EM2696AV63HI3S1PFB CARLO GAVAZZI Selected parameters FUNCTION MID Energy analyzer MOUNTING Panel POWER SUPPL.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

EM2696AV63HI3S1PFB CARLO GAVAZZI Selected parameters FUNCTION MID Energy analyzer MOUNTING Panel POWER SUPPL..

EM2696AV63HI3S1PFB

CARLO GAVAZZI

Selected parameters FUNCTION MID Energy analyzer MOUNTING Panel POWER SUPPLY 90 to 260V AC/DC OUTPUT DIGITAL INPUT Digital Input INPUT TYPE 3-phase AC CONNECTION CT/VT COMMUNICATION RS485 Others RANGE 70V to 250 VLL 1/5(10)A DISPLAY 7+1 DGT VARIABLES kWh, kvarh, VLL, VLN, Admd, VA, VAdmd, Vadmd, max, W, Wdmd, Wdmd max, var, PF, Hz, Phase-sequence DIGITAL INPUTS 3 PULSE none ALARMS none ANALOGUE none

More details


Home > CARLO GAVAZZI

* Brand new product in its original packaging covered by the warranties and certifications provided by CARLO GAVAZZI

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Energy Management Energy Analyzer Type EM26 96
● M-bus communication by means of VMU-B adapter
● Application adaptable display and programming procedure (Easyprog function)
● Easy connections management
● Certified according to MID Directive (option PF only):
see “how to order” below
● Other versions available (not certified, option XX):
see “how to order” on the next page
Product Description
● Class 1 (kWh) according to EN62053-21
● Class B (kWh) according to EN50470-3
● Class 2 (kvarh) according to EN62053-23
● Accuracy ±0.5% RDG (current/voltage)
● Dual colour backlight: no backlight, blue or white (selectable)
● Energy analyzer
● Instantaneous variables readout: 4 DGT
● Energies/gas/water readout: 8 DGT
● System variables: VLL, VLN, Admd, VA, VAdmd, VAdmd max, W, Wdmd, Wdmd max, var, PF, Hz, Phase-sequence.
● Single phase variables: VLL, VLN, A, VA, W, var, PF
● Energy measurements: total and partial kWh and kvarh or based on 4 different tariffs single phase measurements
● Gas, cold water, hot water, kWh remote heating measurements
● Hour counter (6+2 DGT)
● Harmonic analysis (FFT) up to 15th harmonic (current/voltage)
● TRMS measurements of distorted sine waves (voltages/currents)
● Universal power supply: 90 to 260AC/VDC
● 3 digital inputs for tariff selection, DMD synch or gas/water (hot- cold) and remote heating metering (on request)
● 3 digital outputs for pulses or for alarms or as a mix of them
(on request)
● Front dimensions: 96x96mm
● Protection degree (front): IP50
● RS485 serial output (on request) (MODBUS-RTU), iFIX SCADA
compatibility
Three-phase energy analyzer with built-in configuration joy- stickand LCD data displaying particularly indicated for active andreactiveenergymetering
and for cost allocation. Housing for panel mounting with IP50 (front) protection degree. Exter- nal Current and potential trans- formersconnection.Moreover
the meter can be provided with digital outputs that can be used: for pulses proportional to the active and reactive energy being measured or for alarm outputs,
or for remote control. RS485 communication port and 3 digi- talinputsare available asan option.
MID
CertifiedaccordingtoMIDDirective,Annex "B" + Annex "D" for legal metrology relevant to active electrical energy meters (see Annex MI-
003ofMID).Canbeusedforfiscal(legal)
How to order EM26 96 AV5 3 H O3 S1 PF A
Model Range code System
metrology.Only thetotalpositiveenergy meter is certified
according to MID.
Type Selection
Power supply Input/Output Communication Options Measurement
Range codes
AV5: 230 VLN/400VLL
1/5(10)A
VLN : 160 V to 480 VLN
VLL : 277 V to 830 VLL
AV6: 120 VLN/208VLL
1/5(10)A
VLN : 40 V to 144 VLN
VLL : 70 V to 250 VLL
System
3:3-phase, 4-wire
Power supply
H: 90 to 260VAC/DC (48 to 62Hz)
Communication
XX:none
S1: RS485 port
Input/Output
O1:single open collector type
(pulse or alarm)
O3:3 open collector type (mixed combination of pulse, alarm and/or remote output)
R2:dual relay type (functions as per “O3”)
I3:3 digital inputs for tariff selection or Gas/water/ energy/remote heating metering
Options
PF: Certified according to MID Directive, Annex "B" + Annex "D" for legal metrology relevant to active electrical energy meters (see Annex MI-003 of MID). Can be used for fiscal (legal) metrology.
Measurement
A:The power is always integrated (both in case of positive and negative power) and the total energy meter is certified according to MID.
AV53
AV6
H O1XX O3S1
R2
I3 S1
A PFB
NOTE: please check the availability of the needed code on the verification path diagram on left before order.
B:Only the total positive energy meter is certified according to MID. The negative energy meter is not certified according to MID.
Specifications are subject to change without noticeEM2696 DS ENG 0610141

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.