Standards
IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanicalDC operated [Operations]
6.4 x 106
Operating frequency, mechanicalDC operated [Operations/h]
3600
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-25 - +60 °C
Ambient temperatureEnclosed
- 25 - 40 °C
Ambient temperatureStorage
- 40 - 80 °C
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msMain contactsN/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msAuxiliary contactsN/O contact
7 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msAuxiliary contactsN/C contact
5 g
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mountedHalf-sinusoidal shock, 10 msMain contactsN/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mountedHalf-sinusoidal shock, 10 msAuxiliary contactsN/O contact
7 g
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mountedHalf-sinusoidal shock, 10 msAuxiliary contactsN/C contact
5 g
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Screw connector terminalsTerminal capacity main cableFlexible with ferrule
1 x (10 - 70)
2 x (10 - 50) mm2
Screw connector terminalsTerminal capacity main cableStranded
1 x (16 - 70)
2 x (16 - 50) mm2
Screw connector terminalsTerminal capacity main cableSolid or stranded
single 8…3/0, double 8…2/0 AWG
Screw connector terminalsTerminal capacity main cableFlat conductor [Lamellenzahl x Breite x Dicke ]
2 x (6 x 16 x 0.8) mm
Screw connector terminalsTerminal capacity main cableStripping length
24 mm
Screw connector terminalsTerminal capacity main cableTerminal screw
M10
Screw connector terminalsTerminal capacity main cableTightening torque
14 Nm
Screw connector terminalsTerminal capacity main cableToolHexagon socket-head spanner [SW]
5 mm
Screw connector terminalsTerminal capacity control circuit cablesSolid
1 x (0.75 - 4)
2 x (0.75 - 2.5) mm2
Screw connector terminalsTerminal capacity control circuit cablesFlexible with ferrule
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Screw connector terminalsTerminal capacity control circuit cablesSolid or stranded
18 - 14 AWG
Screw connector terminalsTerminal capacity control circuit cablesStripping length
10 mm
Screw connector terminalsTerminal capacity control circuit cablesTerminal screw
M3.5
Screw connector terminalsTerminal capacity control circuit cablesTightening torque
1.2 Nm
Screw connector terminalsTerminal capacity control circuit cablesToolPozidriv screwdriver
2 Size
Screw connector terminalsTerminal capacity control circuit cablesToolStandard screwdriver
0.8 x 5.5
1 x 6 mm
Rated impulse withstand voltage [Uimp]
8000 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
690 V AC
Rated operational voltage [Ue]
690 V AC
Safe isolation to EN 61140between coil and contacts
690 V AC
Safe isolation to EN 61140between the contacts
690 V AC
Making capacity (p.f. to IEC/EN 60947) [Up to 690 V]
1120 A
Breaking capacity220 V 230 V
800 A
Breaking capacity380 V 400 V
800 A
Breaking capacity500 V
800 A
Breaking capacity660 V 690 V
650 A
Short-circuit ratingShort-circuit protection maximum fuseType “2” coordination400 V [gG/gL 500 V]
160 A
Short-circuit ratingShort-circuit protection maximum fuseType “2” coordination690 V [gG/gL 690 V]
160 A
Short-circuit ratingShort-circuit protection maximum fuseType “1” coordination400 V [gG/gL 500 V]
250 A
Short-circuit ratingShort-circuit protection maximum fuseType “1” coordination690 V [gG/gL 690 V]
200 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 40 °C [Ith=Ie]
110 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 50 °C [Ith=Ie]
98 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 55 °C [Ith=Ie]
94 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 60 °C [Ith=Ie]
90 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 Hzenclosed [Ith]
80 A
AC-1Rated operational currentConventional free air thermal current, 1 poleopen [Ith]
225 A
AC-1Rated operational currentConventional free air thermal current, 1 poleenclosed [Ith]
200 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 HzNotes
At maximum permissible ambient temperature (open.)
Also tested according to AC-3e.
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz220 V 230 V [Ie]
80 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz240 V [Ie]
80 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz380 V 400 V [Ie]
80 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz415 V [Ie]
80 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz440V [Ie]
80 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz500 V [Ie]
80 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz660 V 690 V [Ie]
65 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz380 V 400 V [Ie]
80 A
AC-3Motor rating [P]220 V 230 V [P]
25 kW
AC-3Motor rating [P]240V [P]
27.5 kW
AC-3Motor rating [P]380 V 400 V [P]
37 kW
AC-3Motor rating [P]415 V [P]
48 kW
AC-3Motor rating [P]440 V [P]
51 kW
AC-3Motor rating [P]500 V [P]
58 kW
AC-3Motor rating [P]660 V 690 V [P]
63 kW
AC-4Open, 3-pole: 50 – 60 Hz220 V 230 V [Ie]
40 A
AC-4Open, 3-pole: 50 – 60 Hz240 V [Ie]
40 A
AC-4Open, 3-pole: 50 – 60 Hz380 V 400 V [Ie]
40 A
AC-4Open, 3-pole: 50 – 60 Hz415 V [Ie]
40 A
AC-4Open, 3-pole: 50 – 60 Hz440 V [Ie]
40 A
AC-4Open, 3-pole: 50 – 60 Hz500 V [Ie]
40 A
AC-4Open, 3-pole: 50 – 60 Hz660 V 690 V [Ie]
27 A
AC-4Motor rating [P]220 V 230 V [P]
11.5 kW
AC-4Motor rating [P]240 V [P]
13 kW
AC-4Motor rating [P]380 V 400 V [P]
20 kW
AC-4Motor rating [P]415 V [P]
24 kW
AC-4Motor rating [P]440 V [P]
25 kW
AC-4Motor rating [P]500 V [P]
29 kW
AC-4Motor rating [P]660 V 690 V [P]
26 kW
Rated operational current, openDC-160 V [Ie]
110 A
Rated operational current, openDC-1110 V [Ie]
110 A
Rated operational current, openDC-1220 V [Ie]
70 A
3 pole, at Ith(60°)
11.4 W
Current heat loss at Ieto AC-3/400 V
9 W
Voltage toleranceDC operated [Pick-up]
0.7 - 1.2 x Uc
Voltage toleranceNotes
RDC 130 (Umin110 V DC/Umax130 V DC)
Example: US= 0.7 x Umin- 1.2 x Umax/ US= 0.7 x 110V - 1.2 x 130V DC
Voltage toleranceDC operated [Drop-out]
0.15 - 0.6 x Uc
Voltage toleranceNotes
at least smoothed two-phase bridge rectifier or three-phase rectifier
Power consumption of the coil in a cold state and 1.0 x USDC operated [Pick-up]
90 W
Power consumption of the coil in a cold state and 1.0 x USDC operated [Sealing]
1.5 W
Changeover time at 100 % US(recommended value)Main contactsDC operatedClosing delayClosing delay
45 ms
Changeover time at 100 % US(recommended value)Main contactsDC operatedOpening delayOpening delay
34 ms
Changeover time at 100 % US(recommended value)Arcing time
15 ms
Changeover time at 100 % US(recommended value)Permissible residual current with actuation of A1 - A2 by the electronics (with 0 signal).
≦ 1 mA
Electromagnetic compatibility (EMC)
Emitted interference
to EN 60947-1
Interference immunity
to EN 60947-1
Rating data for approved types
Switching capacityMaximum motor ratingThree-phase200 V
208 V
25 HP
Switching capacityMaximum motor ratingThree-phase230 V
240 V
30 HP
Switching capacityMaximum motor ratingThree-phase460 V
480 V
60 HP
Switching capacityMaximum motor ratingThree-phase575 V
600 V
75 HP
Switching capacityMaximum motor ratingSingle-phase115 V
120 V
7.5 HP
Switching capacityMaximum motor ratingSingle-phase230 V
240 V
15 HP
Switching capacityGeneral use
125 A
Short Circuit Current RatingBasic RatingSCCR
10 kA
Short Circuit Current RatingBasic Ratingmax. Fuse
600 A
Short Circuit Current RatingBasic Ratingmax. CB
600 A
Short Circuit Current Rating480 V High FaultSCCR (fuse)
30/100 kA
Short Circuit Current Rating480 V High Faultmax. Fuse
300/300 Class J A
Short Circuit Current Rating480 V High FaultSCCR (CB)
65 kA
Short Circuit Current Rating480 V High Faultmax. CB
250 A
Short Circuit Current Rating600 V High FaultSCCR (fuse)
30/100 kA
Short Circuit Current Rating600 V High Faultmax. Fuse
300/300 Class J A
Short Circuit Current Rating600 V High FaultSCCR (CB)
30 kA
Short Circuit Current Rating600 V High Faultmax. CB
350 A
Special Purpose RatingsElectrical Discharge Lamps (Ballast)480V 60Hz 3phase, 277V 60Hz 1phase
100 A
Special Purpose RatingsElectrical Discharge Lamps (Ballast)600V 60Hz 3phase, 347V 60Hz 1phase
100 A
Special Purpose RatingsIncandescent Lamps (Tungsten)480V 60Hz 3phase, 277V 60Hz 1phase
100 A
Special Purpose RatingsIncandescent Lamps (Tungsten)600V 60Hz 3phase, 347V 60Hz 1phase
100 A
Special Purpose RatingsResistance Air Heating480V 60Hz 3phase, 277V 60Hz 1phase
100 A
Special Purpose RatingsResistance Air Heating600V 60Hz 3phase, 347V 60Hz 1phase
100 A
Special Purpose RatingsRefrigeration Control (CSA only)LRA 480V 60Hz 3phase
540 A
Special Purpose RatingsRefrigeration Control (CSA only)FLA 480V 60Hz 3phase
90 A
Special Purpose RatingsRefrigeration Control (CSA only)LRA 600V 60Hz 3phase
420 A
Special Purpose RatingsRefrigeration Control (CSA only)FLA 600V 60Hz 3phase
70 A
Special Purpose RatingsDefinite Purpose Ratings (100,000 cycles acc. to UL 1995)LRA 480V 60Hz 3phase
480 A
Special Purpose RatingsDefinite Purpose Ratings (100,000 cycles acc. to UL 1995)FLA 480V 60Hz 3phase
80 A
Special Purpose RatingsElevator Control200V 60Hz 3phase
20 HP
Special Purpose RatingsElevator Control200V 60Hz 3phase
62.1 A
Special Purpose RatingsElevator Control240V 60Hz 3phase
25 HP
Special Purpose RatingsElevator Control240V 60Hz 3phase
68 A
Special Purpose RatingsElevator Control480V 60Hz 3phase
50 HP
Special Purpose RatingsElevator Control480V 60Hz 3phase
65 A
Special Purpose RatingsElevator Control600V 60Hz 3phase
60 HP
Special Purpose RatingsElevator Control600V 60Hz 3phase
62 A