Product successfully added to your shopping cart
1SBL176060R2101
ABB
1
AF16ZB-30-01RTCONT.TR.24-60VAC20-60VDC
AF16ZB-30-01RT-21 24-60V50/60HZ 20-60VDC Contactor
Low-voltage industrial components > Power contactor, AC switching
Contactors and overload relays > AF contactors to 38 A
Brand new product in its original packaging covered by the warranties and certifications provided by ABB
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SBC100220C0201 |
| Instructions and Manuals | 1SBC101035M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 77 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.32 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives. |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Main Circuit 690 V | |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Control Circuit 50 / 60 Hz | |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A |
| acc. to IEC 60947-5-1, Θ = 40 °C 16 A | |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 30 A |
| (690 V) 60 °C 30 A | |
| (690 V) 70 °C 26 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 18 A |
| (440 V) 60 °C 18 A | |
| (500 V) 60 °C 15 A | |
| (690 V) 60 °C 10.5 A | |
| (380 / 400 V) 60 °C 18 A | |
| (220 / 230 / 240 V) 60 °C 18 A | |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 18 A |
| (440 V) 60 °C 18 A | |
| (500 V) 60 °C 15 A | |
| (690 V) 60 °C 10.5 A | |
| (380 / 400 V) 60 °C 18 A | |
| (220 / 230 / 240 V) 60 °C 18 A | |
| Rated Operational Current AC-15 (Ie) | (500 V) 2 A |
| (690 V) 2 A | |
| (24 / 127 V) 6 A | |
| (220 / 240 V) 4 A | |
| (400 / 440 V) 3 A | |
| Rated Operational Current DC-1 (Ie) | (110 V) 1-Pole, 40 °C 20 A |
| (110 V) 1-Pole, 60 °C 20 A | |
| (110 V) 1-Pole, 70 °C 20 A | |
| (110 V) 2 Poles in Series, 40 °C 30 A | |
| (110 V) 2 Poles in Series, 60 °C 30 A | |
| (110 V) 2 Poles in Series, 70 °C 26 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 20 A | |
| (220 V) 2 Poles in Series, 60 °C 20 A | |
| (220 V) 2 Poles in Series, 70 °C 20 A | |
| (220 V) 3 Poles in Series, 40 °C 30 A | |
| (220 V) 3 Poles in Series, 60 °C 30 A | |
| (220 V) 3 Poles in Series, 70 °C 26 A | |
| (72 V) 1-Pole, 40 °C 30 A | |
| (72 V) 1-Pole, 60 °C 30 A | |
| (72 V) 1-Pole, 70 °C 26 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| Rated Operational Current DC-3 (Ie) | (110 V) 1-Pole, 40 °C 8 A |
| (110 V) 1-Pole, 60 °C 8 A | |
| (110 V) 1-Pole, 70 °C 8 A | |
| (110 V) 2 Poles in Series, 40 °C 30 A | |
| (110 V) 2 Poles in Series, 60 °C 30 A | |
| (110 V) 2 Poles in Series, 70 °C 26 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 8 A | |
| (220 V) 2 Poles in Series, 60 °C 8 A | |
| (220 V) 2 Poles in Series, 70 °C 8 A | |
| (220 V) 3 Poles in Series, 40 °C 30 A | |
| (220 V) 3 Poles in Series, 60 °C 30 A | |
| (220 V) 3 Poles in Series, 70 °C 26 A | |
| (72 V) 1-Pole, 40 °C 30 A | |
| (72 V) 1-Pole, 60 °C 30 A | |
| (72 V) 1-Pole, 70 °C 26 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| Rated Operational Current DC-5 (Ie) | (110 V) 1-Pole, 40 °C 4 A |
| (110 V) 1-Pole, 60 °C 4 A | |
| (110 V) 1-Pole, 70 °C 4 A | |
| (110 V) 2 Poles in Series, 40 °C 20 A | |
| (110 V) 2 Poles in Series, 60 °C 20 A | |
| (110 V) 2 Poles in Series, 70 °C 20 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 4 A | |
| (220 V) 2 Poles in Series, 60 °C 4 A | |
| (220 V) 2 Poles in Series, 70 °C 4 A | |
| (220 V) 3 Poles in Series, 40 °C 16 A | |
| (220 V) 3 Poles in Series, 60 °C 16 A | |
| (220 V) 3 Poles in Series, 70 °C 16 A | |
| (72 V) 1-Pole, 40 °C 16 A | |
| (72 V) 1-Pole, 60 °C 16 A | |
| (72 V) 1-Pole, 70 °C 16 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| (48 V) 2.8 A / 134 W | |
| (72 V) 1 A / 72 W | |
| (110 V) 0.55 A / 60 W | |
| (125 V) 0.55 A / 69 W | |
| (220 V) 0.27 A / 60 W | |
| (250 V) 0.27 A / 68 W | |
| (400 V) 0.15 A / 60 W | |
| (500 V) 0.13 A / 65 W | |
| (600 V) 0.1 A / 60 W | |
| Rated Operational Power AC-3 (Pe) | (415 V) 9 kW |
| (440 V) 9 kW | |
| (500 V) 9 kW | |
| (690 V) 9 kW | |
| (380 / 400 V) 7.5 kW | |
| (220 / 230 / 240 V) 4 kW | |
| Rated Operational Power AC-3e (Pe) | (415 V) 9 kW |
| (440 V) 9 kW | |
| (500 V) 9 kW | |
| (690 V) 9 kW | |
| (380 / 400 V) 7.5 kW | |
| (220 / 230 / 240 V) 4 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | |
| for 0.1 s 140 A | |
| for 1 s 100 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V |
| acc. to IEC 60947-5-1 690 V | |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| (AC-15) 1200 cycles per hour | |
| (AC-2 / AC-4) 300 cycles per hour | |
| (AC-3) 1200 cycles per hour | |
| (DC-13) 900 cycles per hour | |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 24 ... 60 V |
| 60 Hz 24 ... 60 V | |
| DC Operation 20 ... 60 V | |
| Power Loss | at 6 A per Pole 0.1 W |
| at Rated Operating Conditions AC-1 per Pole 1.2 W | |
| at Rated Operating Conditions AC-3 per Pole 0.35 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms |
| Between Coil De-energization and NO Contact Opening 11 ... 95 ms | |
| Between Coil Energization and NC Contact Opening 38 ... 90 ms | |
| Between Coil Energization and NO Contact Closing 40 ... 95 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP10 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 | |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 | |
| Tightening Torque | Auxiliary Circuit 1.2 N·m |
| Control Circuit 1.2 N·m | |
| Main Circuit 1.5 N·m | |
| Terminal Type | Ring-Tongue Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 30 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 1-1/2 hp |
| (200 ... 208 V AC) Three Phase 5 hp | |
| (220 ... 240 V AC) Three Phase 5 hp | |
| (240 V AC) Single Phase 3 hp | |
| (440 ... 480 V AC) Three Phase 10 hp | |
| (550 ... 600 V AC) Three Phase 15 hp | |
| Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb |
| Control Circuit 11 in·lb | |
| Main Circuit 13 in·lb | |
| Full Load Amps Motor Use | (120 V AC) Single Phase 20 A |
| (200 ... 208 V AC) Three Phase 17.5 A | |
| (220 ... 240 V AC) Three Phase 15.2 A | |
| (240 V AC) Single Phase 17 A | |
| (440 ... 480 V AC) Three Phase 14 A | |
| (550 ... 600 V AC) Three Phase 17 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C |
| Close to Contactor without Thermal O/L Relay -40 ... 70 °C | |
| Close to Contactor for Storage -60 ... +80 °C | |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Shock and Vibration Withstand acc. to IEC 61373 | Category 1, Class B |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | c797b628-c03d-46d3-a03f-064dd9d3b87a China |
| Simplified SCIP | 67c4332d-a4f3-442b-81e9-ec483de891c1 Hungary |
| b2d25bc0-49fc-4932-ab7c-f646bd4a1ef0 Belgium | |
| c9db7cc9-de68-4955-8491-ed367a07b79e Greece | |
| 2756ca59-6791-42ce-982a-0c29e07233a2 Estonia | |
| c3719952-4541-4f15-93cb-24e4afe0d4b1 Poland | |
| ffbb7f61-4828-4323-ac8c-6b817716c125 Netherlands | |
| 654270b8-d9aa-475a-a92b-7a81f63d735d Croatia | |
| 5d3ea4f0-880b-4b32-b24b-20bc68f800f1 Germany | |
| 965dadd4-b4d6-48af-8e25-f569b14302f3 Denmark | |
| 10c4073e-5b7e-4c1a-b318-c67d588e4a79 Germany | |
| dc1da448-7c6d-4f00-974a-bbaad0186238 Hungary | |
| 91f878d0-02b8-4ba3-a0b1-12858b0ad9b1 Belgium | |
| 2aed67e5-4574-4169-9a54-7f92e816b1d7 France | |
| 6321facc-c67f-4cef-a8c7-3942c12bb8d6 Germany | |
| 1e7646c9-ffef-41af-8d94-d06f339023da Sweden | |
| fae2b6e4-0d67-486a-b9d7-d837c834bf7e Germany | |
| 2ab2a1ce-7ea5-45b3-8c58-3f16d0bd6eaa Portugal | |
| e28147a6-88d0-4a9c-8268-41605e078c5d Bulgaria | |
| 28ad1c38-588e-4fc2-8223-3a26c2b7fb40 Sweden | |
| 1386518d-8cf8-47fc-bc0e-9b7d723d7b7b Poland | |
| 5b81d0e2-b2ad-4e8c-83d0-cf6758fa0208 France | |
| 9733fd79-e9a9-4f7c-9536-5054d05cee55 Germany | |
| 1858a942-703e-4f7b-a5f3-c7fd9c1068e4 Norway | |
| dc87921f-42cb-434f-8162-4df064009cfb Spain | |
| 0ea4d62a-fd9a-4a60-8c70-aa0e19b4ab78 Poland | |
| b7643e28-3aec-4450-a3b1-f4aee71eaaee Czech Republic | |
| e7698bf2-796d-4130-8019-708a9e2d27c3 Finland | |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| End Of Life Disassembling Instructions | 1SBC101080M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E3000 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 92.7 % |
| Certificates and Declarations | |
| CB Certificate | CB_SE-113345 |
| CCC Certificate | CCC_2024010304656669 |
| CQC Certificate | CQC2010010304445624 |
| Declaration of Conformity - CCC | 2020980304001253 |
| Declaration of Conformity - CE | 1SBD250004U1000 |
| Declaration of Conformity - UKCA | 1SBD250035U1000 |
| UL Listing Card | UL_E312527 |
| UR Certificate | UL_20121122-E312527_9_5 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 87 mm |
| Package Level 1 Depth / Length | 79 mm |
| Package Level 1 Height | 47 mm |
| Package Level 1 Gross Weight | 0.32 kg |
| Package Level 1 EAN | 3471523128316 |
| Package Level 2 Units | box 27 piece |
| Package Level 2 Width | 250 mm |
| Package Level 2 Depth / Length | 300 mm |
| Package Level 2 Height | 315 mm |
| Package Level 2 Gross Weight | 17.28 kg |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE MOTOR PROTECTION EN.pdf | 240 Mbytes |
|
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.