Design verification according to IEC/EN 61439(display characteristics)(hide features)
Technical specifications for verification of design
Rated current job for indication of the power dissipated
In Has Thirteen
Power dissipated per pole, according to the current
Pvid W Zero
Power dissipated in the material, a function of the current
Pvid W 2.5
Power dissipated static, dependent on the current
Pvs W Zero
Power emission of the power dissipated
Pve W Zero
Temperature of use min.
°C -25
Working temperature max.
°C Fifty five
linear by +1 °C causes a decrease of 0.5 % intensity of the eligible
Certificate for IEC/EN 61439
10.2 Strength of materials and parts
10.2.2 Resistance to corrosion
The requirements of the product standard are met.
10.2.3.1 heat Resistance of the envelope
The requirements of the product standard are met.
10.2.3.2 Resistance of insulating Materials to Heat normal
The requirements of the product standard are met.
10.2.3.3 Resistance insulating Materials for outstanding Warmth
The requirements of the product standard are met.
10.2.4 Resistance to UV
The requirements of the product standard are met.
10.2.5 Elevation
Without object to the fact that the entire apparatus must be evaluated.
10.2.6 shock Test
Without object to the fact that the entire apparatus must be evaluated.
10.2.7 Inscriptions
The requirements of the product standard are met.
10.3 Degree of protection of the envelope
Without object to the fact that the entire apparatus must be evaluated.
10.4 isolation Distances and lines of flight
The requirements of the product standard are met.
10.5 Protection against electric shock
Without object to the fact that the entire apparatus must be evaluated.
10.6 Mounting hardware
Without object to the fact that the entire apparatus must be evaluated.
10.7 electrical Circuits and connections internal
Under the responsibility of the tableautier.
10.8 Connections for the conductors passed from the outside
Under the responsibility of the tableautier.
10.9 Properties of isolation
10.9.2 withstand Voltage at industrial frequency
Under the responsibility of the tableautier.
10.9.3 there Voltage shock
Under the responsibility of the tableautier.
10.9.4 Test envelope insulation
Under the responsibility of the tableautier.
10.10 Warm-up
The calculation of the warm-up is under the responsibility of the tableautier. Eaton provides the data of the dissipated power of the devices.
10.11 resistance to short-circuits
Under the responsibility of the tableautier. The specifications of the devices must be observed.
10.12 electromagnetic Compatibility
Under the responsibility of the tableautier. The specifications of the devices must be observed.
10.13 mechanical Operation
At the level of the device, the required conditions are met, to the extent the instructions of the installation manual (IT) are taken into account.
Technical data ETIM 6.0
characteristic of tripping
C
number of poles (total)
One
number of poles-protected
One
current rating assigned
Has Thirteen
rated voltage
V Two hundred thirty
breaking power assigned to Icn according to EN 60898 230 V
kA Six
breaking power assigned to Icn according to EN 60898 400 V
kA Six
breaking power assigned to Icu according to IEC 60947-2 230 V
kA Zero
breaking power assigned to Icu according to IEC 60947-2 400 V
kA Zero
type of voltage
CA
class energy limited
Three
frequency
Hz 50 - 60
a neutral conductor connected simultaneously
not
suitable for in-wall installation
not
overvoltage category
Three
pollution degree
Two
width in units of partition
One
mounting depth
mm 70.5
auxiliary devices possible
yes
protection class (IP)
IP20

Datasheet - PDF

Title: Size: Type:
PDF CATALOGUE EATON EN.pdf 51 Mbytes
CLS6-C13 263657 263657.pdf 128 Kbytes   CLS6-C13  263657 263657.pdf

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.