PTA02CD48 CARLO GAVAZZI POWER SUPPLY RANGE 24÷48 VAC/DC MONITORING FUNCTION Over temperature MOUTING Plug-i..

PTA02CD48

CARLO GAVAZZI

Available

Ship on today

POWER SUPPLY RANGE 24÷48 VAC/DC MONITORING FUNCTION Over temperature MOUTING Plug-in INPUT RANGE PTC OTHERS Reset function

More details


Energy Meters Control Analizers

Controls

Monitoring Relays and Measurement Current Transformers

* Brand new product in its original packaging covered by the warranties and certifications provided by CARLO GAVAZZI

Quantity Price
1+$113.78
4+$102.87
8+$99.30
11+$97.96
15+$96.95
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Monitoring Relays
Motor temperature
Types DTA01, PTA01, DTA02, PTA02
• Motor temperature monitoring relay
• Measuring ranges: PTC according to EN 44081
• Remote and local alarm reset (DTA02, PTA02)
• Output: 8 A SPDT (PTA01/DTA01/DTA02) or SPST (DTA01) relay, normally energized
• For mounting on DIN-rail in accordance with DIN/EN
50 022 (DTA01, DTA02) or plug-in module (PTA01, PTA02)
• 22.5 mm Euronorm housing (DTA01, DTA02) or
36 mm plug-in module (PTA01, PTA02)
• LED indication for relay and power supply ON (DTA02, PTA02)
• Galvanically separated power supply
DTA01, DTA02PTA01, PTA02
Product Description Ordering Key
DTA 01 C 230
DTA01, DTA02, PTA01 and PTA02 are precisethermis- tor monitoring relays.
They can be used to monitor the temperature of the coils of a motor with built-in PTC’s.The alarm statusof therelaycanberesetby
either an external contact or an internal button (DTA02, PTA02).
The testbuttonallowsthe simulation of the fault condi- tion (DTA02, PTA02).
The redLED indicatesthe alarm status.
Housing Function Type
Item number
Output
Power supply
Type Selection
Mounting OutputSupply: 24 to 48 VAC/DC Supply: 115 VACSupply: 230 VAC
DIN-rail SPSTDTA 01 CD 48 DTA 01 C 115 DTA 01 C 230
Plug-inSPDTPTA 01 CD 48 PTA 01 C 115PTA 01 C 230
DIN-rail SPDTDTA 02 CD 48 DTA 02 C 115 DTA 02 C 230
Plug-inSPDTPTA 02 CD 48 PTA 02 C 115PTA 02 C 230
InputSpecifications
Output Specifications
Input (PTC)DTA01, DTA02: Terminals T1, T2
PTA01, PTA02: Terminals 5, 6
Measuring ranges
Max cold PTC resistance 1500 Ω
Alarm setpoint 3100 Ω ± 10% Return setpoint 1650 Ω ± 10% Short-circuit detection0 to 10 Ω
Measurement voltage ≤ 2.5V (acc. to IEC 60034-11)
Contact input
DTA02 Terminals Z1, Z2
PTA02 Terminals 8, 9
Disabled > 10 kΩ Enabled< 500 Ω Alarm reset > 500 ms
OutputSPST or SPDT relay
Rated insulation voltage 250 VAC
Contact ratings (AgSnO2) µ
Resistive loadsAC 1 8 A @ 250 VAC DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC DC 13 2.5 A @ 24 VDC
Mechanical life≥ 30 x 106 operations
Electrical life≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency ≤ 7200 operations/h
Dielectric strength
Dielectric voltage≥ 2 kVAC (rms) Rated impulse withstand volt. 4 kV (1.2/50 µs)
Specifications are subject to change without notice (04.06.10)1

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.