Standards
IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanicalAC operated [Operations]
5.7 x 106
Operating frequency, mechanicalAC operated [Operations/h]
3600
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-25 - +60 °C
Ambient temperatureEnclosed
- 25 - 40 °C
Ambient temperatureStorage
- 40 - 80 °C
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msMain contactsN/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msAuxiliary contactsN/O contact
7 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msAuxiliary contactsN/C contact
5 g
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mountedHalf-sinusoidal shock, 10 msMain contactsN/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mountedHalf-sinusoidal shock, 10 msAuxiliary contactsN/O contact
7 g
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mountedHalf-sinusoidal shock, 10 msAuxiliary contactsN/C contact
5 g
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Screw connector terminalsTerminal capacity main cableFlexible with ferrule
1 x (10 - 70)
2 x (10 - 50) mm2
Screw connector terminalsTerminal capacity main cableStranded
1 x (16 - 70)
2 x (16 - 50) mm2
Screw connector terminalsTerminal capacity main cableSolid or stranded
single 8…3/0, double 8…2/0 AWG
Screw connector terminalsTerminal capacity main cableFlat conductor [Lamellenzahl x Breite x Dicke ]
2 x (6 x 16 x 0.8) mm
Screw connector terminalsTerminal capacity main cableStripping length
24 mm
Screw connector terminalsTerminal capacity main cableTerminal screw
M10
Screw connector terminalsTerminal capacity main cableTightening torque
14 Nm
Screw connector terminalsTerminal capacity main cableToolHexagon socket-head spanner [SW]
5 mm
Screw connector terminalsTerminal capacity control circuit cablesSolid
1 x (0.75 - 4)
2 x (0.75 - 2.5) mm2
Screw connector terminalsTerminal capacity control circuit cablesFlexible with ferrule
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Screw connector terminalsTerminal capacity control circuit cablesSolid or stranded
18 - 14 AWG
Screw connector terminalsTerminal capacity control circuit cablesStripping length
10 mm
Screw connector terminalsTerminal capacity control circuit cablesTerminal screw
M3.5
Screw connector terminalsTerminal capacity control circuit cablesTightening torque
1.2 Nm
Screw connector terminalsTerminal capacity control circuit cablesToolPozidriv screwdriver
2 Size
Screw connector terminalsTerminal capacity control circuit cablesToolStandard screwdriver
0.8 x 5.5
1 x 6 mm
Rated impulse withstand voltage [Uimp]
8000 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
690 V AC
Rated operational voltage [Ue]
690 V AC
Safe isolation to EN 61140between coil and contacts
690 V AC
Safe isolation to EN 61140between the contacts
690 V AC
Making capacity (p.f. to IEC/EN 60947) [Up to 690 V]
1120 A
Breaking capacity220 V 230 V
800 A
Breaking capacity380 V 400 V
800 A
Breaking capacity500 V
800 A
Breaking capacity660 V 690 V
650 A
Short-circuit ratingShort-circuit protection maximum fuseType “2” coordination400 V [gG/gL 500 V]
160 A
Short-circuit ratingShort-circuit protection maximum fuseType “2” coordination690 V [gG/gL 690 V]
160 A
Short-circuit ratingShort-circuit protection maximum fuseType “1” coordination400 V [gG/gL 500 V]
250 A
Short-circuit ratingShort-circuit protection maximum fuseType “1” coordination690 V [gG/gL 690 V]
200 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 40 °C [Ith=Ie]
110 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 50 °C [Ith=Ie]
98 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 55 °C [Ith=Ie]
94 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 60 °C [Ith=Ie]
90 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 Hzenclosed [Ith]
80 A
AC-1Rated operational currentConventional free air thermal current, 1 poleopen [Ith]
225 A
AC-1Rated operational currentConventional free air thermal current, 1 poleenclosed [Ith]
200 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 HzNotes
At maximum permissible ambient temperature (open.)
Also tested according to AC-3e.
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz220 V 230 V [Ie]
80 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz240 V [Ie]
80 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz380 V 400 V [Ie]
80 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz415 V [Ie]
80 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz440V [Ie]
80 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz500 V [Ie]
80 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz660 V 690 V [Ie]
65 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz380 V 400 V [Ie]
80 A
AC-3Motor rating [P]220 V 230 V [P]
25 kW
AC-3Motor rating [P]240V [P]
27.5 kW
AC-3Motor rating [P]380 V 400 V [P]
37 kW
AC-3Motor rating [P]415 V [P]
48 kW
AC-3Motor rating [P]440 V [P]
51 kW
AC-3Motor rating [P]500 V [P]
58 kW
AC-3Motor rating [P]660 V 690 V [P]
63 kW
AC-4Open, 3-pole: 50 – 60 Hz220 V 230 V [Ie]
40 A
AC-4Open, 3-pole: 50 – 60 Hz240 V [Ie]
40 A
AC-4Open, 3-pole: 50 – 60 Hz380 V 400 V [Ie]
40 A
AC-4Open, 3-pole: 50 – 60 Hz415 V [Ie]
40 A
AC-4Open, 3-pole: 50 – 60 Hz440 V [Ie]
40 A
AC-4Open, 3-pole: 50 – 60 Hz500 V [Ie]
40 A
AC-4Open, 3-pole: 50 – 60 Hz660 V 690 V [Ie]
27 A
AC-4Motor rating [P]220 V 230 V [P]
11.5 kW
AC-4Motor rating [P]240 V [P]
13 kW
AC-4Motor rating [P]380 V 400 V [P]
20 kW
AC-4Motor rating [P]415 V [P]
24 kW
AC-4Motor rating [P]440 V [P]
25 kW
AC-4Motor rating [P]500 V [P]
29 kW
AC-4Motor rating [P]660 V 690 V [P]
26 kW
Rated operational current, openDC-160 V [Ie]
110 A
Rated operational current, openDC-1110 V [Ie]
110 A
Rated operational current, openDC-1220 V [Ie]
70 A
3 pole, at Ith(60°)
11.4 W
Current heat loss at Ieto AC-3/400 V
9 W
Voltage toleranceAC operated [Pick-up]
0.8 - 1.1 x Uc
Voltage toleranceDrop-out voltage AC operated [Drop-out]
0.3 - 0.6 x Uc
Power consumption of the coil in a cold state and 1.0 x US50/60 Hz [Pick-up]
372
328 VA
Power consumption of the coil in a cold state and 1.0 x US50/60 Hz [Sealing]
37.1
22.6 VA
Power consumption of the coil in a cold state and 1.0 x US50/60 Hz [Sealing]
5.8 W
Changeover time at 100 % US(recommended value)Main contactsAC operatedClosing delay
14 - 20 ms
Changeover time at 100 % US(recommended value)Main contactsAC operatedOpening delay
9 - 14 ms
Changeover time at 100 % US(recommended value)Arcing time
15 ms
Changeover time at 100 % US(recommended value)Permissible residual current with actuation of A1 - A2 by the electronics (with 0 signal).
≦ 1 mA
Lifespan, mechanical; Coil 50/60 Hz
Mechanical lifespan at 50 Hz approx. 30% lower than under “General” x 106
Electromagnetic compatibility (EMC)
Emitted interference
to EN 60947-1
Interference immunity
to EN 60947-1