XIOC-TC1 135265 0004560855 EATON ELECTRIC Communication module for XC100/200, 24 V DC, serial, modbus, SUCOM.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

XIOC-TC1 135265 0004560855 EATON ELECTRIC Communication module for XC100/200, 24 V DC, serial, modbus, SUCOM..

XIOC-TC1

135265

0004560855

EATON-MOELLER

Communication module for XC100/200, 24 V DC, serial, modbus, SUCOM-A, DNP3

XIOC-TC1

More details


PLC's > PLC communication module

XC Modular PLC

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



EL-Nummer (Norway)
4560855
Communication module for XC100/200, 24 V DC, serial, modbus, SUCOM-A, DNP3
Modular programmable controllers XC100 and XC200 offer an outstanding level of scalability. Different CPU performance classes and a wide range of expansion modules (XIOC-Module) are available. The compact modular PLCs XC152 facilitate cost-effective solutions of automation tasks using their computing power, the SmartWire-DT interface as well as a whole range of further interfaces. a particular feature is the ability to integrate the product into modern communication concepts. Data exchange via the Ethernet interface to OPC clients or the integrated WEB servers enables the creation of innovative solutions.

Delivery program

Function
Communication modules
Compact I/O system for connection to XC100/200 Modular PLCs
XC100/200 expandable with up to 15 XI/OC modules
Optionally, screw terminals or spring-loaded terminals for digital/analog modules
Description
Serial interface
RS232C, RS485, RS422
Modes of operation:
Transparent mode
MODBUS Master/Slave
SUCOM-A
DNP3-Protocol

Technical data

General
Standards
IEC/EN 61131-2
EN 50178
Ambient temperature
0 - +55 °C
Storage [ϑ]
-20 - +70 °C
Vibration resistance
10 - 57 Hz ±0.075 mm
57 - 150 Hz ±1.0 mm
Mechanical shock resistance
15
Shock duration 11 ms g
Impact resistance
500 g/⌀ 50 mm ±25 g
Overvoltage category/pollution degree
II/2
Protection class
1
Degree of Protection
IP20
Emitted interference
DIN/EN 55011/22, Class A
Weight
0.2 kg
Power supply
Rated voltage [Ue]
24 (12) V DC
Admissible range
20.4 – 28.8 (11.8 – 14.4)
Residual ripple
≦ 5 %
Neutral polesDuration of dip
10 ms
Neutral polesRepetition rate
1 s
Maximum power loss [Pv]
6.6 W
Interfaces
Built-in interfaces
RS232(C), RS422, RS485
Protocol
Tranparent mode, Modbus Master/Slave, SUCOM-A, DNP3 protocol
Character formats
8E1, 8O1, 8N1, 8N2, 7E2, 7O2, 7N2, 7E1
Control and signal cables
RTS, CTS, DTR, DSR, DCD
Data transfer rate
0.3 …57.6 kBit/s
Potential isolation
Yes (RS485, RS422)
Transmit/receive data
250/500
Bus terminating resistors
Switchable for RS485, RS422
Plug arrangement
RS232: 9 pole SUB-D plug RS485, 422: plug terminal block
Current consumption [Ie]
275 mA
Number of modules
XC200: 4
Slots
As required
Interface modules
Operating mode Transparent modeData transfer rate
0.3 …57.6 kBit/s
Operating mode Transparent modeCharacter formats
8E1, 8O1, 8N1, 8N2, 7E2, 7O2, 7N2, 7E1
Operating modeTransmit/receive data
250/500

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
0 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
6.6 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
0 °C
Operating ambient temperature max.
+55 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

PLC's (EG000024) / PLC communication module (EC001423)
Electric engineering, automation, process control engineering / Control / Programmable logic control (SPS) / SPS communication module ([email protected] [AKE531014])
Number of HW-interfaces industrial Ethernet
0
Number of interfaces PROFINET
0
Number of HW-interfaces RS-232
1
Number of HW-interfaces RS-422
1
Number of HW-interfaces RS-485
1
Number of HW-interfaces serial TTY
0
Number of HW-interfaces USB
0
Number of HW-interfaces parallel
0
Number of HW-interfaces Wireless
0
Number of HW-interfaces other
0
With optical interface
No
Supporting protocol for TCP/IP
No
Supporting protocol for PROFIBUS
No
Supporting protocol for CAN
No
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for KNX
No
Supporting protocol for MODBUS
Yes
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
No
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
No
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
No
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for other bus systems
Yes
Radio standard Bluetooth
No
Radio standard WLAN 802.11
No
Radio standard GPRS
No
Radio standard GSM
No
Radio standard UMTS
No
IO link master
No
Redundancy
No
Type of data transmission
Serial
Transmission rate
57.6 kBit/s
With potential separation
No
Category according to EN 954-1
SIL according to IEC 61508
None
Suitable for safety functions
No
Performance level acc. EN ISO 13849-1
None
Appendant operation agent (Ex ia)
No
Appendant operation agent (Ex ib)
No
Explosion safety category for gas
None
Explosion safety category for dust
None
Width
30 mm
Height
100 mm
Depth
95 mm

Approvals

North America Certification
Request filed for UL and CSA
Specially designed for North America
No
Current Limiting Circuit-Breaker
No

Dimensions

272X107
272X046

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.