ANUNCIAR
EU6E-SWD-2D2D-2 183265 Y7-183265 EATON ELECTRIC SWD Block module I/O module IP69K, 24 V DC, 2 inputs with po.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

EU6E-SWD-2D2D-2 183265 Y7-183265 EATON ELECTRIC SWD Block module I/O module IP69K, 24 V DC, 2 inputs with po..

EU6E-SWD-2D2D-2

183265

Y7-183265

EATON-MOELLER

SWD Block module I/O module IP69K, 24 V DC, 2 inputs with power supply, 2 outputs 2A with separate power supply, 4 M12 I/O sockets

EU6E-SWD-2D2D-2

SWD module with IP69K degree of protection for connecting 2 digital inputs and 2 digital outputs, sensor supply for each M12 socket: 24 VDC, 70 mA, short-circuit proof, automatic address setting, outputs 24 V DC 2A short-circuit proof, separate M22 connector for output supply, I/O connection with M12 socket for each in-/output

More details


PLC's > Fieldbus, decentr. periphery - digital I/O module

Smartwire Darwin

Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total: $402.07
Unit price: $402.07
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



General specifications

Product Name
Eaton EU6E I/O module
Catalog Number
183265
Model Code
EU6E-SWD-2D2D-2
EAN
4015081781980
Product Length/Depth
34 mm
Product Height
156.8 mm
Product Width
60.8 mm
Product Weight
0.25 kg
Certifications
IEC/EN 61131-2
CSA
UL
Catalog Notes
with supply

Features & Functions

Electric connection type
Screw connection
Features
Fieldbus connection over separate bus coupler possible
Overload protection (sensor supply)
Short-circuit protection (sensor supply)
Overload proof (with diagnostics)
Functions
Short-circuit protection, outputs available
For connection of digital I/O signals

General

Current consumption
50 mA, SmartWire-DT network, 24 V, without sensor and without I/O supply
70 mA, Max. current consumption per M12 I/O plug, Sensor supply, SmartWire-DT network
Degree of protection
IP69K
Mounting method
Wall mounting/direct mounting
Screw fixing (M4)
Overvoltage category
II
Pollution degree
3
Product category
SmartWire-DT slave
Type
Digital modules
Voltage type
DC

Ambient conditions, mechanical

Constant acceleration
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
Constant amplitude
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
As required
Shock resistance
30 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
50 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Climatic proofing
Dry heat to IEC 60068-2-2
Damp heat, constant, to IEC 60068-2-3
Environmental conditions
Condensation: permissible
Operating temperature - min
-25 °C
Operating temperature - max
50 °C
Relative humidity
5 - 95 % (non-condensing, IEC/EN 60068-2-30)

Electro magnetic compatibility

Air discharge
8 kV, according to IEC 61131-2, level 3, ESD
Burst impulse
2 kV, Supply cable, according to IEC/EN 61131-2, Level 3
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3
1 kV, Signal cable, according to IEC/EN 61131-2, Level 3
Contact discharge
4 kV, according to IEC/EN 61131-2, Level 2, ESD
Electromagnetic fields
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
Radiated RFI
10 V (IEC/EN 61131-2:2008, Level 3)
Radio interference class
Class A (EN 55011)
Surge rating
1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
0.5 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC

Electrical rating

Input current
4 mA (at 24 V DC, Digital inputs)
Input current at signal 1
4 mA
Output current
2 A
Power loss
1.3 W
Short-circuit tripping current
Max. 6 A over 3 ms, Digital semi-conductor outputs
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at DC - min
20.4 VDC
Supply voltage at DC - max
28.8 VDC

Communication

Connection to SmartWire-DT
Yes
Connection type
SWD-OUT: M12 socket (A-keyed), 5 pole
SWD-IN : M12 plug (A-keyed), 5 pole
5-pin M12 socket (A-keyed), Supply and I/O sensor
Data transfer rate
Setting automatically
2 MBit/s, SmartWire-DT
LED indicator
Status indication of SmartWire-DT network: Green LED
Status indication of input: Yellow LED
Protocol
Other bus systems
Station
SmartWire-DT slave, SmartWire-DT network

Input/Output

Input delay
< 0.2 ms
Lamp load
≤ 3 W (at RLL)
Limit value type 1
High: > 15 V DC
Low: < 5 V DC
Number of inputs (digital)
2
Number of outputs (digital)
2
Output
2 Transistor Outputs
Switching capacity
IEC/EN 60947-5-1, utilization category DC-13, Digital outputs

Safety

Explosion safety category for dust
None
Explosion safety category for gas
None

Design verification

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1.3 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

ETIM for 183265 PLC's (EC001599)
Feature Name Feature Value
Supply voltage AC 50 Hz (EF007532) 0 V
Supply voltage AC 60 Hz (EF007533) 0 V
Supply voltage DC (EF007534) 20.4 V
Voltage type (supply voltage) (EF002991) DC
Number of digital inputs (EF001992) 2
Number of digital outputs (EF001993) 2
Digital inputs configurable (EF008516) No
Digital outputs configurable (EF008520) No
Input current at signal 1 (EF001428) 4 mA
Permitted voltage at input (EF007554) 20.4 V
Type of voltage (input voltage) (EF003033) DC
Type of digital output (EF003601) Other
Output current (EF003202) 2 A
Permitted voltage at output (EF007553) 20.4 V
Type of output voltage (EF008222) DC
Short-circuit protection, outputs available (EF003203) Yes
Number of HW-interfaces industrial Ethernet (EF003020) 0
Number of interfaces PROFINET (EF006932) 0
Number of HW-interfaces RS-232 (EF003021) 0
Number of HW-interfaces RS-422 (EF003022) 0
Number of HW-interfaces RS-485 (EF003023) 0
Number of HW-interfaces serial TTY (EF003024) 0
Number of HW-interfaces parallel (EF003026) 0
Number of HW-interfaces wireless (EF006933) 0
Number of HW-interfaces USB (EF003025) 0
Number of HW-interfaces other (EF003027) 0
With optical interface (EF003028) No
Supporting protocol for EtherCAT (EF017564) No
Supporting protocol for TCP/IP (EF003050) No
Supporting protocol for PROFIBUS (EF003052) No
Supporting protocol for CAN (EF003053) No
Supporting protocol for INTERBUS (EF003054) No
Supporting protocol for ASI (EF003051) No
Supporting protocol for KNX (EF003055) No
Supporting protocol for Modbus (EF003057) No
Supporting protocol for Data-Highway (EF003058) No
Supporting protocol for DeviceNet (EF003059) No
Supporting protocol for SUCONET (EF003060) No
Supporting protocol for LON (EF003017) No
Supporting protocol for PROFINET IO (EF007525) No
Supporting protocol for PROFINET CBA (EF007524) No
Supporting protocol for SERCOS (EF006657) No
Supporting protocol for Foundation Fieldbus (EF007522) No
Supporting protocol for EtherNet/IP (EF007521) No
Supporting protocol for AS-Interface Safety at Work (EF007519) No
Supporting protocol for DeviceNet Safety (EF007520) No
Supporting protocol for INTERBUS-Safety (EF006662) No
Supporting protocol for PROFIsafe (EF007526) No
Supporting protocol for SafetyBUS p (EF007527) No
Supporting protocol for other bus systems (EF003062) Yes
Radio standard Bluetooth (EF007178) No
Radio standard WLAN 802.11 (EF007179) No
Radio standard GPRS (EF008523) No
Radio standard GSM (EF008524) No
Radio standard UMTS (EF008525) No
IO link master (EF007298) No
System accessory (EF004118) Yes
Degree of protection (IP) (EF005474) IP69K
Type of electric connection (EF003961) Screw connection
Time delay at signal change (EF002382) 0.2 ms
Fieldbus connection over separate bus coupler possible (EF004002) Yes
Suitable for rail mounting (EF003972) No
Wall mounting/direct mounting (EF007020) Yes
Front built-in possible (EF007016) No
Rack-assembly possible (EF007018) No
Suitable for safety functions (EF001597) No
SIL according to IEC 61508 (EF009889) None
Performance level according to EN ISO 13849-1 (EF007399) None
Appendant operation agent (Ex ia) (EF004141) No
Appendant operation agent (Ex ib) (EF004142) No
Explosion safety category for gas (EF003997) None
Explosion safety category for dust (EF003998) None
Certified for UL hazardous location class I (EF017622) No
Certified for UL hazardous location class II (EF017625) No
Certified for UL hazardous location class III (EF017627) No
Certified for UL hazardous location division 1 (EF017628) No
Certified for UL hazardous location division 2 (EF017629) No
Certified for UL hazardous location group A (acetylene) (EF017632) No
Certified for UL hazardous location group B (hydrogen) (EF017633) No
Certified for UL hazardous location group C (ethylene) (EF017635) No
Certified for UL hazardous location group D (propane) (EF017636) No
Certified for UL hazardous location group E (metal dusts) (EF017637) No
Certified for UL hazardous location group F (carbonaceous dusts) (EF017638) No
Certified for UL hazardous location group G (non-conductive dusts) (EF017639) No
Width (EF000008) 60.8 mm
Height (EF000040) 156.8 mm
Depth (EF000049) 34 mm

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.