CC-E/RTD 1SVR011706R2200 ABB CC-E/RTD Temp. converter, univers. PT100 / V/I, 110-240VAC View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

CC-E/RTD 1SVR011706R2200 ABB CC-E/RTD Temp. converter, univers. PT100 / V/I, 110-240VAC

CC-E/RTD

1SVR011706R2200

ABB

CC-E/RTD Temp. converter, univers. PT100 / V/I, 110-240VAC

More details


Converters > C.A.I.S-E converters

* Brand new product in its original packaging covered by the warranties and certifications provided by ABB

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



The CC-E/RTD is an universal temperature signal converter from the CC-E range. This converter, with 3-way electrical isolation, for RTD sensors (PT100, 2- or 3-wire connection), operates with a rated control supply voltage of 110-240 V AC and provides a configurable detection of input signal interruption (low fail safe / high fail safe). The 6 input temperature ranges (0…100 °C, 0…300 °C, 0…500 °C, -50…+ 50 °C, -50…+250 °C, -50…+450 °C) and the 3 output signal ranges (0-10 V, 0-20 mA, 4-20 mA) can be configured by means of directly accessible lateral DIP switches. The adjustment of the gain and the offset is made via potentiometers on the front of the unit. Applied supply voltage is displayed by a green LED.

Ordering

  • EAN:
    4013614351716
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85369085

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    81 mm
  • Package Level 1 Length:
    27 mm
  • Package Level 1 Height:
    109 mm
  • Package Level 1 Gross Weight:
    0.112 kg

Dimensions

  • Product Net Width:
    22.5mm
  • Product Net Height:
    75mm
  • Product Net Depth:
    107mm
  • Product Net Weight:
    0.093kg

Technical

  • Function:
    RTD sensor signals
    Multifunction
  • Input Signal:
    0 ... 100 °C / 0 ... 500 °C / -50 ... +50 °C / -50 ... +450 °C
  • Output Signal:
    0 ... 10 V / 0 ... 20 mA / 4 ... 20 mA
  • Rated Control Supply Voltage (Us):
    110 ... 240 V AC

Environmental

  • RoHS Status:
    Following EU Directive 2002/95/EC August 18, 2005 and amendment

Certificates and Declarations (Document Number)

Classifications

  • Object Classification Code:
    T
  • ETIM 4:
    EC002653 - Isolation amplifier
  • ETIM 5:
    EC002653 - Isolation amplifier
  • UNSPSC:
    39120000
  • eClass:
    7.0 27210120

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.