Standards
IEC/EN 60947, EN 60947-5-1, VDE 0660, UL, CSA
Lifespan, mechanicalDC operated [Operations]
20 x 106
Maximum operating frequency [Operations/h]
9000
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-25 - +60 °C
Ambient temperatureEnclosed
- 25 - 40 °C
Ambient temperatureAmbient temperature, storage
- 40 - 80 °C
Mounting positionMounting position
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msBasic unit with auxiliary contact moduleN/O contact
7 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msBasic unit with auxiliary contact moduleN/C contact
5 g
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
WeightDC operated
0.294 kg
Terminal capacitiesSpring-loaded terminalsSolid
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Terminal capacitiesSpring-loaded terminalsFlexible with or without ferrule DIN 46228
1 x (0,75 - 1.5)
2 x (0,75 - 1.5) mm2
Terminal capacitiesSpring-loaded terminalsSolid or stranded
18 - 14 AWG
Terminal capacitiesSpring-loaded terminalsStripping length
10 mm
Terminal capacitiesSpring-loaded terminalsStandard screwdriver
0.6 x 3.5 mm
Positive operating contacts to ZH 1/457, including auxiliary contact module
Yes
Rated impulse withstand voltage [Uimp]
6000 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
690 V AC
Rated operational voltage [Ue]
690 V AC
Safe isolation to EN 61140between coil and auxiliary contacts
400 V AC
Safe isolation to EN 61140between the auxiliary contacts
400 V AC
Rated operational currentConventional free air thermal current, 1 poleOpenat 60 °C [Ith=Ie]
16 A
Rated operational currentAC-15220 V 230 V 240 V [Ie]
4 A
Rated operational currentAC-15380 V 400 V 415 V [Ie]
4 A
Rated operational currentAC-15500 V [Ie]
1.5 A
Rated operational currentDC currentNotes
Switch-on and switch-off conditions based on DC-13, time constant as specified.
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:1 [24 V]
10 A
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:1 [60 V]
6 A
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:2 [60 V]
10 A
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:1 [110 V]
3 A
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:3 [110 V]
6 A
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:1 [220 V]
1 A
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:3 [220 V]
5 A
Rated operational currentDC currentDC L/R ≦ 50 msContacts in series:3 [24 V]
4 A
Rated operational currentDC currentDC L/R ≦ 50 msContacts in series:3 [60 V]
4 A
Rated operational currentDC currentDC L/R ≦ 50 msContacts in series:3 [110 V]
2 A
Rated operational currentDC currentDC L/R ≦ 50 msContacts in series:3 [220 V]
1 A
Rated operational currentControl circuit reliability [Failure rate]
<10-8, < one failure at 100 million operations
(at Ue= 24 V DC, Umin= 17 V, Imin= 5.4 mA) λ
Short-circuit rating without weldingMaximum overcurrent protective device220 V 230 V 240 V
4 PKZM0
Short-circuit rating without weldingMaximum overcurrent protective device380 V 400 V 415 V
4 PKZM0
Short-circuit rating without weldingShort-circuit protection maximum fuse500 V
10 A gG/gL
Current heat loss at IthDC operated
0.85 W
Voltage toleranceDC operatedNotes
Smoothed DC, three-phase bridge rectifiers or smoothed double-wave rectification
Voltage toleranceDC operatedPick-up voltage
0.81.1
Voltage toleranceDC operatedat 24 V: without auxiliary contact component (40 °C) [Pick-up]
0.7 - 1.3 x Uc
Power consumptionDC operationDC operated [Pull-in = sealing]
3 W
Changeover time at 100 % US(recommended value)DC operated closing delaySwitching times, DC operated, max. closing delay
31 ms
Changeover time at 100 % US(recommended value)DC operated N/O contact opening delaySwitching times, DC actuated make contact Opening delay, max.
12 ms
Rating data for approved types
Auxiliary contactsPilot DutyAC operated
A600
Auxiliary contactsPilot DutyDC operated
P300
Auxiliary contactsGeneral UseAC
600 V
Auxiliary contactsGeneral UseAC
15 A
Auxiliary contactsGeneral UseDC
250 V
Auxiliary contactsGeneral UseDC
1 A