IB IL TEMP 4/8 RTD-PAC 2863915 PHOENIX CONTACT Inline analog input terminal, complete with accessories (conn.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

IB IL TEMP 4/8 RTD-PAC 2863915 PHOENIX CONTACT Inline analog input terminal, complete with accessories (conn..

IB IL TEMP 4/8 RTD-PAC

2863915

PHOENIX_CONTACT

Available

Ship on today

Inline analog input terminal, complete with accessories (connector and labeling field), 8 channels, RTD (resistance temperature detector), 2, 3-wire connection method

More details


AUTOMATION Industrial Automation - PHOENIX CONTACT

Control technology - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Product description

This terminal block provides you with an inexpensive 8-channel input module for resistive temperature sensors.

The module supports platinum and nickel sensors in acc. with DIN and SAMA directives. With the platinum sensors, not only Pt 100, Pt 500 and Pt 1000 are supported, but also the Pt 10000 (e.g. from building automation) and numerous other measuring sensors. The sensors are connected using the 2 or 3-wire system.

The measured temperature is displayed via 16-bit values per channel (2 x 4 channels in process data multiplex) or via 16 bits per channel with PCP communication.

Software library CD "CD AS SW LIB" contains function blocks and sample programs for analog value processing.

The Inline terminal can be identified using hinged labeling fields. The fields have insert cards that can be labeled individually to suit the application. Zack marker strip ZBF 6... or Zack marker sheet ZBFM 6... can also be used for labeling the terminal points.

Dimensions

Width48.8 mm
Height136.8 mm
Depth71.5 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 55 °C
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20

General

Net weight190 g
Mounting typeDIN rail
Operating modeProcess data mode with 5 words/1 word PCP

Interfaces

DesignationInline local bus
Connection methodInline data jumper
Transmission speed500 kBit/s
Transmission physicsCopper

Inline potentials

Communications power UL7.5 V DC (via voltage jumper)
Current consumption from ULtyp. 75 mA
I/O supply voltage UANA24 V DC
Current consumption from UANAtyp. 28 mA
Power consumptiontyp. 1.24 W

Analog inputs

Number of inputs8
Input nameAnalog RTD inputs
Description of the inputInput for resistive temperature sensors
Connection methodSpring-cage connection
2, 3-conductor
Sensor types (RTD) that can be usedPt, Ni, KTY, Cu sensors, linear resistors
Linear resistance measuring range0 Ω ... 400 Ω
0 Ω ... 20 kΩ
Measuring principleSuccessive approximation
Measured value representation16 bits (15 bits + sign bit)
A/D conversion timemax. 10 µs
Process data update6 ms (Up to 230 ms possible depending on operating mode)
Data formatsIB IL, IB ST, S7 compatible
Precisiontyp. 0.06 %

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2863915-IB IL TEMP 4/8 RTD-PACEnglish127 KbytesPHOENIX CONTACT-2863915-IB IL TEMP 4/8 RTD-PAC

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or