IZM32B4-U20F 124064 EATON ELECTRIC Automatic switch, 4P, 2000A, fixed

IZM32B4-U20F

124064

EATON-MOELLER

Automatic switch, 4P, 2000A, fixed

Circuit-breaker IZM32 ( Air circuit-breakers/switch-disconnectors), 4 pole, Current Range: 4000 to 6300 A, Rated current = rated uninterrupted current( In = Iu): 2000 A, Rated ultimate short-circuit breaking capacity up to 440V/690V 42/42( Icu): 65 kA, Rated service short-circuit breaking capacity up to 440V/690V 42/42( Ics): 65 kA, Overload release, min.( Ir): 800 A, Overload release, max.( Ir): 2000 A, Installation type: Fixed, Standard/Approval: IEC, Protective function: Universal protection

More details


Low-voltage industrial components > Power circuit-breaker for trafo/generator/installation protection

Home > EATON - MOELLER

Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Delivery programme
Product range
Air circuit-breakers/switch-disconnectors
Product range
Open circuit-breakers
Current Range
over 4000 A
Protective function
Universal protection
Installation type
Fixed
Construction size
IZM32
Release system
Electronic release
Standard/Approval
IEC
Number of poles
4 pole
Degree of Protection
IP20, IP55 with protective cover, IP41 with door sealing frame
Rated current = rated uninterrupted current
In= Iu A 2000
Breaking capacity Icu = Ics to 440 V 50/60 Hz
Icu kA 65
Breaking capacity Ics to 440 V 50/60 Hz
Ics kA 65
Overload release, min.
Ir A 800
Overload release, max.
Ir A 2000
Non-delayed
Ii= Inx … 2 - 10, OFF
Delayed
Isd= Irx … 2 - 10
Notes

Including rear connection main terminals and secondary terminal blocks according to ordered breaker options.

Technical data
General
Standards
IEC/EN 60947
Ambient temperature
Storage
ϑ °C -25 - +70 (device with LCD-display -20 - +70)
Operating (open)
°C -25 - +70 (device with LCD-display -20 - +70)
Mounting position
>
>
Utilization category
B
Degree of Protection
IP20, IP55 with protective cover, IP41 with door sealing frame
Direction of incoming supply
as required
Main conducting paths
Rated current = rated uninterrupted current
In= Iu A 2000
Rated uninterrupted current at 50 °C
Iu A 2000
Rated uninterrupted current at 60 °C
Iu A 2000
Rated uninterrupted current at 70 °C
Iu A 2000
Rated impulse withstand voltage
Uimp V AC 8000
Rated operational voltage
Ue V AC 690
Use in IT electrical power networks up to U = 440 V
IIT kA 28
Overvoltage category/pollution degree
III/3
Rated insulation voltage
Ui V 1000
Switching capacity
Rated short-circuit making capacity
Icm
up to 440 V 50/60 Hz
Icm kA 136
up to 690 V 50/60 Hz
Icm kA 137
Rated short-time withstand current 50/60 Hz
t = 1 s
Icw kA 65
t = 3 s
Icw kA 50
Rated short-circuit breaking capacity Icn
Icn
IEC/EN 60947 operating sequence IcuO-t-CO
up to 240 V 50/60 Hz
Icu kA 65
up to 440 V 50/60 Hz
Icu kA 65
up to 690 V 50/60 Hz
Icu kA 65
IEC/EN 60947 operating sequence IcsO-t-CO-t-CO
up to 240 V 50/60 Hz
Ics kA 65
up to 440 V 50/60 Hz
Ics kA 65
up to 690 V 50/60 Hz
Ics kA 65
Operating times
Closing delay via spring release
ms 30
Break times
ms 40
Total opening delay via shunt release
ms 35
Total opening delay via undervoltage release
ms 35/70
Total opening delay on non-delayed short-circuit release (up to complete arc quenching)
ms 35
Maximum operating frequency
Operations/h 60
Heat dissipation at rated current In
Fixed mounting
W 190
Withdrawable units (switch with cassette)
W 330
Weight
Fixed mounting
3-pole
kg 63
4-pole
kg 78
Withdrawable
3-pole
kg 75
4-pole
kg 94
Cassette
3 pole
kg 58
4 pole
kg 60
Terminal capacities
Copper bar
Fixed mounting
Black
mm 3 x 5 x 100
Withdrawable units
Black
mm 3 x 5 x 100


Permissible continuous current for circuit‐breakers operating in switchboards at various internal ambient temperatures. The switchboard’s internal ambient temperature should be estimated using the calculation methods of IEC regulation.

Other technical data (sheet catalogue)
>Tripping characteristics for universal and selective protection
>Notes - tripping characteristics
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
Operating ambient temperature min.
°C -25
Operating ambient temperature max.
°C 70
Dimensions
>
Additional product information (links)
> >Notes - tripping characteristics
> >Tripping characteristics for universal and selective protection

ETIM for 124064 Low-voltage industrial controls and switchgear (EC000228)
Feature Name Feature Value
Overload release current setting (EF002336) 800 A
Integrated earth fault protection (EF007296) No
Suitable for DIN rail (top hat rail) mounting (EF007250) No
DIN rail (top hat rail) mounting optional (EF008904) No
With switched-off indicator (EF007006) No
With integrated under voltage release (EF001390) No
Number of poles (EF001391) 4
Position of connection for main current circuit (EF006671) Back
Complete device with protection unit (EF008906) No
Motor drive integrated (EF006697) No
Motor drive optional (EF007386) No
Degree of protection (IP) (EF005474) IP20

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.