KLV-48UPM-F 178832 EATON ELECTRIC Quadro di distribuzione compatto da incasso multimedia 4 file porta in lam.. Visualizza ingrandito
Le immagini sono solo per fini illustrativi. Si prega di fare riferimento alla scheda tecnica p...

KLV-48UPM-F 178832 EATON ELECTRIC Quadro di distribuzione compatto da incasso multimedia 4 file porta in lam..

KLV-48UPM-F

178832

EATON-MOELLER

Quadro di distribuzione compatto da incasso; multimedia; 4 file; porta in lamiera d'acciaio piatta

Scatola multimediale da incasso 4 file porta in metallo

Eaton xComfort KLV LV systems Final Distribution Boards. Compact distribution board-flush mounting, multimedia, 4-rows, flush sheet steel door

Maggiori dettagli


materiale d’installazione per reti di comunicazione dnt/fnt > Quadro per telecomunicazioni

Scatole di distribuzione compatti

* Prodotto nuovo nel suo imballaggio d'origine con tutte le garanzie e certificazioni de EATON-MOELLER

Prezzo totale: $222.02
Prezzo unitario: $222.02

Quantità Prezzo
1+$222.02
2+$218.25
*Questo prezzo è per unità e mostra il valore netto ( escluse le imposte indirette se applicabile ).

Se il nostro prezzo non è il migliore, chiedici un preventivo Richiedi un preventivo

Dettagli



General specifications

Product Name
Eaton xComfort KLV multimedia distribution board
Catalog Number
178832
EAN
4015081741618
Product Length/Depth
100 mm
Product Height
715 mm
Product Width
360 mm
Product Weight
6.5 kg
Compliances
RoHS conform
Certifications
IEC/EN 60670-24 (GP)
IEC/EN 62208
Model Code
KLV-48UPM-F

Delivery program

Type
Basic deviceInstallation distribution boardKLV multimedia
Model
Distributor enclosure
Application
Indoor (installation site)
Color
Traffic white (RAL 9016)
White

Technical data - electrical

Voltage rating at AC
230 V AC
Frequency rating of contacts
50 Hz

Technical data - mechanical

Mounting dimension
Other
Mounting method
DIN-compatible
Flush mounting
Flush mounted (plaster)
Material
Steel plate/plastic
Sheet steel, powder-coated
Polystyren (plastic)
Number of cores (dual) - max
12
Number of module space units per row
12
Number of mountable connection strips
12
Number of rows
4
Terminal type
Without terminals
Cable entry postion
Cable entries on top and bottom, side, back plate
Cover/door color
White
Module rack type
Media mounting plate
Protective shrouding material
Without shroud for protection against accidental contact

Temperature-rise verification as per IEC 60890

Heat diss. ambient 35°C delta T:20°C flush mount individ. encl. top(IEC 60890)
24 W
Heat diss. ambient 35°C delta T:35°C flush mount individ. encl. top(IEC 60890)
48 W

Design verification as per IEC/EN 61439 - technical data

Ambient operating temperature details
-5 °C - 40 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
650 °C; meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2.6 Mechanical impact
IK05
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP30
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 400 V AC
10.9.3 Impulse withstand voltage
4 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.

Additional information

Features
110-compatible
Fitted with:
Wall trough
Spirit level for leveling
Device holder
3D adjustment element for mounting designed to adjust the mounting depth by up to 18 mm
Cable retainer
Microperforated mounting plate
Nail lugs
Installation instructions
Device support rails
2x single-way socket outlet
Door/Frame
Functions
Basic device
Protection class
II (totally insulated)
Special features
IP30Protection Class IIPlastic enclosure with sheet steel door, white (RAL 9016)Note: To obtain protection class II, all devices installed on the mounting plate must be of the fully insulated type.

Datasheet - PDF

Titolo: Dimensione: Tipo:
KLV-48UPM-F 178832 ES_178830.pdf 2 Mbytes   KLV-48UPM-F  178832 ES_178830.pdf

Recensioni: (0)

Nessun commento per il momento.

Inserisci recensione
nascondi form
Valutazione:
Nome:
Email:
Titolo:
Testo:
  Captcha
  Inserisci recensione

Tutti i feedback che riceviamo dagli elementi che offriamo sono reali e verificati. Un piccolo gesto, ma di grande valore. Quindi grazie per quel minuto si spende in noi lasciare il vostro parere e punteggio sui prodotti, perché ci aiuta a continuare a migliorare e di offrire ancora maggiore qualità del servizio.