Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
Rated operational current for specified heat dissipation
In A 6
Heat dissipation per pole, current-dependent
Pvid W 0
Equipment heat dissipation, current-dependent
Pvid W 2.9
Static heat dissipation, non-current-dependent
Pvs W 0
Heat dissipation capacity
Pdiss W 0
Operating ambient temperature min.
°C -25
Operating ambient temperature max.
°C 55
linear, per +1 °C, results in a 0.5% reduction of current carrying capacity
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0
Circuit breakers and fuses (EG000020) / Miniature circuit breaker (MCB) (EC000042)
Electric engineering, automation, process control engineering / Electrical installation, device / Miniature circuit breaker system (MCB) / Miniature circuit breaker (MCB) ([email protected] [AAB905011])
Release characteristic
C
Number of poles (total)
2
Number of protected poles
2
Nominal rated current
A 6
Nominal rated voltage
V 400
Rated short-circuit breaking capacity Icn EN 60898 at 230 V
kA 6
Rated short-circuit breaking capacity Icn EN 60898 at 400 V
kA 6
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V
kA 0
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V
kA 0
Voltage type
AC
Current limiting class
3
Frequency
Hz 50 - 60
Concurrently switching N-neutral
No
Suitable for flush-mounted installation
No
Over voltage category
3
Pollution degree
2
Width in number of modular spacings
2
Built-in depth
mm 70.5
Additional equipment possible
Yes
Degree of protection (IP)
IP20

Datasheet - PDF

Title: Size: Type:
PDF CATALOGUE EATON EN.pdf 51 Mbytes
CLS6-C6/2 263679 263679.pdf 137 Kbytes   CLS6-C6/2  263679 263679.pdf

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.