| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SBC100220C0201 |
| Instructions and Manuals | 1SBC101027M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 77 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.31 kg |
| Technical | |
| Number of Main Contacts NO | 4 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives. |
| Rated Operational Voltage | Main Circuit 690 V |
| Rated Frequency (f) | Control Circuit 50 / 60 Hz |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 25 A |
| (690 V) 60 °C 25 A | |
| (690 V) 70 °C 22 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 9 A |
| (440 V) 60 °C 9 A | |
| (500 V) 60 °C 9.5 A | |
| (690 V) 60 °C 7 A | |
| (380 / 400 V) 60 °C 9 A | |
| (220 / 230 / 240 V) 60 °C 9 A | |
| Rated Operational Current DC-1 (Ie) | (110 V) 1-Pole, 40 °C 10 A |
| (110 V) 1-Pole, 60 °C 10 A | |
| (110 V) 1-Pole, 70 °C 10 A | |
| (110 V) 2 Poles in Series, 40 °C 25 A | |
| (110 V) 2 Poles in Series, 60 °C 25 A | |
| (110 V) 2 Poles in Series, 70 °C 22 A | |
| (110 V) 3 Poles in Series, 40 °C 25 A | |
| (110 V) 3 Poles in Series, 60 °C 25 A | |
| (110 V) 3 Poles in Series, 70 °C 22 A | |
| (110 V) 4 Poles in Series, 40 °C 25 A | |
| (110 V) 4 Poles in Series, 60 °C 25 A | |
| (110 V) 4 Poles in Series, 70 °C 22 A | |
| (220 V) 2 Poles in Series, 40 °C 10 A | |
| (220 V) 2 Poles in Series, 60 °C 10 A | |
| (220 V) 2 Poles in Series, 70 °C 10 A | |
| (220 V) 3 Poles in Series, 40 °C 25 A | |
| (220 V) 3 Poles in Series, 60 °C 25 A | |
| (220 V) 3 Poles in Series, 70 °C 22 A | |
| (220 V) 4 Poles in Series, 40 °C 25 A | |
| (220 V) 4 Poles in Series, 60 °C 25 A | |
| (220 V) 4 Poles in Series, 70 °C 22 A | |
| (440 V) 4 Poles in Series, 40 °C 10 A | |
| (440 V) 4 Poles in Series, 60 °C 10 A | |
| (440 V) 4 Poles in Series, 70 °C 10 A | |
| (72 V) 1-Pole, 40 °C 25 A | |
| (72 V) 1-Pole, 60 °C 25 A | |
| (72 V) 1-Pole, 70 °C 22 A | |
| (72 V) 2 Poles in Series, 40 °C 25 A | |
| (72 V) 2 Poles in Series, 60 °C 25 A | |
| (72 V) 2 Poles in Series, 70 °C 22 A | |
| (72 V) 3 Poles in Series, 40 °C 25 A | |
| (72 V) 3 Poles in Series, 60 °C 25 A | |
| (72 V) 3 Poles in Series, 70 °C 22 A | |
| (72 V) 4 Poles in Series, 40 °C 25 A | |
| (72 V) 4 Poles in Series, 60 °C 25 A | |
| (72 V) 4 Poles in Series, 70 °C 22 A | |
| Rated Operational Current DC-3 (Ie) | (110 V) 1-Pole, 40 °C 6 A |
| (110 V) 1-Pole, 60 °C 6 A | |
| (110 V) 1-Pole, 70 °C 6 A | |
| (110 V) 2 Poles in Series, 40 °C 25 A | |
| (110 V) 2 Poles in Series, 60 °C 25 A | |
| (110 V) 2 Poles in Series, 70 °C 22 A | |
| (110 V) 3 Poles in Series, 40 °C 25 A | |
| (110 V) 3 Poles in Series, 60 °C 25 A | |
| (110 V) 3 Poles in Series, 70 °C 22 A | |
| (110 V) 4 Poles in Series, 40 °C 25 A | |
| (110 V) 4 Poles in Series, 60 °C 25 A | |
| (110 V) 4 Poles in Series, 70 °C 22 A | |
| (220 V) 2 Poles in Series, 40 °C 6 A | |
| (220 V) 2 Poles in Series, 60 °C 6 A | |
| (220 V) 2 Poles in Series, 70 °C 6 A | |
| (220 V) 3 Poles in Series, 40 °C 25 A | |
| (220 V) 3 Poles in Series, 60 °C 25 A | |
| (220 V) 3 Poles in Series, 70 °C 22 A | |
| (220 V) 4 Poles in Series, 40 °C 25 A | |
| (220 V) 4 Poles in Series, 60 °C 25 A | |
| (220 V) 4 Poles in Series, 70 °C 22 A | |
| (440 V) 4 Poles in Series, 40 °C 6 A | |
| (440 V) 4 Poles in Series, 60 °C 6 A | |
| (440 V) 4 Poles in Series, 70 °C 6 A | |
| (72 V) 1-Pole, 40 °C 25 A | |
| (72 V) 1-Pole, 60 °C 25 A | |
| (72 V) 1-Pole, 70 °C 22 A | |
| (72 V) 2 Poles in Series, 40 °C 25 A | |
| (72 V) 2 Poles in Series, 60 °C 25 A | |
| (72 V) 2 Poles in Series, 70 °C 22 A | |
| (72 V) 3 Poles in Series, 40 °C 25 A | |
| (72 V) 3 Poles in Series, 60 °C 25 A | |
| (72 V) 3 Poles in Series, 70 °C 22 A | |
| (72 V) 4 Poles in Series, 40 °C 25 A | |
| (72 V) 4 Poles in Series, 60 °C 25 A | |
| (72 V) 4 Poles in Series, 70 °C 22 A | |
| Rated Operational Current DC-5 (Ie) | (110 V) 1-Pole, 40 °C 4 A |
| (110 V) 1-Pole, 60 °C 4 A | |
| (110 V) 1-Pole, 70 °C 4 A | |
| (110 V) 2 Poles in Series, 40 °C 10 A | |
| (110 V) 2 Poles in Series, 60 °C 10 A | |
| (110 V) 2 Poles in Series, 70 °C 10 A | |
| (110 V) 3 Poles in Series, 40 °C 25 A | |
| (110 V) 3 Poles in Series, 60 °C 25 A | |
| (110 V) 3 Poles in Series, 70 °C 22 A | |
| (110 V) 4 Poles in Series, 40 °C 25 A | |
| (110 V) 4 Poles in Series, 60 °C 25 A | |
| (110 V) 4 Poles in Series, 70 °C 22 A | |
| (220 V) 2 Poles in Series, 40 °C 4 A | |
| (220 V) 2 Poles in Series, 60 °C 4 A | |
| (220 V) 2 Poles in Series, 70 °C 4 A | |
| (220 V) 3 Poles in Series, 40 °C 9 A | |
| (220 V) 3 Poles in Series, 60 °C 9 A | |
| (220 V) 3 Poles in Series, 70 °C 9 A | |
| (220 V) 4 Poles in Series, 40 °C 10 A | |
| (220 V) 4 Poles in Series, 60 °C 10 A | |
| (220 V) 4 Poles in Series, 70 °C 10 A | |
| (440 V) 4 Poles in Series, 40 °C 4 A | |
| (440 V) 4 Poles in Series, 60 °C 4 A | |
| (440 V) 4 Poles in Series, 70 °C 4 A | |
| (72 V) 1-Pole, 40 °C 9 A | |
| (72 V) 1-Pole, 60 °C 9 A | |
| (72 V) 1-Pole, 70 °C 9 A | |
| (72 V) 2 Poles in Series, 40 °C 25 A | |
| (72 V) 2 Poles in Series, 60 °C 25 A | |
| (72 V) 2 Poles in Series, 70 °C 22 A | |
| (72 V) 3 Poles in Series, 40 °C 25 A | |
| (72 V) 3 Poles in Series, 60 °C 25 A | |
| (72 V) 3 Poles in Series, 70 °C 22 A | |
| (72 V) 4 Poles in Series, 40 °C 25 A | |
| (72 V) 4 Poles in Series, 60 °C 25 A | |
| (72 V) 4 Poles in Series, 70 °C 22 A | |
| Rated Operational Power AC-3 (Pe) | (400 V) 4 kW |
| (415 V) 4 kW | |
| (440 V) 4 kW | |
| (500 V) 5.5 kW | |
| (690 V) 5.5 kW | |
| (380 / 400 V) 4 kW | |
| (220 / 230 / 240 V) 2.2 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 48 ... 130 V |
| 60 Hz 48 ... 130 V | |
| DC Operation 48 ... 130 V | |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 0.8 W |
| at Rated Operating Conditions AC-3 per Pole 0.1 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms |
| Between Coil De-energization and NO Contact Opening 11 ... 95 ms | |
| Between Coil Energization and NC Contact Opening 38 ... 90 ms | |
| Between Coil Energization and NO Contact Closing 40 ... 95 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 6 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 4 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | |
| Rigid Solid 1/2x 1 ... 4 mm² | |
| Rigid Stranded 1/2x 1 ... 6 mm² | |
| Connecting Capacity Auxiliary Circuit | Rigid Solid 1/2x 1 ... 2.5 mm² |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Wire Stripping Length | Control Circuit 10 mm |
| Main Circuit 10 mm | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 | |
| Tightening Torque | Control Circuit 1.2 N·m |
| Main Circuit 1.5 N·m | |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 25 A |
| Connecting Capacity Main Circuit UL/CSA | Rigid Solid 1/2x 16-10 AWG |
| Rigid Stranded 1/2x 16-10 AWG | |
| Connecting Capacity Auxiliary Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Connecting Capacity Control Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Tightening Torque UL/CSA | Control Circuit 11 in·lb |
| Main Circuit 13 in·lb | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C |
| Near Contactor for Operation in Free Air -40 ... 70 °C | |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Shock and Vibration Withstand acc. to IEC 61373 | Category 1, Class B |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | c36e80bb-553c-476f-88e2-a23965abcddc China |
| Simplified SCIP | 608a0822-53b1-4d49-b5c6-102395629976 Poland |
| b8af45fe-5f6d-4684-a5c0-9e1388956f83 Czech Republic | |
| 45801744-d7ac-4ac8-90a1-3d86e51b04c8 Sweden | |
| c65f772b-6b10-4f4f-9d69-094acbf42720 Germany | |
| f38d6315-4720-4bbe-83ba-ed85320d1b37 Norway | |
| d8c850d9-618b-4793-89d9-548187bb7496 Belgium | |
| 5835657a-7656-4813-b514-29a4d41be6f3 Finland | |
| 0a63e959-4c21-4821-8c50-4b1cd1b6301b Denmark | |
| 628d6717-69b3-4ef0-8d3d-336baba8341e Germany | |
| ff8e50db-8ad8-4962-bd9d-d35eb82862a7 Germany | |
| a80e8b94-f91b-4cba-8756-e5334fcbeaaf Croatia | |
| cffd360e-0af1-4a18-b3dc-581ed93d5028 Greece | |
| da762866-25e1-4804-85fa-6ed043e1eaf8 Estonia | |
| c954e4d1-7403-43b4-a8d6-f4042b224e35 Hungary | |
| 373b62f1-185e-4c11-88d6-45218b06a919 Netherlands | |
| 7c93fa55-04b2-4095-97f6-91115a221ca5 Poland | |
| 06b9e1d3-94b5-419a-bfaf-c24130755c93 Spain | |
| 5b80ebab-3ca4-4b38-bdbd-1b198984087e Belgium | |
| 21beabb6-ec81-4922-835b-300691fb3a67 Hungary | |
| cf0af572-e006-4047-987c-b50d52fb1119 France | |
| 5be04ab9-70bf-47f2-8a10-00d1ac1c06d9 Germany | |
| bfabc05c-6223-40e1-b604-39fa5f0b3d7d Poland | |
| d1758f79-830c-4c03-8365-9eebf9940984 Bulgaria | |
| dffe877b-ce89-4a0b-9cb6-fd9eb53cc764 Portugal | |
| 7d7b9a82-a476-41f1-8137-813604b17ef6 France | |
| 2565b5c8-e1c6-44d1-8540-b3c476032686 Germany | |
| 11f09a80-dc3c-473a-9edd-b8adf6b78fdf Sweden | |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| End Of Life Disassembling Instructions | 1SBC101080M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E3000 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 92.7 % |
| Certificates and Declarations | |
| A2L Certificate – UL | 9AKK108469A4875 |
| 9AKK108469A4879 | |
| CB Certificate | CB_SE-113345 |
| CCC Certificate | CCC_2024010304656669 |
| CQC Certificate | CQC2010010304445624 |
| Declaration of Conformity - CCC | 2020980304001253 |
| Declaration of Conformity - CE | 1SBD250002U1000 |
| Declaration of Conformity - UKCA | 1SBD250033U1000 |
| GOST Certificate | GOST_POCCFR.ME77.B07175.pdf |
| KC Certificate | KC_HW02016-15007C |
| UL Certificate | UL-US-L319322-13-72119002-5 |
| UL-CA-L319322-43-72119002-6 | |
| UL Listing Card | UL_E319322 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 87 mm |
| Package Level 1 Depth / Length | 79 mm |
| Package Level 1 Height | 47 mm |
| Package Level 1 Gross Weight | 0.31 kg |
| Package Level 1 EAN | 3471523124424 |
| Package Level 2 Units | box 27 piece |
| Package Level 2 Width | 250 mm |
| Package Level 2 Depth / Length | 300 mm |
| Package Level 2 Height | 315 mm |
| Package Level 2 Gross Weight | 16.74 kg |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE MOTOR PROTECTION EN.pdf | 240 Mbytes |
|
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.