1SBL236061R2200 ABB AF26ZB-30-00CONT.TRAC.BOB.48-130VAC-DC View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

1SBL236061R2200 ABB AF26ZB-30-00CONT.TRAC.BOB.48-130VAC-DC

1SBL236061R2200

ABB

AF26ZB-30-00CONT.TRAC.BOB.48-130VAC-DC

AF26ZB-30-00-22 48-130V50/60HZ-DC Contactor

More details


Low-voltage industrial components > Power contactor, AC switching

Contactors and overload relays > AF contactors to 38 A

Brand new product in its original packaging covered by the warranties and certifications provided by ABB

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Ordering
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
Data Sheet, Technical Information1SBC100220C0201
Instructions and Manuals1SBC101027M6801
Instructions and Manuals (Part 2)1SAC200017M0002
CAD Dimensional Drawing2CDC001079B0201
Dimensions
Product Net Width45 mm
Product Net Depth / Length86 mm
Product Net Height86 mm
Product Net Weight0.37 kg
Technical
Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC0
Number of Poles3P
StandardsIEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational VoltageMain Circuit 690 V
Rated Frequency (f)Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 50 A
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 45 A
(690 V) 60 °C 40 A
(690 V) 70 °C 32 A
Rated Operational Current AC-3 (Ie)(415 V) 60 °C 26 A
(440 V) 60 °C 26 A
(500 V) 60 °C 23 A
(690 V) 60 °C 17 A
(380 / 400 V) 60 °C 26 A
(220 / 230 / 240 V) 60 °C 26 A
Rated Operational Current AC-3e (Ie)(415 V) 60 °C 26 A
(440 V) 60 °C 26 A
(500 V) 60 °C 23 A
(690 V) 60 °C 17 A
(380 / 400 V) 60 °C 26 A
(220 / 230 / 240 V) 60 °C 26 A
Rated Operational Current DC-1 (Ie)(110 V) 2 Poles in Series, 40 °C 45 A
(110 V) 2 Poles in Series, 60 °C 40 A
(110 V) 2 Poles in Series, 70 °C 32 A
(110 V) 3 Poles in Series, 40 °C 45 A
(110 V) 3 Poles in Series, 60 °C 40 A
(110 V) 3 Poles in Series, 70 °C 32 A
(220 V) 3 Poles in Series, 40 °C 45 A
(220 V) 3 Poles in Series, 60 °C 40 A
(220 V) 3 Poles in Series, 70 °C 32 A
(72 V) 1-Pole, 40 °C 45 A
(72 V) 1-Pole, 60 °C 40 A
(72 V) 1-Pole, 70 °C 32 A
(72 V) 2 Poles in Series, 40 °C 45 A
(72 V) 2 Poles in Series, 60 °C 40 A
(72 V) 2 Poles in Series, 70 °C 32 A
(72 V) 3 Poles in Series, 40 °C 45 A
(72 V) 3 Poles in Series, 60 °C 40 A
(72 V) 3 Poles in Series, 70 °C 32 A
Rated Operational Current DC-3 (Ie)(110 V) 2 Poles in Series, 40 °C 45 A
(110 V) 2 Poles in Series, 60 °C 40 A
(110 V) 2 Poles in Series, 70 °C 32 A
(110 V) 3 Poles in Series, 40 °C 45 A
(110 V) 3 Poles in Series, 60 °C 40 A
(110 V) 3 Poles in Series, 70 °C 32 A
(220 V) 3 Poles in Series, 40 °C 45 A
(220 V) 3 Poles in Series, 60 °C 40 A
(220 V) 3 Poles in Series, 70 °C 32 A
(72 V) 1-Pole, 40 °C 45 A
(72 V) 1-Pole, 60 °C 40 A
(72 V) 1-Pole, 70 °C 32 A
(72 V) 2 Poles in Series, 40 °C 45 A
(72 V) 2 Poles in Series, 60 °C 40 A
(72 V) 2 Poles in Series, 70 °C 32 A
(72 V) 3 Poles in Series, 40 °C 45 A
(72 V) 3 Poles in Series, 60 °C 40 A
(72 V) 3 Poles in Series, 70 °C 32 A
Rated Operational Current DC-5 (Ie)(110 V) 2 Poles in Series, 40 °C 45 A
(110 V) 2 Poles in Series, 60 °C 40 A
(110 V) 2 Poles in Series, 70 °C 32 A
(110 V) 3 Poles in Series, 40 °C 45 A
(110 V) 3 Poles in Series, 60 °C 40 A
(110 V) 3 Poles in Series, 70 °C 32 A
(220 V) 3 Poles in Series, 40 °C 20 A
(220 V) 3 Poles in Series, 60 °C 20 A
(220 V) 3 Poles in Series, 70 °C 20 A
(72 V) 1-Pole, 40 °C 20 A
(72 V) 1-Pole, 60 °C 20 A
(72 V) 1-Pole, 70 °C 20 A
(72 V) 2 Poles in Series, 40 °C 45 A
(72 V) 2 Poles in Series, 60 °C 40 A
(72 V) 2 Poles in Series, 70 °C 32 A
(72 V) 3 Poles in Series, 40 °C 45 A
(72 V) 3 Poles in Series, 60 °C 40 A
(72 V) 3 Poles in Series, 70 °C 32 A
Rated Operational Power AC-3 (Pe)(415 V) 11 kW
(440 V) 15 kW
(500 V) 15 kW
(690 V) 15 kW
(380 / 400 V) 11 kW
(220 / 230 / 240 V) 6.5 kW
Rated Operational Power AC-3e (Pe)(415 V) 11 kW
(440 V) 15 kW
(500 V) 15 kW
(690 V) 15 kW
(380 / 400 V) 11 kW
(220 / 230 / 240 V) 6.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 50 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 700 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 200 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)6 kV
Maximum Electrical Switching Frequency(AC-1) 600 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 1200 cycles per hour
Maximum Mechanical Switching Frequency3600 cycles per hour
Rated Control Circuit Voltage (Uc)50 Hz 48 ... 130 V
60 Hz 48 ... 130 V
DC Operation 48 ... 130 V
Power Lossat Rated Operating Conditions AC-1 per Pole 1.8 W
at Rated Operating Conditions AC-3 per Pole 0.6 W
Operate TimeBetween Coil De-energization and NC Contact Closing 13 ... 98 ms
Between Coil De-energization and NO Contact Opening 11 ... 95 ms
Between Coil Energization and NC Contact Opening 38 ... 90 ms
Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied) 2 x M4 Screws Placed Diagonally
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 1.5 ... 10 mm²
Flexible with Insulated Ferrule 1x 1.5 ... 10 mm²
Flexible with Insulated Ferrule 2x 1.5 ... 4 mm²
Rigid Solid 1/2x 2.5 ... 4 mm²
Rigid Stranded 1/2x 2.5 ... 10 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid Solid 1/2x 1 ... 2.5 mm²
Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping LengthControl Circuit 10 mm
Main Circuit 14 mm
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening TorqueControl Circuit 1.2 N·m
Main Circuit 2.5 N·m
Terminal TypeScrew Terminals
Product NameBlock Contactor
Technical UL/CSA
NEMA Size1
Continuous Current Rating NEMA27 A
Horsepower Rating NEMA(115 V AC) Single Phase 2 Hp
(200 V AC) Three Phase 7-1/2 Hp
(230 V AC) Single Phase 3 Hp
(230 V AC) Three Phase 7-1/2 Hp
(460 V AC) Three Phase 10 Hp
(575 V AC) Three Phase 10 Hp
Maximum Operating Voltage UL/CSAMain Circuit 600 V
General Use Rating UL/CSA(600 V AC) 45 A
Horsepower Rating UL/CSA(120 V AC) Single Phase 2 hp
(200 ... 208 V AC) Three Phase 7-1/2 hp
(220 ... 240 V AC) Three Phase 7-1/2 hp
(240 V AC) Single Phase 3 hp
(440 ... 480 V AC) Three Phase 15 hp
(550 ... 600 V AC) Three Phase 20 hp
Connecting Capacity Main Circuit UL/CSARigid Solid 1/2x 14-10 AWG
Rigid Stranded 1/2x 14-8 AWG
Connecting Capacity Control Circuit UL/CSARigid Solid 1/2x 18-14 AWG
Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSAControl Circuit 11 in·lb
Main Circuit 22 in·lb
Full Load Amps Motor Use(120 V AC) Single Phase 24 A
(200 ... 208 V AC) Three Phase 25.3 A
(220 ... 240 V AC) Three Phase 22 A
(240 V AC) Single Phase 17 A
(440 ... 480 V AC) Three Phase 21 A
(550 ... 600 V AC) Three Phase 22 A
Environmental
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C
Close to Contactor without Thermal O/L Relay -40 ... 70 °C
Close to Contactor for Storage -60 ... +80 °C
Climatic WithstandCategory B according to IEC 60947-1 Annex Q
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373Category 1, Class B
Pollution Degree3
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIPd70f8eae-81f1-4adf-8ee9-d05bdf5daf0d China
Simplified SCIPd4c6f01d-c8db-4d55-9780-c9968dbf3a7f Finland
c7974796-f5fc-4fd3-a51b-77e8c026f9ee Belgium
25d3bdbd-ed98-4d17-89ba-493dfd40decb Norway
daf2490c-f761-4c29-81cd-7eb9dbdef3c8 Poland
112df531-6155-4c91-a8f7-c26944b9b408 Sweden
f825d4e1-305d-4fed-97e6-6e291691b529 Portugal
d32978e3-d492-4b2b-b884-be7e3bdf00a5 Bulgaria
cca3a15d-f7c9-4762-85d1-27a049c82355 France
f76f0099-0df5-4ac3-981a-4e50065db74e Hungary
c79f4915-a712-4f83-b9c6-a4e3e8eb7040 Germany
877abd8d-cc42-4e62-bddc-18ac8c469c78 France
e2873c25-cbc6-4aed-b355-9b719cd0cd77 Netherlands
0f02227f-1802-4bd3-ba4f-ee2108b236e8 Sweden
04b6223d-7dac-4c16-a9da-780c0b5a6808 Germany
50e9f47e-8720-4316-83de-d9afa4acf586 Belgium
6b1280b1-b0e9-4188-9a56-c6a945a874e3 Spain
183b315c-d5e0-4e26-a76f-a14523c4572a Germany
de15a7e1-a15e-4ee7-8df5-ac4eb6e29a91 Czech Republic
03371e32-d408-4372-aed0-61dc56b40645 Poland
b2a2ba73-056f-42fe-8194-2366c62d5dd8 Germany
1a41321f-2e42-4ff8-9719-10c320cda45a Denmark
ccdb5ea3-22eb-49ee-b664-7ca571edbd34 Germany
59b6bb47-14a8-4bb8-afc1-7918a4b9a61e Croatia
3bcc44d9-eaab-415c-add4-10e47975ab97 Hungary
e2d397e2-88fa-4a4f-a830-1345780c410c Poland
4a1a253f-a788-4a9b-9a74-63a800dacff3 Greece
a5083e1a-cab5-4197-916c-1d006319d91b Estonia
Toxic Substances Control Act - TSCA2CMT2023-006525
WEEE B2C / B2BBusiness To Business
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill
End Of Life Disassembling Instructions1SBC101080M6801
Environmental Product Declaration - EPD1SBD250584E4000
Improved Energy Efficiency for CustomersProduct Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 94.3 %
Certificates and Declarations
A2L Certificate – UL9AKK108469A4875
9AKK108469A4879
CB CertificateCB_SE-116364
CCC CertificateCCC_2024010304656668
CQC CertificateCQC2010010304445623
Declaration of Conformity - CCC2020980304001254
Declaration of Conformity - CE1SBD250002U1000
Declaration of Conformity - UKCA1SBD250033U1000
GOST CertificateGOST_POCCFR.ME77.B07175.pdf
KC CertificateKC_HW02016-15001C
UL CertificateUL-US-2150887-5
UL-CA-2142658-5
UL Listing CardE312527
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width87 mm
Package Level 1 Depth / Length87 mm
Package Level 1 Height47 mm
Package Level 1 Gross Weight0.37 kg
Package Level 1 EAN3471523124127
Package Level 2 Unitsbox 21 piece
Package Level 2 Width250 mm
Package Level 2 Depth / Length300 mm
Package Level 2 Height315 mm
Package Level 2 Gross Weight16.65 kg
External Classifications and Standards
Object Classification CodeQ
ETIM 7EC000066 - Power contactor, AC switching
ETIM 8EC000066 - Power contactor, AC switching
ETIM 9EC000066 - Power contactor, AC switching
eClassV11.0 : 27371003
UNSPSC39121529
IDEA Granular Category Code (IGCC)4758 >> Iec Contactors

Datasheet - PDF

Title: Size: Type:
PDF CATALOGUE MOTOR PROTECTION EN.pdf 240 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.