1SBL136060R2201 ABB AF09ZB-30-01RTCONT.TRAC.B.48-130VAC-DC View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

1SBL136060R2201 ABB AF09ZB-30-01RTCONT.TRAC.B.48-130VAC-DC

1SBL136060R2201

ABB

AF09ZB-30-01RTCONT.TRAC.B.48-130VAC-DC

AF09ZB-30-01RT-22 48-130V50/60HZ-DC Contactor

More details


Low-voltage industrial components > Power contactor, AC switching

Contactors and overload relays > AF contactors to 38 A

Brand new product in its original packaging covered by the warranties and certifications provided by ABB

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Ordering
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
Data Sheet, Technical Information1SBC100220C0201
Instructions and Manuals1SBC101035M6801
Instructions and Manuals (Part 2)1SAC200017M0002
CAD Dimensional Drawing2CDC001079B0201
Dimensions
Product Net Width45 mm
Product Net Depth / Length77 mm
Product Net Height86 mm
Product Net Weight0.32 kg
Technical
Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC1
Number of Poles3P
StandardsIEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational VoltageAuxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A
acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 25 A
(690 V) 60 °C 25 A
(690 V) 70 °C 22 A
Rated Operational Current AC-3 (Ie)(415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
(380 / 400 V) 60 °C 9 A
(220 / 230 / 240 V) 60 °C 9 A
Rated Operational Current AC-3e (Ie)(415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
(380 / 400 V) 60 °C 9 A
(220 / 230 / 240 V) 60 °C 9 A
Rated Operational Current AC-15 (Ie)(500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)(110 V) 1-Pole, 40 °C 10 A
(110 V) 1-Pole, 60 °C 10 A
(110 V) 1-Pole, 70 °C 10 A
(110 V) 2 Poles in Series, 40 °C 25 A
(110 V) 2 Poles in Series, 60 °C 25 A
(110 V) 2 Poles in Series, 70 °C 22 A
(110 V) 3 Poles in Series, 40 °C 25 A
(110 V) 3 Poles in Series, 60 °C 25 A
(110 V) 3 Poles in Series, 70 °C 22 A
(220 V) 2 Poles in Series, 40 °C 10 A
(220 V) 2 Poles in Series, 60 °C 10 A
(220 V) 2 Poles in Series, 70 °C 10 A
(220 V) 3 Poles in Series, 40 °C 25 A
(220 V) 3 Poles in Series, 60 °C 25 A
(220 V) 3 Poles in Series, 70 °C 22 A
(72 V) 1-Pole, 40 °C 25 A
(72 V) 1-Pole, 60 °C 25 A
(72 V) 1-Pole, 70 °C 22 A
(72 V) 2 Poles in Series, 40 °C 25 A
(72 V) 2 Poles in Series, 60 °C 25 A
(72 V) 2 Poles in Series, 70 °C 22 A
(72 V) 3 Poles in Series, 40 °C 25 A
(72 V) 3 Poles in Series, 60 °C 25 A
(72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-3 (Ie)(110 V) 1-Pole, 40 °C 6 A
(110 V) 1-Pole, 60 °C 6 A
(110 V) 1-Pole, 70 °C 6 A
(110 V) 2 Poles in Series, 40 °C 25 A
(110 V) 2 Poles in Series, 60 °C 25 A
(110 V) 2 Poles in Series, 70 °C 22 A
(110 V) 3 Poles in Series, 40 °C 25 A
(110 V) 3 Poles in Series, 60 °C 25 A
(110 V) 3 Poles in Series, 70 °C 22 A
(220 V) 2 Poles in Series, 40 °C 6 A
(220 V) 2 Poles in Series, 60 °C 6 A
(220 V) 2 Poles in Series, 70 °C 6 A
(220 V) 3 Poles in Series, 40 °C 25 A
(220 V) 3 Poles in Series, 60 °C 25 A
(220 V) 3 Poles in Series, 70 °C 22 A
(72 V) 1-Pole, 40 °C 25 A
(72 V) 1-Pole, 60 °C 25 A
(72 V) 1-Pole, 70 °C 22 A
(72 V) 2 Poles in Series, 40 °C 25 A
(72 V) 2 Poles in Series, 60 °C 25 A
(72 V) 2 Poles in Series, 70 °C 22 A
(72 V) 3 Poles in Series, 40 °C 25 A
(72 V) 3 Poles in Series, 60 °C 25 A
(72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-5 (Ie)(110 V) 1-Pole, 40 °C 4 A
(110 V) 1-Pole, 60 °C 4 A
(110 V) 1-Pole, 70 °C 4 A
(110 V) 2 Poles in Series, 40 °C 10 A
(110 V) 2 Poles in Series, 60 °C 10 A
(110 V) 2 Poles in Series, 70 °C 10 A
(110 V) 3 Poles in Series, 40 °C 25 A
(110 V) 3 Poles in Series, 60 °C 25 A
(110 V) 3 Poles in Series, 70 °C 22 A
(220 V) 2 Poles in Series, 40 °C 4 A
(220 V) 2 Poles in Series, 60 °C 4 A
(220 V) 2 Poles in Series, 70 °C 4 A
(220 V) 3 Poles in Series, 40 °C 9 A
(220 V) 3 Poles in Series, 60 °C 9 A
(220 V) 3 Poles in Series, 70 °C 9 A
(72 V) 1-Pole, 40 °C 9 A
(72 V) 1-Pole, 60 °C 9 A
(72 V) 1-Pole, 70 °C 9 A
(72 V) 2 Poles in Series, 40 °C 25 A
(72 V) 2 Poles in Series, 60 °C 25 A
(72 V) 2 Poles in Series, 70 °C 22 A
(72 V) 3 Poles in Series, 40 °C 25 A
(72 V) 3 Poles in Series, 60 °C 25 A
(72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-13 (Ie)(24 V) 6 A / 144 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)(415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
(380 / 400 V) 4 kW
(220 / 230 / 240 V) 2.2 kW
Rated Operational Power AC-3e (Pe)(415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
(380 / 400 V) 4 kW
(220 / 230 / 240 V) 2.2 kW
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 690 V
acc. to IEC 60947-5-1 690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)6 kV
Maximum Electrical Switching Frequency(AC-1) 600 cycles per hour
(AC-15) 1200 cycles per hour
(AC-2 / AC-4) 300 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency3600 cycles per hour
Rated Control Circuit Voltage (Uc)50 Hz 48 ... 130 V
60 Hz 48 ... 130 V
DC Operation 48 ... 130 V
Power Lossat 6 A per Pole 0.1 W
at Rated Operating Conditions AC-1 per Pole 0.8 W
at Rated Operating Conditions AC-3 per Pole 0.1 W
Operate TimeBetween Coil De-energization and NC Contact Closing 13 ... 98 ms
Between Coil De-energization and NO Contact Opening 11 ... 95 ms
Between Coil Energization and NC Contact Opening 38 ... 90 ms
Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied) 2 x M4 Screws Placed Diagonally
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP10
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening TorqueAuxiliary Circuit 1.2 N·m
Control Circuit 1.2 N·m
Main Circuit 1.5 N·m
Terminal TypeRing-Tongue Terminals
Product NameBlock Contactor
Technical UL/CSA
NEMA Size00
Continuous Current Rating NEMA9 A
Horsepower Rating NEMA(115 V AC) Single Phase 1/3 Hp
(200 V AC) Three Phase 1-1/2 Hp
(230 V AC) Single Phase 1 Hp
(230 V AC) Three Phase 1-1/2 Hp
(460 V AC) Three Phase 2 Hp
(575 V AC) Three Phase 2 Hp
Maximum Operating Voltage UL/CSAMain Circuit 600 V
General Use Rating UL/CSA(600 V AC) 25 A
Horsepower Rating UL/CSA(120 V AC) Single Phase 3/4 hp
(200 ... 208 V AC) Three Phase 2 hp
(220 ... 240 V AC) Three Phase 2 hp
(240 V AC) Single Phase 1-1/2 hp
(440 ... 480 V AC) Three Phase 5 hp
(550 ... 600 V AC) Three Phase 7-1/2 hp
Tightening Torque UL/CSAAuxiliary Circuit 11 in·lb
Control Circuit 11 in·lb
Main Circuit 13 in·lb
Full Load Amps Motor Use(120 V AC) Single Phase 13.8 A
(200 ... 208 V AC) Three Phase 7.8 A
(220 ... 240 V AC) Three Phase 6.8 A
(240 V AC) Single Phase 10 A
(440 ... 480 V AC) Three Phase 7.6 A
(550 ... 600 V AC) Three Phase 9 A
Environmental
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C
Close to Contactor without Thermal O/L Relay -40 ... 70 °C
Close to Contactor for Storage -60 ... +80 °C
Climatic WithstandCategory B according to IEC 60947-1 Annex Q
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373Category 1, Class B
Pollution Degree3
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIPca06a406-a011-4ccc-a7c1-d6f21053bd3b China
Simplified SCIP072a8cb7-1cc5-41c6-893b-5e08cbb4da59 Spain
d0f164a2-4814-4fe7-b9a6-c33e2dece9e1 Hungary
ca620e0b-d15a-428c-9403-4d5da1e0dffa Belgium
47ba88d4-7ca4-4d66-a5c6-434470bb7e15 France
e96d9225-d904-4c2a-819a-f0d47cc36fb2 Germany
8b207ae6-ddc4-4432-a953-2ed93a9f8b2b Poland
6a549be9-9f8d-464c-9482-fc23cb5277af Portugal
3471e859-9cb1-4412-bffe-6041d2f90d15 Bulgaria
b49712ea-0c44-486d-9a49-68f92ecd6409 Germany
2550b3aa-8680-4c62-8592-98281e7560d3 Sweden
0816a516-471c-454e-89bd-a1e496fb4797 France
977d586a-2959-4403-ab2f-6df0259f0d08 Estonia
6e20fb63-067a-4b2f-82e5-a1a5a9888a4d Greece
89d87129-dca8-45e0-b88a-9a372dd88a42 Poland
6b81241e-1c3b-4325-b103-820c9703793d Hungary
a994cc82-e644-44dc-bdbd-19a01e118a51 Netherlands
0926b176-ad98-4aa9-997a-484997faad9f Belgium
71783093-7a2c-446e-8984-c9e03da4e8ff Finland
755383f0-0a21-43fa-90e0-88d2c1e9eeeb Norway
c2d58517-5cc8-4061-860c-bf92cb85f70d Czech Republic
61c39b94-1b86-41c5-8798-143a3c93eae5 Sweden
efc23c8c-18c9-401d-b6be-0979ce603c21 Poland
12c28e70-9aeb-46ad-9874-d2e257e667c5 Germany
31544a20-2475-4dc7-a49c-29ea01ce9498 Croatia
ca0448d6-54f5-44d2-8c1f-587a69254538 Denmark
e91fb549-a21e-4d5c-8c7f-481676697ea4 Germany
379e304b-12aa-4d7c-9f14-f0f377cbbe06 Germany
Toxic Substances Control Act - TSCA2CMT2023-006525
WEEE B2C / B2BBusiness To Business
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
End Of Life Disassembling Instructions1SBC101080M6801
Environmental Product Declaration - EPD1SBD250584E3000
2TFP200035A1001
Sustainable Material Content in Packaging (wt. %)Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)Recycled Metal - 28 %
Certificates and Declarations
CB CertificateCB_SE-113345
CCC CertificateCCC_2024010304656669
CQC CertificateCQC2010010304445624
Declaration of Conformity - CCC2020980304001253
Declaration of Conformity - CE1SBD250004U1000
Declaration of Conformity - UKCA1SBD250035U1000
UL Listing CardUL_E312527
UR CertificateUL_20121122-E312527_9_5
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width87 mm
Package Level 1 Depth / Length79 mm
Package Level 1 Height47 mm
Package Level 1 Gross Weight0.32 kg
Package Level 1 EAN3471523127722
Package Level 2 Unitsbox 27 piece
Package Level 2 Width250 mm
Package Level 2 Depth / Length300 mm
Package Level 2 Height315 mm
Package Level 2 Gross Weight17.28 kg
External Classifications and Standards
Object Classification CodeQ
ETIM 7EC000066 - Power contactor, AC switching
ETIM 8EC000066 - Power contactor, AC switching
ETIM 9EC000066 - Power contactor, AC switching
eClassV11.0 : 27371003
UNSPSC39121529
IDEA Granular Category Code (IGCC)4758 >> Iec Contactors

Datasheet - PDF

Title: Size: Type:
PDF CATALOGUE MOTOR PROTECTION EN.pdf 240 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.