UL/CSA)
Climatic environmental conditions
Altitude
Max. 3000 m
Max. 1000 m
Above 1000 m with 1 % performance reduction per 100 m
Ambient operating temperature - min
-10 °C
Ambient operating temperature - max
40 °C
Ambient operating temperature at 150% overload - min
-10 °C
Ambient operating temperature at 150% overload - max
40 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Climatic proofing
< 95 % relative humidity, no condensation, no corrosion, no dripping water
Main circuit
Mains voltage - min
380 V
Mains voltage - max
500 V
Operating mode
Sensorless vector control (SLV)
Optional: Vector control with feedback (CLV)
U/f control
Output frequency - min
0 Hz
Output frequency - max
320 Hz
Output voltage (U2)
500 V AC, 3-phase
400 V AC, 3-phase
480 V AC, 3-phase
Rated control supply voltage
10 V DC (Us, max. 10 mA)
Rated frequency - min
45 Hz
Rated frequency - max
66 Hz
Rated operational current (Ie) at 110% overload
1030 A
Rated operational current (Ie) at 150% overload
920 A
Rated operational power at 380/400 V, 50 Hz, 3-phase
500 kW
Rated operational power at 380/400 V, 50 Hz, 3-phase, 110% overload
560 kW
Rated operational voltage
400 V AC, 3-phase
480 V AC, 3-phase
500 V AC, 3-phase
Resolution
0.01 Hz (Frequency resolution, setpoint value)
Supply frequency
50/60 Hz
Switching frequency
3.6 kHz, 1 - 6 kHz adjustable, fPWM, Power section, Main circuit
System configuration type
AC supply systems with earthed center point
Voltage rating - max
480 V AC
Motor rating
Assigned motor power at 460/480 V, 60 Hz, 3-phase
700 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase, 110 % overload
800 HP
Control circuit
Number of inputs (analog)
2
Number of inputs (digital)
6
Number of outputs (analog)
1
Number of outputs (digital)
1
Number of relay outputs
2 (parameterizable, N/O, 8 A (24 V DC) / 8 A (250 V AC) / 0,4 A (125 V DC))
Rated control voltage (Uc)
24 V DC (external, max. 250 mA)
Communication
Communication interface
DeviceNet, optional
CANopen®, optional
BACnet/IP, optional
PROFIBUS-DP
LonWorks, optional
Modbus-TCP, optional
BACnet MS/TP, optional
EtherCAT, optional
Ethernet IP, optional
Modbus-RTU, optional
PROFINET, optional
Connection to SmartWire-DT
No
Protocol
PROFIBUS
Data-Highway
Other bus systems
DeviceNet
CAN
TCP/IP
LON
Design verification
Equipment heat dissipation, current-dependent Pvid
12500 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
920 A
Static heat dissipation, non-current-dependent Pvs
0 W
Heat dissipation details
Operation (with 150 % overload)
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.