Product successfully added to your shopping cart
1SBL281074R8010
ABB
1
AX32-30-10-80 220-230V50Hz 230-240V60Hz
AX32-30-10-80 220-230V50Hz/230-240V60Hz Contactor
Low-voltage industrial components > Power contactor, AC switching
Contactors and overload relays
Brand new product in its original packaging covered by the warranties and certifications provided by ABB
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| EPLAN Data | 9AAC177928_EPLAN |
| Data Sheet, Technical Information | 1SBC100187L0203 |
| Instructions and Manuals | 9AKK107492A7057 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 54 mm |
| Product Net Depth / Length | 90 mm |
| Product Net Height | 108.3 mm |
| Product Net Weight | 0.667 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 0 |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Main Circuit 690 V | |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 65 A |
| acc. to IEC 60947-5-1, Θ = 40 °C 16 A | |
| Rated Operational Current AC-1 (Ie) | (220 / 240 V) 55 °C 55 A |
| (690 V) 40 °C 55 A | |
| (690 V) 70 °C 39 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 32 A |
| (440 V) 55 °C 32 A | |
| (500 V) 55 °C 28 A | |
| (690 V) 55 °C 21 A | |
| (380 / 400 V) 55 °C 32 A | |
| (220 / 230 / 240 V) 55 °C 32 A | |
| Rated Operational Current AC-15 (Ie) | (500 V) NC 2 |
| (500 V) 2 A | |
| (690 V) 2 A | |
| (24 / 127 V) 6 A | |
| (220 / 240 V) 4 A | |
| (380 / 400 V) 3 A | |
| (400 / 440 V) 2 A | |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| (110 V) 0.55 A / 60 W | |
| (125 V) 1.1 A / 138 W | |
| (220 V) 0.55 A / 121 W | |
| (250 V) 0.55 A / 138 W | |
| (400 V) 2.8 A / 134 W | |
| (500 V) 2 A / 144 W | |
| Rated Operational Power AC-3 (Pe) | (415 V) 15 kW |
| (440 V) 18.5 kW | |
| (500 V) 18.5 kW | |
| (690 V) 18.5 kW | |
| (380 / 400 V) 15 kW | |
| (220 / 230 / 240 V) 9 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 400 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 65 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 600 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A | |
| for 0.1 s 140 A | |
| for 1 s 100 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 820 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 340 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V |
| Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| (AC-15) 1200 cycles per hour | |
| (AC-3) 1200 cycles per hour | |
| (DC-13) 900 cycles per hour | |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 220 ... 230 V |
| 60 Hz 230 ... 240 V | |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 2.5 W |
| at Rated Operating Conditions AC-3 per Pole 0.9 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 7 ... 14 ms |
| Between Coil De-energization and NO Contact Opening 4 ... 11 ms | |
| Between Coil Energization and NC Contact Opening 6 ... 18 ms | |
| Between Coil Energization and NO Contact Closing 8 ... 21 ms | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 | |
| Tightening Torque | Auxiliary Circuit 1 N·m |
| Control Circuit 1 N·m | |
| Main Circuit 2.3 N·m | |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| General Use Rating UL/CSA | (600 V AC) 50 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 3 hp |
| (200 ... 208 V AC) Three Phase 10 hp | |
| (220 ... 240 V AC) Three Phase 10 hp | |
| (240 V AC) Single Phase 7.5 hp | |
| (440 ... 480 V AC) Three Phase 25 hp | |
| (550 ... 600 V AC) Three Phase 30 hp | |
| Tightening Torque UL/CSA | Auxiliary Circuit 9 in·lb |
| Control Circuit 9 in·lb | |
| Main Circuit 20 in·lb | |
| Full Load Amps Motor Use | (120 V AC) Single Phase 34 A |
| (200 ... 208 V AC) Three Phase 32.2 A | |
| (220 ... 240 V AC) Three Phase 28 A | |
| (240 V AC) Single Phase 40 A | |
| (440 ... 480 V AC) Three Phase 34 A | |
| (550 ... 600 V AC) Three Phase 32 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C |
| Close to Contactor without Thermal O/L Relay -40 ... 70 °C | |
| Close to Contactor for Storage -60 ... +80 °C | |
| Near Contactor for Operation in Free Air -40 ... 70 °C | |
| Climatic Withstand | according to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 Specification II |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Simplified SCIP | 1fa2bf05-8d82-4696-9d67-8ca45d1f6807 Finland |
| 21b2866a-c103-4bcc-b13e-9a79ef47fd9a Hungary | |
| 2258c81c-5dba-48dc-92a4-f3345f0dd577 Germany | |
| 2874ad5b-104f-4107-b8ac-a4ec89dedb51 Croatia | |
| 3f1df392-9ace-44a0-ad36-6f2d094de224 Germany | |
| 467c33ce-a571-4ab7-90e3-9ea49ecaa8f9 Poland | |
| 572fba3c-0d3d-411a-84e3-0785ab7e7f66 Czech Republic | |
| 5a4626c5-d1f8-4c48-9150-a32264a0c112 Denmark | |
| 86869519-50f8-41a1-ab4c-02efbc42c380 Estonia | |
| 8e1d6f30-eb59-4784-8dc1-a2ac2a56ecd0 Hungary | |
| 912ab3a7-3917-4348-8dcb-609b2b6fc350 Sweden | |
| 9f6699ed-0aa3-4438-acee-b6e1d8516714 Greece | |
| a5589388-3e31-4a69-b85b-33e11bd8075a Portugal | |
| a7c35f59-a5ee-41e8-9fbf-5c1d616d2518 Belgium | |
| afc1e8c5-35f8-4f9e-a138-9e94dee59fad Belgium | |
| b19d1189-110c-4361-a0c0-e9669be74c1f Italy | |
| b86a8ffe-903d-4d9f-8725-e0eeab4aff5b Norway | |
| dd1e0116-108d-45d9-8c88-77b3f0825240 Spain | |
| f9a0001b-b41a-4f9d-8d76-4b948e94ea91 France | |
| fd766c33-9e6f-490b-aaa0-5a3a783c42a1 Netherlands | |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| Certificates and Declarations | |
| CB Certificate | 9AKK107492A7073 |
| CCC Certificate | 9AKK107492A7090 |
| CCS Certificate | GZ23PTB00147 |
| CQC Certificate | CQC2013010304647116 |
| Declaration of Conformity - CCC | 2020980304001065 |
| Declaration of Conformity - CE | 1SBD250011U1000 |
| UL Certificate | UL_20140702-E312527-10-6 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 65 mm |
| Package Level 1 Depth / Length | 101 mm |
| Package Level 1 Height | 115 mm |
| Package Level 1 Gross Weight | 0.71 kg |
| Package Level 1 EAN | 3471522399809 |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4755 >> Contactors |
| E-Number (Finland) | 3707341 |
| Feature Name | Feature Value |
|---|---|
| Rated control supply voltage AC 50 Hz (EF003978) | 220 V |
| Rated control supply voltage AC 60 Hz (EF003979) | 230 V |
| Voltage type for actuating (EF008242) | AC |
| Rated operation current Ie at AC-1, 400 V (EF001393) | 55 A |
| Rated operation current Ie at AC-3, 400 V (EF001392) | 32 A |
| Rated operation power at AC-3, 400 V (EF001364) | 15 kW |
| Modular version (EF001126) | No |
| Number of auxiliary contacts as normally open contact (EF001376) | 1 |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| Number of normally closed contacts as main contact (EF001375) | 0 |
| Number of normally open contacts as main contact (EF001374) | 3 |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE MOTOR PROTECTION EN.pdf | 240 Mbytes |
|
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.