More info



ProductTEFC, 3-phase, squirrel cage induction motor
Product code3GGP 182 410-BDLCalc. ref.3GZF021018-145
Type/FrameM3GP 180MLA 4
MountingIM3011, V1(flange)
Rated output PN18.5kW
Service factor1
Type of dutyS1(IEC) 100%
Rated voltage UN400VD± 5 % (IEC 60034-1)
Rated frequency fN50Hz± 2 % (IEC 60034-1)
Rated speed nN1481r/min
Rated current IN34,9A
No-load current12.6A
Starting current Is/IN7.2Meet IEC 60034-12, N,(H at 60 Hz)
Nominal torque TN119Nm
Locked rotor torque TS/TN2.8
Maximum torque Tmax/TN3
Minimum torque Tmin/TN2,0
Speed at minimum torque825r/min
Load characteristics (IEC 60034-2-1:2014)Load %Current AEfficiency %Power factor
PLL determined from residual loss10034,992,6 / IE30.83
7526,993.20.8
5020,892.90.69
Start2510.4
Maximum starting time from hot11s
Maximum starting time from cold19s
Insulation class / Temperature classF / B
Ambient temperature,-20 up to +50ºC°C
Altitude1000m.a.s.l.
EnclosureIP55
Cooling systemIC411 self ventilated
Bearing DE/NDENU6310 - 6209/C3
Type of Grease
Sound pressure level (LP dB(A) 1m)60dB(A)at load
Moment of inertia J = ¼ GD20,219kg-m2
Balancing
Vibration class
Position of terminal boxTop
Terminal box entries; no, dimens.
Number of power terminals
Direction of rotationCW or CCW
Weight of rotor56kg
Total weight of motor215kg
Dimension drawing no.
Ex-motors
Type of protectionEx ec IIC T3 Gc
EC Type Examination NoDEMKO 18 ATEX 2076 X
Option Variant Codes / Definition
+066 Modified for non-standard mounting position
+002 Restamping voltage, frequency and output, continuous duty
396 Motor disigned for minimum mbient temperature -20 to -40ºC
037 Roller bearing at D-end

Datasheet - PDF

Title: Size: Type:
PDF CATALOGUE LOW VOLTAGE2 ABB EN.pdf 25 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.