EC4P-222-MRXX1 106402 0004519743 EATON ELECTRIC Compact PLC, 24 V DC, 12DI(of 4AI), 6DO(R), ethernet, CAN View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

EC4P-222-MRXX1 106402 0004519743 EATON ELECTRIC Compact PLC, 24 V DC, 12DI(of 4AI), 6DO(R), ethernet, CAN

EC4P-222-MRXX1

106402

0004519743

EATON-MOELLER

Compact PLC, 24 V DC, 12DI(of 4AI), 6DO(R), ethernet, CAN

EC4P-222-MRXX1

More details


PLC's > PLC device set

EC4P PLCs

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Compact PLC, 24 V DC, 12DI(of 4AI), 6DO(R), ethernet, CAN
Compact controller for small and medium-sized automation tasks, programming according to IEC 61131 (CoDeSys), the Ethernet interface and the serial interface (ec4p-222 types) are for the purpose of programming, the communication via UDP and Modbus as well as connection of OPC clients

Delivery program

Expandable: Inputs/outputs and bus systems
individual laser inscription possible with EC4-COMBINATION-*
Description
easyNet/CANopen® and Ethernet on board
Inputs
Digital
12
of which can be used as analog
4
Outputs
Relay 10 A (UL)
6
Supply voltage
24 V DC

Technical data

General
Dimensions (W x H x D)
107.5 x 90 x 72 without/79 with adapter for MCC (6 SU) mm
Weight
0.3 kg
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using 3 fixing brackets ZB4-101-GF1 (accessories)
Terminal capacities
Solid
0.2/4 (AWG 22 - 12) mm2
Flexible with ferrule
0.2/2.5 (AWG 22 - 12) mm2
Standard screwdriver
0.8 x 3.5 mm
Max. tightening torque
0.6 Nm
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
LCD display (clearly legible)
0 - 55 °C
Storage [ϑ]
-40 - +70 °C
Relative humidity, non-condensing (IEC/EN 60068-2-30)
5 - 95 %
Air pressure (operation)
1080 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations (IEC/EN 60068-2-6)Constant amplitude 0.15 mm
10 - 57 Hz
Vibrations (IEC/EN 60068-2-6)Constant acceleration 2 g
57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
1 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
II/2
Electrostatic discharge (ESD)applied standard
IEC/EN 61000-4-2, Level 3
Electrostatic discharge (ESD)Air discharge
8 kV
Electrostatic discharge (ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
10 V/m
Radio interference suppression
EN 55011 Class B, EN 55022 Class B
Burst
IEC/EN 61000-4-4, level 3 kV
BurstSupply cable
2 kV
BurstSignal lines
2 kV
power pulses (Surge)
2 kV (supply cables, symmetrical, EASY...AC)
0.5 kV (supply cables, symmetrical, easy-DC)
according to IEC/EN 61000-4-5
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Insulation resistance
Clearance in air and creepage distances
EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
EN 50178
Back-up of real-time clock
Back-up of real-time clock
252U067
① Backup time (hours) with fully charged double layer capacitor
② Service life (years)
Accuracy of the real-time clock
part no. ± 5 (± 0.5 h⁄Year) s/day
Retentive memory
Write cycles of the retentive memory
10000000000 (10¹⁰) (Read-write cycles)
Power supply
Rated operational voltage [Ue]
24 DC (-15/+20%) V
Permissible range [Ue]
20.4 - 28.8 V DC
Residual ripple
≦ 5 %
Input current
normally 140 mA at Ue
Voltage dips
≤ 10
(IEC/EN 61131-2) ms
Heat dissipation [P]
Normally 3.4 W
CPU
Processor
Infineon XC161
MemoryProgram code/data
256/14 segments of 16 KB each kByte
MemoryMarker/retentive data
16/4/4/8 KByte
Cycle time for 1 k of instructions (Bit, Byte)
< 0.3 ms
Interfaces
PRG interface RS232Data transfer rate
4.8, 9.6, 19.2, 38.4, 57.6, 115.2 (character format: 8 bit data, no parity, 1 stop bit) kBit/s
PRG interface RS232Connection types
RJ45-bus
PRG interface RS232Potential isolation
none
PRG interface RS232Master modeData transfer rate
0.3, 0.6, 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 kbit/s
PRG interface RS232Master modeCharacter formats
8E1, 8O1, 8N1, 8N2, 7E2, 7O2, 7N2, 7E1
PRG interface RS232Master modeNumber of transmission bytes in a block
190 bytes
PRG interface RS232Master modeNumber of received bytes in a block
190 bytes
EthernetData transfer rate
10 MBit/s, 100 m Mbit/s
EthernetConnection types
RJ45
EthernetPotential isolation
No
CANopen®Data transfer rate
500 kBit/s, 25 m250 kBit/s, 60m125 kBit/s, 125 m50 kBit/s, 300 m20 kBit/s, 700 m10 kBit/s, 1000 m
CANopen®Bus termination (first and last station)
EASY-NT-R plug (incl. bus terminating resistor 120 Ω)
CANopen®Connection types
2 x RJ45, 8 pole
Master modeNumber
8
Mode slaveStations
max. 126 Number
Mode slavePDO type
Asynchronous, cyclic, acyclic
Mode slaveControl contact rated current
To DS 301 V4
Digital inputs 24 V DC
Number
12
Inputs can be used as analog inputs
4 (I7, I8, I11, I12)
Status Display
LCD-Display
Potential isolation
from the outputs: yes
to network easyNet, easyLink
Rated operational voltage [Ue]
24 V DC
Input voltage
< 5 (I1 - I6, I9 - I10) < 8 (I7, I8, I11, I12) at signal "0"
> 15.0 (I1 - I6, I9, I10) > 8.0 (I7, I8, I11, I12) at signal "1" V DC
Input current on 1 signalInput current at signal 1
3.3 (I1 to I6)
2.2 (I7, I8)
3.3 (I9, I10)
2.2 (I11, I12) mA
Deceleration time
normally 0.02 (I1 - I4), normally 0.25 (I5 - I12) (from ''0'' to "1")
normally 0.02 (I1 - I4), normally 0.25 (I5 - I12) (from ''0'' to "1") ms
Cable length
100 (unshielded) m
Incremental counterNumber of counter inputs
1 (I1, I2, I3, I4)
Incremental counterValue range
32 Bit
Incremental counterCounter frequency
≦ 40 kHz
Incremental counterPulse shape
Square
Incremental counterCounter inputs
I1, I2
Incremental counterReference input
I3
Incremental counterInput for reference switch
I4
Incremental counterCounter inputs I1 and I2, I3 and I4
1
Incremental counterSignal offset
90°
Rapid counter inputsNumber
2 (I1, I2) at 16 Bit or 1 (I1) at 32 Bit
Rapid counter inputsValue range
16/32 Bit
Rapid counter inputsCable length
≦ 20 (screened) m
Rapid counter inputsCounter frequency
≦ 50 kHz
Rapid counter inputsPulse shape
Square
Analog inputs
Number
4 (I7, I8, I11, I12)
Potential isolation
from the outputs: yes
to interface/memory card: no
Input type
DC voltage
Signal range
0-10 V DC
Resolution
0.01 V analog
0.01 V digital
10 Bit (value 0 - 1023)
Input impedance
11.2 kΩ
Accuracy of actual valueWithin a single device
± 2, (I7, I8, I11, I12) ± 0.12 V %
Conversion time, analog/digital
each CPU cycle ms
Input current
< 1 mA
Cable length
≦ 30, screened m
Relay outputs
Outputs in groups of
1
Parallel switching of outputs for increased output
Not permissible
Protection of an output relay
Miniature circuit-breaker B16 or fuse 8 A (slow)
Potential isolation
from power supply: yes
From the inputs: yes
in groups
Safe isolation according to EN 50178: 300 V AC
Basic isolation: 600 V AC
Lifespan, mechanical [Operations]
10 x 106
ContactsConventional thermal current (10 A UL)
8 A
ContactsRecommended for load: 12 V AC/DC
> 500 mA
ContactsShort-circuit-proof cos ϕ = 1, characteristic B16 at 600 A
16 A
ContactsShort-circuit-proof cos ϕ = 0.5 to 0.7, characteristic B16 at 900 A
16 A
ContactsRated impulse withstand voltage Uimpof contact coil
6 kV
ContactsRated operational voltage [Ue]
250 V AC
Rated insulation voltage [Ui]
250 V AC
Safe isolation according to EN 50178
300 between coil and contact
300 between two contacts V AC
Making capacityAC–-15, 250 V AC, 3 A (600 ops./h) [Operations]
300000
Making capacityDC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) [Operations]
200000
Breaking capacityAC-15, 250 V AC, 3 A (600 Ops./h) [Operations]
300000
Breaking capacityDC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) [Operations]
200000
Filament bulb load1000 W at 230/240 V AC [Operations]
25000
Filament bulb load500 W at 115/120 V AC [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 10 x 58 W at 230/240 V ACWith upstream electrical device [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 10 x 58 W at 230/240 V ACUncompensated [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated [Operations]
25000
Switching frequencyMechanical operations
10 x 106
Switching frequencySwitching frequency
10 Hz
Switching frequencyResistive load/lamp load
2 Hz
Switching frequencyInductive load
0.5 Hz
UL/CSAUninterrupted current at 240 V AC
10 A
UL/CSAUninterrupted current at 24 V DC
8 A
UL/CSAACControl Circuit Rating Codes (utilization category)
B 300 Light Pilot Duty
UL/CSAACMax. rated operational voltage
300 V AC
UL/CSAACmax. thermal continuous current cos ϕ = 1 at B 300
5 A
UL/CSAACmax. make/break cos ϕ ≠ capacity 1 at B 300
3600/360 VA
UL/CSADCControl Circuit Rating Codes (utilization category)
R 300 Light Pilot Duty
UL/CSADCMax. rated operational voltage
300 V DC
UL/CSADCMax. thermal uninterrupted current at R 300
1 A
UL/CSADCMax. make/break capacity at R 300
28/28 VA
Network easyNet
Bus termination (first and last station)
EASY-NT-R plug (incl. bus terminating resistor 120 Ω)

Design verification as per IEC/EN 61439

Datos técnicos para la verificación del diseño
Intensidad asignada de empleo para disipación térmica específica [In]
0 A
Disipación térmica por polo, en función de la intensidad [Pvid]
0 W
Disipación térmica del equipo, en función de la intensidad [Pvid]
0 W
Disipación térmica estática, en función de la intensidad [Pvs]
3.4 W
Capacidad de disipación térmica [Pdiss]
0 W
Temperatura ambiente mínima de funcionamiento
-25 °C
Temperatura ambiente máxima de funcionamiento
+55 °C
Verificación de diseño IEC / EN 61439
10.2 Resistencia de materiales y piezas10.2.2 Resistencia a la corrosión
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.1 Verificación de la estabilidad térmica de los armarios
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.2 Verificación de la resistencia de los materiales aislantes en condiciones de calor normales
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.3. Verificación de la resistencia de los materiales aislantes al calor excesivo y al fuego debido a los efectos eléctricos internos
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.4 Resistencia a radiación ultravioleta (UV)
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.5 Elevación
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.2 Resistencia de materiales y piezas10.2.6 Impacto mecánico
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.2 Resistencia de materiales y piezas10.2.7 Inscripciones
Cumple con los requisitos de la norma del producto.
10.3 Grado de protección de montajes
Cumple con los requisitos de la norma del producto.
10.4 Distancias de separación y fuga
Cumple con los requisitos de la norma del producto.
10.5 Protección contra descargas eléctricas
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.6 Incorporación de dispositivos y componentes de conmutación
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.7 Conexiones y circuitos eléctricos internos
Es responsabilidad del cuadrista.
10.8 Conexiones de conductores externos
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.2 Resistencia eléctrica de frecuencia de alimentación
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.3 Tensión de impulso soportada
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.4 Pruebas de armarios hechos de material aislante
Es responsabilidad del cuadrista.
10.10 Aumento de la temperatura
El cuadrista es responsable del cálculo del aumento de la temperatura. Eaton proporcionará datos de disipación de calor para los dispositivos.
10.11 Resistencia a los cortocircuitos
Es responsabilidad del cuadrista.
10.12 Compatibilidad electromagnética
Es responsabilidad del cuadrista.
10.13 Función mecánica
El dispositivo cumple los requisitos, siempre que se observe la información del folleto de instrucciones (IL).

Technical data ETIM 7.0

PLCs (EG000024) / Sistema PLC completo (EC002581)
Tecnología electrónica, de automatización y de mando de procesos / Control / Controles lógicos programables (CLP) / Sistemas completos de CLP ([email protected] [BAA707013])
Contiene bloques de integración de funciones
Contiene dispositivo básico
Contiene cremallera de módulo
No
Contiene fuente de alimentación
Contiene módulo de entrada analógico
Contiene módulo de salida analógico
No
Contiene módulo de entrada digital
Contiene módulo de salida digital
Contiene módulo de funciones
Contiene módulo de tecnología
No
Contiene módulo de comunicación
Contiene unidad de memoria
Contiene módulo de simulación
No
Contiene cable de conexión
No
Contiene unidad de control
No
Contiene monitor
No
Contiene software de programación
No
Contiene software de ingeniería
Contiene visualización
No
Contiene bibliotecas
Contiene documentación
Contiene otros componentes
Software preinstalado
No

Approvals

Product Standards
IEC: see Technical Data; UL508; CSA-C22.2 No. 0-M; CSA-C22.2 No. 142-M; CE marking
UL File No.
E135462
UL Category Control No.
NRAQ
CSA File No.
012528
CSA Class No.
2252-01
North America Certification
UL listed, CSA certified
Specially designed for North America
No
Current Limiting Circuit-Breaker
No
Degree of Protection
IEC: IP20, UL/CSA Type: -

Dimensions

2724DIM-5

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.