PSR-SCP- 24DC/FSP2/2X1/1X2 2986575 PHOENIX CONTACT Coupling relay View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PSR-SCP- 24DC/FSP2/2X1/1X2 2986575 PHOENIX CONTACT Coupling relay

PSR-SCP- 24DC/FSP2/2X1/1X2

2986575

PHOENIX_CONTACT

Coupling relay

More details


Safety

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $202.28
Unit price: $202.28

Quantity Price
1+$202.28
2+$180.82
3+$167.96
4+$160.68
6+$155.08
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Viewed products


More info



Key Commercial Data

Orderkey2986575
Packing unit1 pc
Catalog pagePage 287 (C-6-2017)
GTIN4046356553322
Weight per Piece (excluding packing)108.770 g
Custom tariff number85364900
Country of originDE (Germany)

Note

Utilization restriction1

Dimensions

Width17.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 70 °C
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Maximum altitude≤ 2000 m (Above sea level)

Input data

Rated control circuit supply voltage US24 V DC -15 % / +10 %
Rated control supply current IStyp. 55 mA
Power consumption at UStyp. 1.32 W
Inrush currentmax. 100 mA
Typ. starting time with Us50 ms
Typical release time50 ms
Recovery time1 s
Operating voltage display1 x yellow LED
Protective circuitSurge protection Suppressor diode, 33 V (A1 - A2)
Maximum switching frequency0.5 Hz
Filter timemax. 5 ms (at A1 in the event of voltage dips at Us)
max. 2 ms (Test pulse width; high test pulse at A1/A2)
≥ 100 ms (Test pulse width; high test pulse at A1/A2)
Test pulse rate = 80 x Test pulse width
max. 5 ms (Test pulse width; low test pulse at A1/A2)
≥ 50 ms (Test pulse rate; low test pulse at A1/A2)
Test pulse rate = 15 x Test pulse width

Output data

Contact type2 enabling current paths
1 confirmation current path
Contact materialAgCuNi, + 0.2 µm Au
Maximum switching voltage250 V AC/DC (N/O contact / N/C contact, observe the load curve)
Minimum switching voltage15 V AC/DC (N/O contact / N/C contact)
Limiting continuous current5 A (N/O contact, pay attention to the derating)
100 mA (N/C contact)
Maximum inrush current5 A (N/O contact)
100 mA (N/C contact)
Inrush current, minimum5 mA (N/O contact / N/C contact)
Sq. Total current50 A2(observe derating)
Interrupting rating (ohmic load) max.120 W (24 V DC, τ = 0 ms, N/C contact: 2.4 W)
192 W (48 V DC, τ = 0 ms, N/C contact: 4.8 W)
162 W (60 V DC, τ = 0 ms, N/C contact: 6 W)
66 W (110 V DC, τ = 0 ms, N/C contact: 11 W)
60 W (220 V DC, τ = 0 ms, N/C contact: 22 W)
1250 VA (250 V AC, τ = 0 ms, N/C contact: 25 VA)
Maximum interrupting rating (inductive load)72 W (24 V DC, τ = 40 ms, N/C contact: 2.4 W)
43 W (48 V DC, τ = 40 ms, N/C contact: 4.8 W)
41 W (60 V DC, τ = 40 ms, N/C contact: 6 W)
35 W (110 V DC, τ = 40 ms, N/C contact: 11 W)
48 W (220 V DC, τ = 40 ms, N/C contact: 22 W)
Switching capacitymin. 75 mW
Mechanical service life10x 106cycles
Output fuse10 A gL/gG (N/O contact)
4 A gL/gG (for low-demand applications)
150 mA Fast-blow (N/C contact)

General

Relay typeElectromechanical relay with forcibly guided contacts in accordance with EN 50205
Nominal operating mode100% operating factor
Net weight108.77 g
Mounting positionany
Mounting typeDIN rail mounting
Degree of protectionIP20
IP54
Min. degree of protection of inst. locationIP54
Housing materialPBT
Housing coloryellow

Connection data

Connection methodScrew connection
pluggableYes
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length7 mm
Screw threadM3

Safety-related characteristic data

Stop category0
DesignationIEC 61508 - High demand
Safety Integrity Level (SIL)2 (max. 10% of the entire SIL; diagnostic coverage (DC) of the control unit at A1/A2 must be ≥ 90% )
DesignationIEC 61508 - Low demand
Safety Integrity Level (SIL)2 (max. 10% of the entire SIL; diagnostic coverage (DC) of the control unit at A1/A2 must be ≥ 90% )
DesignationEN ISO 13849
Performance level (PL)c (Diagnostic coverage (DC) of the control unit at A1/A2 must be ≥ 90 %)
Category1 (Diagnostic coverage (DC) of the control unit at A1/A2 must be ≥ 90 %)
DesignationEN 62061
Safety Integrity Level Claim Limit (SIL CL)1 (max. 10% of the entire SIL; diagnostic coverage (DC) of the control unit at A1/A2 must be ≥ 90% )
DesignationEN 50156
Safety Integrity Level (SIL)2

Standards and Regulations

DesignationAir clearances and creepage distances between the power circuits
Standards/regulationsDIN EN 50178/VDE 0160
Rated insulation voltage250 V AC
Rated surge voltage/insulationSafe isolation, reinforced insulation 6 kV between the control circuits (A1/A2), (31/32), (13/14, 23/24)
Degree of pollution2
Overvoltage categoryIII
Shock15g
Vibration (operation)10 Hz ... 150 Hz, 2g
ConformanceCE-compliant

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.