T7V1250 M 1SDA062992R1 ABB T7V 1250 PR332/P LSIRc In 1250A 4p F F M View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

T7V1250 M 1SDA062992R1 ABB T7V 1250 PR332/P LSIRc In 1250A 4p F F M

1SDA062992R1

ABB

T7V 1250 PR332/P LSIRc In=1250A 4p F F M

More details


Low-voltage industrial components > Power circuit-breaker for trafo/generator/installation protection

Molded case "Isomax-Tmax" > T7

* Brand new product in its original packaging covered by the warranties and certifications provided by ABB

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Ordering

EAN: 8015644655419
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090

Dimensions

Product Net Width: 280 mm
Product Net Height: 268 mm
Product Net Depth / Length: 178 mm
Product Net Weight: 14 kg

Container Information

Package Level 1 Units: 1 piece
Package Level 1 Width: 360 mm
Package Level 1 Height: 350 mm
Package Level 1 Depth / Length: 360 mm
Package Level 1 Gross Weight: 15.5 kg
Package Level 1 EAN: 8015644655419

Additional Information

Electrical Durability: 3000 cycle
60 cycles per hour
Mechanical Durability: 10000 cycle
60 cycles per hour
Number of Poles: 4
Power Loss: at Rated Operating Conditions per Pole 78,3 W
Product Main Type: SACE Tmax T
Product Name: Moulded Case Circuit Breaker
Product Type: CB
Rated Current (In): Main Circuit 1250 A
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Insulation Voltage (Ui): 1000 V
Rated Operational Voltage: 690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 200 kA
(230 V AC) 200 kA
(380 V AC) 150 kA
(400 V AC) 150 kA
(415 V AC) 150 kA
(440 V AC) 130 kA
(500 V AC) 100 kA
(690 V AC) 45 kA
Rated Short-time Withstand Current (Icw): for 1 s 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (220 V AC) 200 kA
(230 V AC) 200 kA
(380 V AC) 150 kA
(400 V AC) 150 kA
(415 V AC) 150 kA
(440 V AC) 130 kA
(500 V AC) 100 kA
(690 V AC) 60 kA
Rated Uninterrupted Current (Iu): 1250 A
Release Type: EL
Standards: IEC
Sub-type: T7
Suitable For: T7M
Suitable for Product Class: Moulded Case Circuit Breakers
Terminal Connection Type: Fixed Circuit-Breakers
Front
Version: F

Certificates and Declarations (Document Number)

Data Sheet, Technical Information: 1SDC210015D0201
Declaration of Conformity - CE: 1SDL000165R0007
Environmental Information: 1SDC210015D0201
GL Certificate: 1SDL000163R0056
Instructions and Manuals: 1SDC210015D0201
RoHS Information: 1SDL000201R0001

Classifications

ETIM 4: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 6: EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 7: EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code: Q
UNSPSC: 39120000
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.