Product successfully added to your shopping cart
1SBL176060R2210
ABB
1
Low-voltage industrial components > Power contactor, AC switching
Contactors and overload relays > AF contactors to 38 A
Brand new product in its original packaging covered by the warranties and certifications provided by ABB
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SBC100220C0201 |
| Instructions and Manuals | 1SBC101035M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 77 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.32 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives. |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Main Circuit 690 V | |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Control Circuit 50 / 60 Hz | |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A |
| acc. to IEC 60947-5-1, Θ = 40 °C 16 A | |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 30 A |
| (690 V) 60 °C 30 A | |
| (690 V) 70 °C 26 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 18 A |
| (440 V) 60 °C 18 A | |
| (500 V) 60 °C 15 A | |
| (690 V) 60 °C 10.5 A | |
| (380 / 400 V) 60 °C 18 A | |
| (220 / 230 / 240 V) 60 °C 18 A | |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 18 A |
| (440 V) 60 °C 18 A | |
| (500 V) 60 °C 15 A | |
| (690 V) 60 °C 10.5 A | |
| (380 / 400 V) 60 °C 18 A | |
| (220 / 230 / 240 V) 60 °C 18 A | |
| Rated Operational Current AC-15 (Ie) | (500 V) 2 A |
| (690 V) 2 A | |
| (24 / 127 V) 6 A | |
| (220 / 240 V) 4 A | |
| (400 / 440 V) 3 A | |
| Rated Operational Current DC-1 (Ie) | (110 V) 1-Pole, 40 °C 20 A |
| (110 V) 1-Pole, 60 °C 20 A | |
| (110 V) 1-Pole, 70 °C 20 A | |
| (110 V) 2 Poles in Series, 40 °C 30 A | |
| (110 V) 2 Poles in Series, 60 °C 30 A | |
| (110 V) 2 Poles in Series, 70 °C 26 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 20 A | |
| (220 V) 2 Poles in Series, 60 °C 20 A | |
| (220 V) 2 Poles in Series, 70 °C 20 A | |
| (220 V) 3 Poles in Series, 40 °C 30 A | |
| (220 V) 3 Poles in Series, 60 °C 30 A | |
| (220 V) 3 Poles in Series, 70 °C 26 A | |
| (72 V) 1-Pole, 40 °C 30 A | |
| (72 V) 1-Pole, 60 °C 30 A | |
| (72 V) 1-Pole, 70 °C 26 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| Rated Operational Current DC-3 (Ie) | (110 V) 1-Pole, 40 °C 8 A |
| (110 V) 1-Pole, 60 °C 8 A | |
| (110 V) 1-Pole, 70 °C 8 A | |
| (110 V) 2 Poles in Series, 40 °C 30 A | |
| (110 V) 2 Poles in Series, 60 °C 30 A | |
| (110 V) 2 Poles in Series, 70 °C 26 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 8 A | |
| (220 V) 2 Poles in Series, 60 °C 8 A | |
| (220 V) 2 Poles in Series, 70 °C 8 A | |
| (220 V) 3 Poles in Series, 40 °C 30 A | |
| (220 V) 3 Poles in Series, 60 °C 30 A | |
| (220 V) 3 Poles in Series, 70 °C 26 A | |
| (72 V) 1-Pole, 40 °C 30 A | |
| (72 V) 1-Pole, 60 °C 30 A | |
| (72 V) 1-Pole, 70 °C 26 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| Rated Operational Current DC-5 (Ie) | (110 V) 1-Pole, 40 °C 4 A |
| (110 V) 1-Pole, 60 °C 4 A | |
| (110 V) 1-Pole, 70 °C 4 A | |
| (110 V) 2 Poles in Series, 40 °C 20 A | |
| (110 V) 2 Poles in Series, 60 °C 20 A | |
| (110 V) 2 Poles in Series, 70 °C 20 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 4 A | |
| (220 V) 2 Poles in Series, 60 °C 4 A | |
| (220 V) 2 Poles in Series, 70 °C 4 A | |
| (220 V) 3 Poles in Series, 40 °C 16 A | |
| (220 V) 3 Poles in Series, 60 °C 16 A | |
| (220 V) 3 Poles in Series, 70 °C 16 A | |
| (72 V) 1-Pole, 40 °C 16 A | |
| (72 V) 1-Pole, 60 °C 16 A | |
| (72 V) 1-Pole, 70 °C 16 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| (48 V) 2.8 A / 134 W | |
| (72 V) 1 A / 72 W | |
| (110 V) 0.55 A / 60 W | |
| (125 V) 0.55 A / 69 W | |
| (220 V) 0.27 A / 60 W | |
| (250 V) 0.27 A / 68 W | |
| (400 V) 0.15 A / 60 W | |
| (500 V) 0.13 A / 65 W | |
| (600 V) 0.1 A / 60 W | |
| Rated Operational Power AC-3 (Pe) | (415 V) 9 kW |
| (440 V) 9 kW | |
| (500 V) 9 kW | |
| (690 V) 9 kW | |
| (380 / 400 V) 7.5 kW | |
| (220 / 230 / 240 V) 4 kW | |
| Rated Operational Power AC-3e (Pe) | (415 V) 9 kW |
| (440 V) 9 kW | |
| (500 V) 9 kW | |
| (690 V) 9 kW | |
| (380 / 400 V) 7.5 kW | |
| (220 / 230 / 240 V) 4 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | |
| for 0.1 s 140 A | |
| for 1 s 100 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V |
| acc. to IEC 60947-5-1 690 V | |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| (AC-15) 1200 cycles per hour | |
| (AC-2 / AC-4) 300 cycles per hour | |
| (AC-3) 1200 cycles per hour | |
| (DC-13) 900 cycles per hour | |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 48 ... 130 V |
| 60 Hz 48 ... 130 V | |
| DC Operation 48 ... 130 V | |
| Power Loss | at 6 A per Pole 0.1 W |
| at Rated Operating Conditions AC-1 per Pole 1.2 W | |
| at Rated Operating Conditions AC-3 per Pole 0.35 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms |
| Between Coil De-energization and NO Contact Opening 11 ... 95 ms | |
| Between Coil Energization and NC Contact Opening 38 ... 90 ms | |
| Between Coil Energization and NO Contact Closing 40 ... 95 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP10 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 | |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 | |
| Tightening Torque | Auxiliary Circuit 1.2 N·m |
| Control Circuit 1.2 N·m | |
| Main Circuit 1.5 N·m | |
| Terminal Type | Ring-Tongue Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 30 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 1-1/2 hp |
| (200 ... 208 V AC) Three Phase 5 hp | |
| (220 ... 240 V AC) Three Phase 5 hp | |
| (240 V AC) Single Phase 3 hp | |
| (440 ... 480 V AC) Three Phase 10 hp | |
| (550 ... 600 V AC) Three Phase 15 hp | |
| Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb |
| Control Circuit 11 in·lb | |
| Main Circuit 13 in·lb | |
| Full Load Amps Motor Use | (120 V AC) Single Phase 20 A |
| (200 ... 208 V AC) Three Phase 17.5 A | |
| (220 ... 240 V AC) Three Phase 15.2 A | |
| (240 V AC) Single Phase 17 A | |
| (440 ... 480 V AC) Three Phase 14 A | |
| (550 ... 600 V AC) Three Phase 17 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C |
| Close to Contactor without Thermal O/L Relay -40 ... 70 °C | |
| Close to Contactor for Storage -60 ... +80 °C | |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Shock and Vibration Withstand acc. to IEC 61373 | Category 1, Class B |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | 6b74413b-8fe7-4d8a-a1a3-df27dac19830 China |
| Simplified SCIP | b7607b41-590c-4369-9f36-87d7b4a5d807 Norway |
| 365a165e-2572-443a-82ea-5e8d991de5cb Germany | |
| 9468f78d-d849-448d-bc88-ce54fbed39fd France | |
| 01a72172-18de-4afd-ae02-4b093d8ea990 Sweden | |
| 1ad41660-d2f1-480a-a422-def2a77041f5 Germany | |
| d7654c15-25c9-4a33-ae52-7a6ccc7c1763 Hungary | |
| ca57cb2e-4ff3-4215-91bc-32ec0d8b6fa6 Belgium | |
| 3740233e-8049-4668-be57-61a9594a8e84 Estonia | |
| 90c36c52-04cb-4a23-9b06-3e73d982c77a Greece | |
| b0249922-df2b-4051-824f-be362dd8401f Portugal | |
| 784dcefb-addd-4a25-afc9-62c763dbab59 Bulgaria | |
| 448447d8-e860-4071-886f-e475c09a5466 Sweden | |
| 726afc21-f9cc-490c-a0e2-546b17a38c7c France | |
| 4e31112f-b4fd-4abb-b4d2-55544bce26e4 Poland | |
| fcf3992a-d654-43f3-a2b8-d30bb14bd00e Germany | |
| 08e7cd80-a039-4294-84e6-5d5b0fe24944 Poland | |
| 660d5211-b01a-404c-b911-1c225b0db549 Netherlands | |
| 8cc5b41f-b3db-44d3-a6ba-30167f50a76c Croatia | |
| 2ea424ad-3eb6-4ba9-b9f1-e6524679d4d1 Germany | |
| bbb018bb-b6eb-42ff-8d58-9a52a0283277 Germany | |
| 91692ec2-e63a-4b0d-be0f-5939cd0a8f53 Denmark | |
| a8a11b1a-6502-4cb9-a20d-834d3a7c42c2 Belgium | |
| 8971bb43-c4f9-4469-a492-01ce98e50174 Hungary | |
| dba3de95-c5b1-4ff0-96ef-904bc1a10235 Finland | |
| 6c54b809-bd66-43f3-94b3-28c881ed87de Czech Republic | |
| 5ea479bf-9881-4230-97e8-68ac9f7d8aa1 Poland | |
| a54894fb-164f-42a5-9b45-6d08db50130f Spain | |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| End Of Life Disassembling Instructions | 1SBC101080M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E3000 |
| 2TFP200035A1001 | |
| Sustainable Material Content in Packaging (wt. %) | Recycled Cardboard - 86 % |
| Sustainable Material Content in Product (wt. %) | Recycled Metal - 28 % |
| Certificates and Declarations | |
| CB Certificate | CB_SE-113345 |
| CCC Certificate | CCC_2024010304656669 |
| CQC Certificate | CQC2010010304445624 |
| Declaration of Conformity - CCC | 2020980304001253 |
| Declaration of Conformity - CE | 1SBD250004U1000 |
| Declaration of Conformity - UKCA | 1SBD250035U1000 |
| UL Listing Card | UL_E312527 |
| UR Certificate | UL_20121122-E312527_9_5 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 87 mm |
| Package Level 1 Depth / Length | 79 mm |
| Package Level 1 Height | 47 mm |
| Package Level 1 Gross Weight | 0.32 kg |
| Package Level 1 EAN | 3471523128224 |
| Package Level 2 Units | box 27 piece |
| Package Level 2 Width | 250 mm |
| Package Level 2 Depth / Length | 300 mm |
| Package Level 2 Height | 315 mm |
| Package Level 2 Gross Weight | 17.28 kg |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE MOTOR PROTECTION EN.pdf | 240 Mbytes |
|
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.