2CCS862001R1557 ABB High Performance Circuit Breaker S800S Tripping characteristic K Number of poles 2 Rated.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

2CCS862001R1557 ABB High Performance Circuit Breaker S800S Tripping characteristic K Number of poles 2 Rated..

2CCS862001R1557

ABB

High Performance Circuit Breaker - S800S - Tripping characteristic K - Number of poles 2 - Rated operational current 40A - Rated operational voltage 250V DC

Int.aut. S802S-UCK40 2p 40A UCK 50kA

More details


Circuit breakers and fuses > Miniature circuit breaker (MCB)

Industrial > S800S-UC

Brand new product in its original packaging covered by the warranties and certifications provided by ABB

* This article is restricted. Please ask us for a quotation and we will check if there are units available or we will offer you an alternative product.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



S802S-UCK40 High Performance Miniature Circuit Breaker 2 Poles K Characteristic 40A 50kA 250VDC

Ordering

  • EAN:
    7612271203504
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85362020

Dimensions

  • Product Net Width:
    54mm
  • Product Net Depth:
    82.5mm
  • Product Net Height:
    95mm
  • Product Net Weight:
    0.49kg

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    105 mm
  • Package Level 1 Length:
    60 mm
  • Package Level 1 Height:
    99 mm
  • Package Level 1 Gross Weight:
    0.51 kg
  • Package Level 1 EAN:
    7612271203504
  • Package Level 2 Units:
    1

Environmental

  • Ambient Air Temperature:
    Operation -25 ... +60 °C
    Storage -40 ... +70 °C
  • RoHS Status:
    Following EU Directive 2002/95/EC August 18, 2005 and amendment

Technical

  • Standards:
    IEC/EN 60947-2
  • Number of Poles:
    2
  • Tripping Characteristic:
    UC-K
  • Rated Current (In):
    40 A
  • Rated Operational Voltage:
    500 V DC
  • Power Loss:
    7.4 W
  • Rated Ultimate Short-Circuit Breaking Capacity (Icu):
    (500 V DC) 50 kA
  • Rated Service Short-Circuit Breaking Capacity (Ics):
    (500 V DC) 50 kA
  • Contact Position Indication:
    ON / OFF / TRIP
  • Connecting Capacity:
    Flexible 1 ... 50 mm²
    Flexible Stranded
    1 …70 mm²

Certificates and Declarations (Document Number)

Classifications

  • ETIM 4:
    EC000042 - Miniature circuit breaker (MCB)
  • ETIM 5:
    EC000042 - Miniature circuit breaker (MCB)
  • Object Classification Code:
    F

ETIM for 2CCS862001R1557 Circuit breakers and fuses (EC000042)
Feature Name Feature Value
Built-in depth (EF000218) 82.5 mm
Release characteristic (EF000889) Other
Number of poles (total) (EF008618) 2
Number of protected poles (EF005548) 2
Rated current (EF000227) 40 A
Rated insulation voltage Ui (EF001366) 1500 V
Rated impulse withstand voltage Uimp (EF011980) 8 kV
Voltage type (EF000187) DC
Frequency (EF000416) 0 Hz
Current limiting class (EF002568) 3
Flush-mounted installation (EF007517) No
Concurrently switching neutral conductor (EF005997) No
Over voltage category (EF002569) 3
Pollution degree (EF002570) 2
Additional equipment possible (EF008148) Yes
Width in number of modular spacings (EF002950) 3
Degree of protection (IP) (EF005474) IP20
Ambient temperature during operating (EF007515) -25 °C
Connectable conductor cross section multi-wired (EF007343) 0 mm²
Connectable conductor cross section solid-core (EF007337) 0 mm²
Explosion-proof (EF004663) No

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.