Product successfully added to your shopping cart
G34960008700
CARLO GAVAZZI
1
Selected parameters MODULE TYPE Serial interface HOUSING DIN-rail I/O TYPE Serial protocol NUMBER OF I/O 0 Others MODULE TYPE RS232/RS485 interface I/O TYPE Koyo PLC protocol
Home > CARLO GAVAZZI
* Brand new product in its original packaging covered by the warranties and certifications provided by CARLO GAVAZZI
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Dupline® Plug & Play Master Module
Interface forKoyo PLC Type G 3496 0008
• Interface for Koyo PLC with the function of a Master
• Plug and play: Automatic communication with specific
PLC/Controllers
• Built-in normal Dupline®Channel Generator
• 128 I/O’s and DC power supply on 3 wires
• RS232/RS422/RS485 port for interfacing to control system
• Split-I/O mode selectable (128 inputs and 128 outputs)
• LED-indications for supply, Dupline®carrier and Com- port TX
• Galvanically isolated Com-port supplied by internal DC/ DC converter
Product Description
Ordering Key G 3496 0008 700
G 3496 0008 is designed as a cost-effective solution for interfacing Dupline® I/O’sto the Koyo DL05 Micro PLC family. It performs three functions:Dupline®channel
generator, power supply syn- chronization(enables 3-wire system with supply) and RS232/RS422/RS485 inter- face.
Type: Dupline® H4-Housing Combined module Interface type
DC supply
Type Selection
SupplyPLC Interface Conformance Ordering no.
20-30 VDCDL05 Micro PLC familyG 3496 0008 700
Input/Output Specifications
Power Output
Output voltage20-30 VDC (pulsating)
Output current< 3.0 A @ 50°C
Short circuit protection 4 A quick acting fuse
Output voltage drop < 1.0 V
Dupline®carrier
Output voltage8.2 V (pulsating)
Current < 60 mA
Short circuit protection Yes
Scan time
128 channels132.2 ms
64 channels69.8 ms
Communication Port
Standard RS232/RS422/RS485
Connection 9 pole female Sub-D
Dielectric voltage
Com-port - Dupline® 1 kVAC (rms)
ProtocolModbus-RTU (function
code 01 and 15)
Channel Configuration in PLC
Baud rate
9600
Data bits 8
Start bit 1
Stop bit 1
ParityNone
Flow-controlNone
Input/Output Specifications (Cont.)
Device no.1
Pin assignment
2-wire RS485
S/R Data line+ (B)3
S/R Data line– (A)8
GND 5
4-wire RS485/RS422
R Data line + (B)3
R Data line - (A) 8
S Data line + (B)2
S Data line - (A) 7
Direction 4 (Connect pin 5 to GND
when using 4-wire com.)
RS232
TX 1
RX9
GND 5
Supply Specifications
Power supplyOvervoltage cat. III (IEC 60664)
Operational voltage (Vin) 20-30 VDC Reverse polarity protectionNone
Current consumption< 150 mA + Power load
Power dissipation < 5 W Transient protection voltage800 V Dielectric voltage
Supply – Dupline®None
Supply – Com-port 1 kVAC (rms)
Note: Use individual power supplies for all G349600xx700, as the input are not galvanic isolated from each other.
Specifications are subject to change without notice (04.12.2014)1
Title: | Size: | Type: |
---|---|---|
PDF CATALOG CARLO GAVAZZI EN.pdf | 13 Mbytes | |
Download general catalog |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.