Circuit-breaker, 3p, 5000A, fixed
Circuit-breaker IZM63 ( Air circuit-breakers/switch-disconnectors), 3 pole, Current Range: 4000 to 6300 A, Rated current = rated uninterrupted current( In = Iu): 5000 A, Rated ultimate short-circuit breaking capacity up to 440V/690V 42/42( Icu): 85 kA, Rated service short-circuit breaking capacity up to 440V/690V 42/42( Ics): 85 kA, Overload release, min.( Ir): 2000 A, Overload release, max.( Ir): 5000 A, Installation type: Fixed, Standard/Approval: IEC, Protective function: Universal protection and power measurement
[

Delivery program

Product range
Air circuit-breakers/switch-disconnectors
Product range
Open circuit-breakers
Current Range
4000 to 6300 A
Protective function
Universal protection and power measurement
Installation type
Fixed
Construction size
IZM63
Standard/Approval
IEC
Number of poles
3 pole
Degree of Protection
IP20, IP55 with protective cover, IP41 with door sealing frame
Rated current = rated uninterrupted current [In= Iu]
5000 A
Rated ultimate short-circuit breaking capacity up to 440V/690V 42/42 [Icu]
85 kA
Rated service short-circuit breaking capacity up to 440V/690V 42/42 [Ics]
85 kA
Overload release, min. [Ir]
2000 A
Overload release, max. [Ir]
5000 A
Non-delayed [Ii= Inx …]
2 - 10, OFF
Delayed [Isd= Irx …]
2 - 10
Notes

Including rear connection main terminals and secondary terminal blocks according to ordered breaker options.

,

Technical data

General
Standards
IEC/EN 60947
Ambient temperatureStorage [ϑ]
-25 - +70 (device with LCD-display -20 - +70) °C
Ambient temperatureOperating (open)
-25 - +70 (device with LCD-display -20 - +70) °C
Mounting position
Utilization category
B
Degree of Protection
IP20, IP55 with protective cover, IP41 with door sealing frame
Direction of incoming supply
as required
Main conducting paths
Rated current = rated uninterrupted current [In= Iu]
5000 A
Rated uninterrupted current at 50 °C [Iu]
5000 A
Rated uninterrupted current at 60 °C [Iu]
5000 A
Rated uninterrupted current at 70 °C [Iu]
5000 A
Rated impulse withstand voltage [Uimp]
8000 V AC
Rated operational voltage [Ue]
690 V AC
Use in IT electrical power networks up to [U]
440 V
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
1000 V
Switching capacity
Rated short-circuit making capacity [Icm]up to 440 V 50/60 Hz [Icm]
178 kA
Rated short-circuit making capacity [Icm]up to 690 V 50/60 Hz [Icm]
179 kA
Rated short-time withstand current 50/60 Hzt = 1 s [Icw]
85 kA
Rated short-circuit breaking capacity Icn[Icn]IEC/EN 60947 operating sequence IcuO-t-COup to 240 V 50/60 Hz [Icu]
85 kA
Rated short-circuit breaking capacity Icn[Icn]IEC/EN 60947 operating sequence IcuO-t-COup to 440 V 50/60 Hz [Icu]
85 kA
Rated short-circuit breaking capacity Icn[Icn]IEC/EN 60947 operating sequence IcuO-t-COup to 690 V 50/60 Hz [Icu]
85 kA
Rated short-circuit breaking capacity Icn[Icn]IEC/EN 60947 operating sequence IcsO-t-CO-t-COup to 240 V 50/60 Hz [Ics]
85 kA
Rated short-circuit breaking capacity Icn[Icn]IEC/EN 60947 operating sequence IcsO-t-CO-t-COup to 440 V 50/60 Hz [Ics]
85 kA
Rated short-circuit breaking capacity Icn[Icn]IEC/EN 60947 operating sequence IcsO-t-CO-t-COup to 690 V 50/60 Hz [Ics]
85 kA
Operating timesClosing delay via spring release
40 ms
Operating timesBreak times
40 ms
Operating timesTotal opening delay via shunt release
35 ms
Operating timesTotal opening delay via undervoltage release
35/70 ms
Operating timesTotal opening delay on non-delayed short-circuit release (up to complete arc quenching)
35 ms
Maximum operating frequency [Operations/h]
60
Heat dissipation at rated current InFixed mounting
400 W
Heat dissipation at rated current InWithdrawable units (switch with cassette)
1000 W
Weight
Fixed mounting3-pole
125 kg
Fixed mounting4-pole
163 kg
Withdrawable3-pole
157 kg
Withdrawable4-pole
200 kg
Cassette3 pole
60 kg
Cassette4 pole
73 kg
Terminal capacities
Copper barFixed mountingBlack
5 x 10 x 100 mm
Copper barWithdrawable unitsBlack
5 x 10 x 100 mm

Permissible continuous current for circuit‐breakers operating in switchboards at various internal ambient temperatures. The switchboard’s internal ambient temperature should be estimated using the calculation methods of IEC regulation.

Other technical data (sheet catalogue)
Tripping characteristics for universal protection and power quality
Notes - tripping characteristics
,

Design verification as per IEC/EN 61439

Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+70 °C
,

Dimensions

]

Datasheet - PDF

Title: Size: Type:
IZM63N3-P50F 124313 124313_EN.pdf 226 Kbytes   IZM63N3-P50F  124313 124313_EN.pdf

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.