AF30Z-30-11-20 1SBL276001R2011 ABB AF30Z-30-11-20 12-20VDC Contactor View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

AF30Z-30-11-20 1SBL276001R2011 ABB AF30Z-30-11-20 12-20VDC Contactor

1SBL276001R2011

ABB

AF30Z-30-11-20 12-20VDC Contactor

More details


Low-voltage industrial components > Power contactor, AC switching

Contactors and overload relays > AF contactors to 38 A

* Brand new product in its original packaging covered by the warranties and certifications provided by ABB

Total price: $158.27
Unit price: $158.27

Quantity Price
1+$158.27
2+$149.26
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



AF30Z contactors are used for controlling power circuits up to 690 V AC and 220 V DC. They are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads. AF..Z contactors include an electronic coil interface accepting a wide control voltage Uc min. ... Uc max. Only four coils cover control voltages between 24...250 V 50/60 Hz or 12...250 V DC. AF..Z contactors can manage large control voltage variations. One coil can be used for different control voltages used worldwide without any coil change. AF..Z contactors allow direct control by PLC-output ≥ 24 V DC 500 mA and obtain a reduced holding coil consumption. AF..Z contactors withstand short voltage dips and voltage sags (SEMI F47-0706 compliance) between 24...250 V 50/60 Hz AF..Z contactors have built-in surge protection and do not require additional surge suppressors The AF... series 2-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles with a non-removable front-mounted 1 N.O. + 1 N.C. auxiliary contact block, side-mounted add-on auxiliary contact blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1 including the "Mechanically Linked" symbol on the contactor side. N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: DC operated for AF..Z-30-..-20 contactors. Only AF..Z-30-..-20 contactors need to respect the polarity on the coil terminals (A1+ and A2-). - Accessories: a wide range of accessories is available. Note: 2-stack contactors available in some countries: please consult your ABB representative.

Ordering

  • EAN:
    3471523114500
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85369085

Dimensions

  • Product Net Width:
    45mm
  • Product Net Depth:
    111.5mm
  • Product Net Height:
    86mm
  • Product Net Weight:
    0.390kg

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    87 mm
  • Package Level 1 Length:
    114 mm
  • Package Level 1 Height:
    47 mm
  • Package Level 1 Gross Weight:
    0.39 kg
  • Package Level 1 EAN:
    3471523114500
  • Package Level 2 Units:
    36 piece
  • Package Level 2 Width:
    250 mm
  • Package Level 2 Length:
    300 mm
  • Package Level 2 Height:
    315 mm
  • Package Level 3 Units:
    864 piece

Technical

  • Number of Main Contacts NO:
    3
  • Number of Main Contacts NC:
    0
  • Number of Auxiliary Contacts NO:
    1
  • Number of Auxiliary Contacts NC:
    1
  • Standards:
    IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14
  • Rated Operational Voltage:
    Auxiliary Circuit 690 V
    Main Circuit 690 V
  • Rated Frequency (f):
    Auxiliary Circuit 50 / 60 Hz
    Main Circuit 50 / 60 Hz
  • Conventional Free-air Thermal Current (Ith):
    acc. to IEC 60947-4-1, Open Contactors q = 40 °C 50 A
    acc. to IEC 60947-5-1, q = 40 °C 16 A
  • Rated Operational Current AC-1 (Ie):
    (690 V) 40 °C 50 A
    (690 V) 60 °C 42 A
    (690 V) 70 °C 37 A
  • Rated Operational Current AC-3 (Ie):
    (220 / 230 / 240 V) 60 °C 33 A
    (380 / 400 V) 60 °C 32 A
    (415 V) 60 °C 32 A
    (440 V) 60 °C 32 A
    (500 V) 60 °C 28 A
    (690 V) 60 °C 21 A
  • Rated Operational Power AC-3 (Pe):
    (220 / 230 / 240 V) 9 kW
    (380 / 400 V) 15 kW
    (415 V) 15 kW
    (440 V) 18.5 kW
    (500 V) 18.5 kW
    (690 V) 18.5 kW
  • Rated Operational Current AC-15 (Ie):
    (220 / 240 V) 4 A
    (24 / 127 V) 6 A
    (400 / 440 V) 3 A
    (500 V) 2 A
    (690 V) 2 A
  • Rated Short-time Withstand Current (Icw):
    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 50 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 700 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
    for 0.1 s 140 A
    for 1 s 100 A
  • Maximum Breaking Capacity:
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 200 A
  • Maximum Electrical Switching Frequency:
    AC-1 600 cycles per hour
    AC-15 1200 cycles per hour
    AC-2 / AC-4 150 cycles per hour
    AC-3 1200 cycles per hour
    DC-13 900 cycles per hour
  • Rated Operational Current DC-13 (Ie):
    (110 V) 0.55 A / 60 W
    (125 V) 0.55 A / 69 W
    (220 V) 0.27 A / 60 W
    (24 V) 6 A / 144 W
    (250 V) 0.27 A / 68 W
    (400 V) 0.15 A / 60 W
    (48 V) 2.8 A / 134 W
    (500 V) 0.13 A / 65 W
    (600 V) 0.1 A / 60 W
    (72 V) 1 A / 72 W
  • Rated Insulation Voltage (Ui):
    acc. to UL/CSA 600 V
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
  • Rated Impulse Withstand Voltage (Uimp):
    6 kV
  • Maximum Mechanical Switching Frequency:
    3600 cycles per hour
  • Rated Control Circuit Voltage (Uc):
    DC Operation 12 ... 20 V
  • Operate Time:
    Between Coil De-energization and NC Contact Closing 13...98 ms
    Between Coil De-energization and NO Contact Opening 11...95 ms
    Between Coil Energization and NC Contact Opening 38...90 ms
    Between Coil Energization and NO Contact Closing 40...95 ms
  • Connecting Capacity-Main Circuit:
    Flexible with Insulated Ferrule 1x 1.5...10 mm²
    Flexible with Insulated Ferrule 2x 1.5...4 mm²
    Flexible with Ferrule 1/2x 1.5...10 mm²
    Rigid 1/2x 2.5...10 mm²
  • Connecting Capacity-Auxiliary Circuit:
    Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
    Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
    Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
    Rigid 1/2x 1...2.5 mm²
  • Connecting Capacity-Control Circuit:
    Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
    Flexible with Insulated Ferrule 1x 0.75...2.5 mm²
    Flexible with Insulated Ferrule 2x 0.75...1.5 mm²
    Rigid 1/2x 1...2.5 mm²
  • Wire Stripping Length:
    Auxiliary Circuit 10 mm
    Control Circuit 10 mm
    Main Circuit 14 mm
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
    acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
  • Terminal Type:
    Screw Terminals

Environmental

  • Ambient Air Temperature:
    Close to Contactor for Storage -60...+80 °C
    Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
    Close to Contactor without Thermal O/L Relay -40 ... +70 °C
  • Maximum Operating Altitude Permissible:
    3000 m
  • Resistance to Shock acc. to IEC 60068-2-27:
    Closed, Shock Direction: B1 25 g
    Open, Shock Direction: B1 5 g
    Shock Direction: A 30 g
    Shock Direction: B2 15 g
    Shock Direction: C1 25 g
    Shock Direction: C2 25 g
  • Resistance to Vibrations acc. to IEC 60068-2-6:
    5...300 Hz 4 g closed position / 2 g open position
  • RoHS Status:
    Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2008 Q1

Technical UL/CSA

  • General Use Rating UL/CSA:
    (600 V AC) 50 A
  • Horsepower Rating UL/CSA:
    (120 V AC) Single Phase 2 Hp
    (240 V AC) Single Phase 5 Hp
    (200 ... 208 V AC) Three Phase 10 Hp
    (220 ... 240 V AC) Three Phase 10 Hp
    (440 ... 480 V AC) Three Phase 20 Hp
    (550 ... 600 V AC) Three Phase 25 Hp
  • Tightening Torque UL/CSA:
    Auxiliary Circuit 11 in·lb
    Control Circuit 11 in·lb
    Main Circuit 22 in·lb

Certificates and Declarations (Document Number)

Classifications

  • ETIM 5:
    EC000066 - Magnet contactor, AC-switching
  • UNSPSC:
    39121529

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.