Product successfully added to your shopping cart
DC1-12011FB-A20N
169252
EATON-MOELLER
1
Variable Frequency Drive, 1-/3- 230 V, 10.5 A, 2.2 kW, EMC-Filter, Brake-Chopper
Power XL Frequency Converters
* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Product range | Variable frequency drives | ||
Part group reference (e.g. DIL) | DC1 | ||
Rated operational voltage | Ue | 230 V AC, 1-phase 240 V AC, single-phase | |
Output voltage with Ve | U2 | 230 V AC, 3-phase 240 V AC, 3-phase | |
Mains voltage (50/60Hz) | ULN | V | 200 (-10%) - 240 (+10%) |
Rated operational current | |||
At 150% overload | Ie | A | 10.5 |
Note | Rated operational current at an operating frequency of 16 kHz and an ambient air temperature of +50 °C | ||
Note | Overload cycle for 60 s every 600 s | ||
Assigned motor rating | |||
Note | for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1at 50 Hz or 1800 min-1at 60 Hz | ||
Note | Overload cycle for 60 s every 600 s | ||
Note | at 230 V, 50 Hz | ||
150 % Overload | P | kW | 2.2 |
150 % Overload | IM | A | 8.7 |
Note | at 220 - 240 V, 60 Hz | ||
150 % Overload | P | HP | 3 |
150 % Overload | IM | A | 9.6 |
Degree of Protection | IP20/NEMA 0 | ||
Interface/field bus (built-in) | OP-Bus (RS485)/Modbus RTU, CANopen® | ||
Fieldbus connection (optional) | SmartWire-DT | ||
Fitted with | Radio interference suppression filter Brake chopper 7-digital display assembly | ||
Frame size | FS2 | ||
Connection to SmartWire-DT | with SmartWire-DT module DX-NET-SWD3 |
General | |||
Standards | Specification for general requirements: IEC/EN 61800-2 EMC requirements: IEC/EN 61800-3 Safety requirements: IEC/EN 61800-5-1 | ||
Certifications | CE, UL, cUL, c-Tick, Ukr Sepro, EAC | ||
Production quality | RoHS, ISO 9001 | ||
Climatic proofing | ρw | % | < 95%, average relative humidity (RH), non-condensing, non-corrosive |
Ambient temperature | |||
operation (150 % overload) | ϑ | °C | -10 - +50 |
-10 - +45 °C for UL compliance over a period of 24 hours. | |||
Storage | ϑ | °C | -40 - +60 |
Radio interference level | |||
Radio interference class (EMC) | C1, C2, C3, depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. | ||
Environment (EMC) | 1st and 2nd environments | ||
maximum motor cable length | I | m | C1 ≤ 1 m C2 ≤ 5 m C3 ≤ 25 m |
Mounting position | Vertical | ||
Altitude | m | 0 - 1000 m above sea level Above 1000 m: 1% derating for every 100 m max. 4000 m | |
Degree of Protection | IP20/NEMA 0 | ||
Protection against direct contact | BGV A3 (VBG4, finger- and back-of-hand proof) | ||
Main circuit | |||
Supply | |||
Rated operational voltage | Ue | 230 V AC, 1-phase 240 V AC, single-phase | |
Mains voltage (50/60Hz) | ULN | V | 200 (-10%) - 240 (+10%) |
Input current (150% overload) | ILN | A | 19.5 |
System configuration | AC supply systems with earthed center point | ||
Supply frequency | fLN | Hz | 50/60 |
Frequency range | fLN | Hz | 48 - 62 |
Mains switch-on frequency | Maximum of one time every 30 seconds | ||
Power section | |||
Function | Frequency inverter with internal DC link and IGBT inverter | ||
Overload current (150% overload) | IL | A | 15.75 |
max. starting current (High Overload) | IH | % | 175 |
Note about max. starting current | for 2 seconds every 20 seconds | ||
Output voltage with Ve | U2 | 230 V AC, 3-phase 240 V AC, 3-phase | |
Output Frequency | f2 | Hz | 0 - 50/60 (max. 500) |
Switching frequency | fPWM | kHz | 16 adjustable 4 - 32 (audible) |
Operation Mode | U/f control Speed control with slip compensation | ||
Frequency resolution (setpoint value) | Δf | Hz | 0.1 |
Rated operational current | |||
At 150% overload | Ie | A | 10.5 |
Note | Rated operational current at an operating frequency of 16 kHz and an ambient air temperature of +50 °C | ||
Power loss | |||
Heat dissipation at rated operational current | PV | W | 103.4 |
Efficiency | η | % | 95.3 |
Maximum leakage current to ground (PE) without motor | IPE | mA | 2.49 |
Fitted with | Radio interference suppression filter Brake chopper 7-digital display assembly | ||
Frame size | FS2 | ||
Motor feeder | |||
Note | for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1at 50 Hz or 1800 min-1at 60 Hz | ||
Note | Overload cycle for 60 s every 600 s | ||
Note | at 230 V, 50 Hz | ||
150 % Overload | P | kW | 2.2 |
Note | at 220 - 240 V, 60 Hz | ||
150 % Overload | P | HP | 3 |
maximum permissible cable length | I | m | screened: 100 screened, with motor choke: 200 unscreened: 150 unscreened, with motor choke: 300 |
Apparent power | |||
Apparent power at rated operation 230 V | S | kVA | 4.18 |
Apparent power at rated operation 240 V | S | kVA | 4.36 |
Braking function | |||
Standard braking torque | max. 30 % MN | ||
DC braking torque | adjustable to 100 % | ||
Braking torque with external braking resistance | Max. 100% of rated operational current Iewith external braking resistor | ||
minimum external braking resistance | Rmin | Ω | 47 |
Switch-on threshold for the braking transistor | UDC | V | 390 V DC |
Control section | |||
Reference voltage | Us | V | 10 V DC (max. 10 mA) |
Analog inputs | 2, parameterizable, 0 - 10 V DC, 0/4 - 20 mA | ||
Analog outputs | 1, parameterizable, 0 - 10 V | ||
Digital inputs | 4, parameterizable, max. 30 V DC | ||
Digital outputs | 1, parameterizable, 24 V DC | ||
Relay outputs | 1, parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1) | ||
Interface/field bus (built-in) | OP-Bus (RS485)/Modbus RTU, CANopen® | ||
Assigned switching and protective elements | |||
Power Wiring | |||
IEC (Type B, gG), 150 % | FAZ-B25/1N | ||
UL (Class CC or J) | A | 25 | |
150 % overload (CT/IH, at 50 °C) | DX-LN1-024 | ||
Motor feeder | |||
150 % overload (CT/IH, at 50 °C) | DX-LM3-011 | ||
150 % overload (CT/IH, at 50 °C) | DX-SIN3-016 | ||
10 % duty factor (DF) | DX-BR050-0K4 | ||
20 % duty factor (DF) | DX-BR050-0K8 | ||
40 % duty factor (DF) | DX-BR047-3K1 |
Technical data for design verification | |||
Rated operational current for specified heat dissipation | In | A | 10.5 |
Heat dissipation per pole, current-dependent | Pvid | W | 0 |
Equipment heat dissipation, current-dependent | Pvid | W | 103.4 |
Static heat dissipation, non-current-dependent | Pvs | W | 0 |
Heat dissipation capacity | Pdiss | W | 0 |
Operating ambient temperature min. | °C | -10 | |
Operating ambient temperature max. | °C | 50 | |
IEC/EN 61439 design verification | |||
10.2 Strength of materials and parts | |||
10.2.2 Corrosion resistance | Meets the product standard's requirements. | ||
10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. | ||
10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. | ||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | Meets the product standard's requirements. | ||
10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. | ||
10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.7 Inscriptions | Meets the product standard's requirements. | ||
10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.4 Clearances and creepage distances | Meets the product standard's requirements. | ||
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. | ||
10.8 Connections for external conductors | Is the panel builder's responsibility. | ||
10.9 Insulation properties | |||
10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. | ||
10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. | ||
10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. | ||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | ||
10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. | ||
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. | ||
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Low-voltage industrial components (EG000017) / Frequency converter =< 1 kV (EC001857) | |||
Electric engineering, automation, process control engineering / Electrical drive / Static frequency converter / Static frequency converter = < 1 kv ([email protected] [AKE177011]) | |||
Mains voltage | V | 200 - 240 | |
Mains frequency | 50/60 Hz | ||
Number of phases input | 1 | ||
Number of phases output | 3 | ||
Max. output frequency | Hz | 500 | |
Max. output voltage | V | 230 | |
Rated output current I2N | A | 11 | |
Max. output at quadratic load at rated output voltage | kW | 2.2 | |
Max. output at linear load at rated output voltage | kW | 2.2 | |
With control unit | Yes | ||
Application in industrial area permitted | Yes | ||
Application in domestic- and commercial area permitted | Yes | ||
Supporting protocol for TCP/IP | No | ||
Supporting protocol for PROFIBUS | No | ||
Supporting protocol for CAN | Yes | ||
Supporting protocol for INTERBUS | No | ||
Supporting protocol for ASI | No | ||
Supporting protocol for KNX | No | ||
Supporting protocol for MODBUS | Yes | ||
Supporting protocol for Data-Highway | No | ||
Supporting protocol for DeviceNet | No | ||
Supporting protocol for SUCONET | No | ||
Supporting protocol for LON | No | ||
Supporting protocol for PROFINET IO | No | ||
Supporting protocol for PROFINET CBA | No | ||
Supporting protocol for SERCOS | No | ||
Supporting protocol for Foundation Fieldbus | No | ||
Supporting protocol for EtherNet/IP | No | ||
Supporting protocol for AS-Interface Safety at Work | No | ||
Supporting protocol for DeviceNet Safety | No | ||
Supporting protocol for INTERBUS-Safety | No | ||
Supporting protocol for PROFIsafe | No | ||
Supporting protocol for SafetyBUS p | No | ||
Supporting protocol for other bus systems | No | ||
Number of HW-interfaces industrial Ethernet | 0 | ||
Number of HW-interfaces PROFINET | 0 | ||
Number of HW-interfaces RS-232 | 0 | ||
Number of HW-interfaces RS-422 | 0 | ||
Number of HW-interfaces RS-485 | 1 | ||
Number of HW-interfaces serial TTY | 0 | ||
Number of HW-interfaces USB | 1 | ||
Number of HW-interfaces parallel | 0 | ||
Number of HW-interfaces other | 0 | ||
With optical interface | No | ||
With PC connection | Yes | ||
Integrated breaking resistance | Yes | ||
4-quadrant operation possible | No | ||
Type of converter | U converter | ||
Degree of protection (IP) | IP20 | ||
Height | mm | 231 | |
Width | mm | 107 | |
Depth | mm | 152 | |
Relative symmetric net frequency tolerance | % | 5 | |
Relative symmetric net current tolerance | % | 10 |
Product Standards | UL 508C; CSA-C22.2 No. 14; IEC/EN61800-3; IEC/EN61800-5; CE marking | ||
UL File No. | E172143 | ||
UL Category Control No. | NMMS, NMMS7 | ||
CSA File No. | UL report applies to both US and Canada | ||
North America Certification | UL listed, certified by UL for use in Canada | ||
Specially designed for North America | No | ||
Suitable for | Branch circuits | ||
Max. Voltage Rating | 1~ 240 V AC IEC: TN-S UL/CSA: Y (Solidly Grounded Wey) | ||
Degree of Protection | IEC: IP20 |
Title: | Size: | Type: |
---|---|---|
PDF EATON STARTING CONTROLLING MOTORS EN.pdf | 32 Mbytes | |
DC1-12011FB-A20N 169252 169252_EN.pdf | 257 Kbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.