Product successfully added to your shopping cart
1SBL177201R1200
ABB
1
Low-voltage industrial components > Power contactor, AC switching
Contactors and overload relays > AF contactors to 38 A
Brand new product in its original packaging covered by the warranties and certifications provided by ABB
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| EPLAN Data | 9AAC159647_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Instructions and Manuals | 1SBC101027M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 77 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.27 kg |
| Technical | |
| Number of Main Contacts NO | 4 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CAN/CSA C22.2 No.60947-1, CAN/CSA C22.2 No.60947-4-1 |
| Rated Operational Voltage | Main Circuit 690 V |
| Rated Frequency (f) | Control Circuit 50 / 60 Hz |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 30 A |
| (690 V) 60 °C 30 A | |
| (690 V) 70 °C 26 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 18 A |
| (440 V) 60 °C 18 A | |
| (500 V) 60 °C 15 A | |
| (690 V) 60 °C 10.5 A | |
| (380 / 400 V) 60 °C 18 A | |
| (220 / 230 / 240 V) 60 °C 18 A | |
| Rated Operational Current DC-1 (Ie) | (110 V) 1-Pole, 40 °C 20 A |
| (110 V) 1-Pole, 60 °C 20 A | |
| (110 V) 1-Pole, 70 °C 20 A | |
| (110 V) 2 Poles in Series, 40 °C 30 A | |
| (110 V) 2 Poles in Series, 60 °C 30 A | |
| (110 V) 2 Poles in Series, 70 °C 26 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (110 V) 4 Poles in Series, 40 °C 30 A | |
| (110 V) 4 Poles in Series, 60 °C 30 A | |
| (110 V) 4 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 20 A | |
| (220 V) 2 Poles in Series, 60 °C 20 A | |
| (220 V) 2 Poles in Series, 70 °C 20 A | |
| (220 V) 3 Poles in Series, 40 °C 30 A | |
| (220 V) 3 Poles in Series, 60 °C 30 A | |
| (220 V) 3 Poles in Series, 70 °C 26 A | |
| (220 V) 4 Poles in Series, 40 °C 30 A | |
| (220 V) 4 Poles in Series, 60 °C 30 A | |
| (220 V) 4 Poles in Series, 70 °C 26 A | |
| (440 V) 4 Poles in Series, 40 °C 20 A | |
| (440 V) 4 Poles in Series, 60 °C 20 A | |
| (440 V) 4 Poles in Series, 70 °C 20 A | |
| (72 V) 1-Pole, 40 °C 30 A | |
| (72 V) 1-Pole, 60 °C 30 A | |
| (72 V) 1-Pole, 70 °C 26 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| (72 V) 4 Poles in Series, 40 °C 30 A | |
| (72 V) 4 Poles in Series, 60 °C 30 A | |
| (72 V) 4 Poles in Series, 70 °C 26 A | |
| Rated Operational Current DC-3 (Ie) | (110 V) 1-Pole, 40 °C 8 A |
| (110 V) 1-Pole, 60 °C 8 A | |
| (110 V) 1-Pole, 70 °C 8 A | |
| (110 V) 2 Poles in Series, 40 °C 30 A | |
| (110 V) 2 Poles in Series, 60 °C 30 A | |
| (110 V) 2 Poles in Series, 70 °C 26 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (110 V) 4 Poles in Series, 40 °C 30 A | |
| (110 V) 4 Poles in Series, 60 °C 30 A | |
| (110 V) 4 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 8 A | |
| (220 V) 2 Poles in Series, 60 °C 8 A | |
| (220 V) 2 Poles in Series, 70 °C 8 A | |
| (220 V) 3 Poles in Series, 40 °C 30 A | |
| (220 V) 3 Poles in Series, 60 °C 30 A | |
| (220 V) 3 Poles in Series, 70 °C 26 A | |
| (220 V) 4 Poles in Series, 40 °C 30 A | |
| (220 V) 4 Poles in Series, 60 °C 30 A | |
| (220 V) 4 Poles in Series, 70 °C 26 A | |
| (440 V) 4 Poles in Series, 40 °C 8 A | |
| (440 V) 4 Poles in Series, 60 °C 8 A | |
| (440 V) 4 Poles in Series, 70 °C 8 A | |
| (72 V) 1-Pole, 40 °C 30 A | |
| (72 V) 1-Pole, 60 °C 30 A | |
| (72 V) 1-Pole, 70 °C 26 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| (72 V) 4 Poles in Series, 40 °C 30 A | |
| (72 V) 4 Poles in Series, 60 °C 30 A | |
| (72 V) 4 Poles in Series, 70 °C 26 A | |
| Rated Operational Current DC-5 (Ie) | (110 V) 1-Pole, 40 °C 4 A |
| (110 V) 1-Pole, 60 °C 4 A | |
| (110 V) 1-Pole, 70 °C 4 A | |
| (110 V) 2 Poles in Series, 40 °C 20 A | |
| (110 V) 2 Poles in Series, 60 °C 20 A | |
| (110 V) 2 Poles in Series, 70 °C 20 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (110 V) 4 Poles in Series, 40 °C 30 A | |
| (110 V) 4 Poles in Series, 60 °C 30 A | |
| (110 V) 4 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 4 A | |
| (220 V) 2 Poles in Series, 60 °C 4 A | |
| (220 V) 2 Poles in Series, 70 °C 4 A | |
| (220 V) 3 Poles in Series, 40 °C 16 A | |
| (220 V) 3 Poles in Series, 60 °C 16 A | |
| (220 V) 3 Poles in Series, 70 °C 16 A | |
| (220 V) 4 Poles in Series, 40 °C 20 A | |
| (220 V) 4 Poles in Series, 60 °C 20 A | |
| (220 V) 4 Poles in Series, 70 °C 20 A | |
| (440 V) 4 Poles in Series, 40 °C 4 A | |
| (440 V) 4 Poles in Series, 60 °C 4 A | |
| (440 V) 4 Poles in Series, 70 °C 4 A | |
| (72 V) 1-Pole, 40 °C 16 A | |
| (72 V) 1-Pole, 60 °C 16 A | |
| (72 V) 1-Pole, 70 °C 16 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| (72 V) 4 Poles in Series, 40 °C 30 A | |
| (72 V) 4 Poles in Series, 60 °C 30 A | |
| (72 V) 4 Poles in Series, 70 °C 26 A | |
| Rated Operational Power AC-3 (Pe) | (400 V) 7.5 kW |
| (415 V) 9 kW | |
| (440 V) 9 kW | |
| (500 V) 9 kW | |
| (690 V) 9 kW | |
| (380 / 400 V) 7.5 kW | |
| (220 / 230 / 240 V) 4 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 48 ... 130 V |
| 60 Hz 48 ... 130 V | |
| DC Operation 48 ... 130 V | |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 1.2 W |
| at Rated Operating Conditions AC-3 per Pole 0.35 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms |
| Between Coil De-energization and NO Contact Opening 11 ... 95 ms | |
| Between Coil Energization and NC Contact Opening 38 ... 90 ms | |
| Between Coil Energization and NO Contact Closing 40 ... 95 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 6 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 4 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | |
| Rigid Solid 1/2x 1 ... 4 mm² | |
| Rigid Stranded 1/2x 1 ... 6 mm² | |
| Connecting Capacity Auxiliary Circuit | Rigid Solid 1/2x 1 ... 2.5 mm² |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Wire Stripping Length | Control Circuit 10 mm |
| Main Circuit 10 mm | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 | |
| Tightening Torque | Control Circuit 1.2 N·m |
| Main Circuit 1.5 N·m | |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 30 A |
| Connecting Capacity Main Circuit UL/CSA | Rigid Solid 1/2x 16-10 AWG |
| Rigid Stranded 1/2x 16-10 AWG | |
| Connecting Capacity Auxiliary Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Connecting Capacity Control Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Tightening Torque UL/CSA | Control Circuit 11 in·lb |
| Main Circuit 13 in·lb | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C |
| Near Contactor for Operation in Free Air -40 ... 70 °C | |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: B1 25 g |
| Open, Shock Direction: B1 5 g | |
| Shock Direction: A 30 g | |
| Shock Direction: B2 15 g | |
| Shock Direction: C1 25 g | |
| Shock Direction: C2 25 g | |
| Resistance to Vibrations | 4g Closed Position & 2g Open position 5 ... 300 Hz |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | 672cff06-e791-4721-9934-51f532576f43 China |
| Simplified SCIP | 1baf2009-edd4-4033-bea9-2c10fcdf268b Finland |
| fe57b341-c308-401a-aed4-a77bc817b1c6 Spain | |
| 4e391b0c-e5e0-446b-96ef-85949789f403 Poland | |
| d9c9f455-b359-407a-b5e0-dea767eb261b Greece | |
| 365f234e-abee-495b-89e8-967dca55a993 Estonia | |
| 25ed118d-7357-4b75-aa7f-8c6af220e760 Hungary | |
| 61fb25c5-a164-4b93-8c66-d6313849a10b Netherlands | |
| 0057c86f-a520-485a-b3fe-e33146be0787 Germany | |
| 50d5ccfd-3de0-4361-bcb8-77daa864be6d Germany | |
| b4bfa5dd-4713-4ee2-916a-7b932d38cc0c Denmark | |
| faa4e509-e3b7-476c-b112-b66c6d4efde1 Croatia | |
| e1a48cce-e286-4cc4-a732-d8af260cc9fb France | |
| 44249b97-dc22-4961-99ba-f296184c3380 Germany | |
| 75068f9a-b9cd-4958-8867-39327c5b9654 Hungary | |
| 0e5aebb0-ca9e-4931-abe7-e98750fe42fb Belgium | |
| 1777e366-2a6e-430b-a94f-586897120bb0 Poland | |
| 402622b6-cdbe-44c1-89ba-a6cc890fc4d4 Portugal | |
| 1492ca64-49fa-43a8-a465-9a88379addf3 Bulgaria | |
| f6d6015e-b330-402f-9942-569d4cffdd04 Sweden | |
| 08b0df27-95ea-4dea-aa46-395e716253af Sweden | |
| f4bc0ba9-72c2-489d-82eb-ee3e7e0823be Germany | |
| ef66ffb8-2632-4e2f-ab9c-2ac38ba33650 France | |
| 1c6b3fc2-09cd-4fc7-9e65-02ac79738807 Czech Republic | |
| 03ff4c92-3c9e-4b75-8769-e2d29daf85ad Poland | |
| c083a242-56cf-4322-9757-3b09de0879b1 Germany | |
| 3ef1c4da-9454-49c5-99de-9b1600ae0edd Norway | |
| 3047868f-4224-41d7-bdd2-815d48a9b9f3 Belgium | |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| End Of Life Disassembling Instructions | 1SBC101080M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E3000 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 92.7 % |
| Certificates and Declarations | |
| A2L Certificate – UL | 9AKK108469A4875 |
| 9AKK108469A4879 | |
| ABS Certificate | ABS_20-2060694-PDA |
| BV Certificate | BV_2634H24898C0 |
| CB Certificate | CB_SE-113345 |
| CCC Certificate | CCC_2024010304656669 |
| CQC Certificate | CQC2010010304445624 |
| CQC2020010304298240 | |
| Declaration of Conformity - CCC | 2020980304001253 |
| 2020980304001082 | |
| Declaration of Conformity - CE | 1SBD250001U1000 |
| Declaration of Conformity - UKCA | 1SBD250032U1000 |
| DNV Certificate | DNV_TAE00001AF-4 |
| GOST Certificate | GOST_POCCFR.ME77.B07175.pdf |
| KC Certificate | KC_HW02016-15008C |
| LR Certificate | LRS_LR23403517TA-02 |
| RINA Certificate | RINA_ELE142224XG |
| RMRS Certificate | RMRS_1802705280 |
| UL Certificate | UL-US-L319322-13-72119002-5 |
| UL-CA-L319322-43-72119002-6 | |
| UL Listing Card | UL_E319322 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 87 mm |
| Package Level 1 Depth / Length | 79 mm |
| Package Level 1 Height | 47 mm |
| Package Level 1 Gross Weight | 0.27 kg |
| Package Level 1 EAN | 3471523115125 |
| Package Level 2 Units | box 27 piece |
| Package Level 2 Width | 250 mm |
| Package Level 2 Depth / Length | 300 mm |
| Package Level 2 Height | 315 mm |
| Package Level 2 Gross Weight | 14.58 kg |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
| E-Number (Finland) | 3706336 |
| E-Number (Sweden) | 3211397 |
| Feature Name | Feature Value |
|---|---|
| Rated control supply voltage AC 50 Hz (EF003978) | 48 V |
| Rated control supply voltage AC 60 Hz (EF003979) | 48 V |
| Rated control supply voltage DC (EF003980) | 48 V |
| Voltage type for actuating (EF008242) | AC/DC |
| Rated operation current Ie at AC-1, 400 V (EF001393) | 30 A |
| Rated operation current Ie at AC-3, 400 V (EF001392) | 18 A |
| Rated operation power at AC-3, 400 V (EF001364) | 7.5 kW |
| Modular version (EF001126) | No |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| Number of normally closed contacts as main contact (EF001375) | 0 |
| Number of normally open contacts as main contact (EF001374) | 4 |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE MOTOR PROTECTION EN.pdf | 240 Mbytes |
|
| AF16-40-00-12 48-130V50/60HZ-DC Contactor - ABB - AF16-40-00-12 - 1SBL177201R1200 | 100 Kbytes |
![]() |
| AF16-40-00-12 1SBL177201R1200 ABB AF16-40-00-12 48-130V50/60HZ-DC Contactor | 80 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.