MINI MCR-SL-CVS-24-5-10-SP-NC 2902823 PHOENIX CONTACT Constant voltage source View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MINI MCR-SL-CVS-24-5-10-SP-NC 2902823 PHOENIX CONTACT Constant voltage source

MINI MCR-SL-CVS-24-5-10-SP-NC

2902823

PHOENIX_CONTACT

Constant voltage source

More details


INTERFACE Components (IF)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Key Commercial Data

Orderkey2902823
Packing unit1 pc
Catalog pagePage 114 (C-7-2015)
GTIN4046356682435
Weight per Piece (excluding packing)79.300 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restriction1

Dimensions

Width6.2 mm
Height93.1 mm
Depth102.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 65 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C

Input data

Voltage input signal9.6 V DC ... 30 V DC

Output data

Configurable/programmableYes, preconfigured
Output current≤ 30 mA
Short-circuit currentapprox. 32 mA
Ripple< 20 mVPP

Power supply

Nominal supply voltage24 V DC
Supply voltage range9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Max. current consumption< 25 mA (10 V output with 30 mA load at 24 V DC IN)
< 65 mA (10 V output with 30 mA load at 9.6 V DC IN)
< 50 mA (10 V voltage output with 30 mA load at 12 V DC IN)
< 20 mA (10 V voltage output with 30 mA load at 30 V DC IN)
Power consumption< 600 mW (at 24 V IN)
< 624 mW (at 9.6 V IN)
< 564 mW (At 12 V IN)
< 540 mW (at 30 V IN)

Connection data

Connection methodSpring-cage connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Stripping length8 mm

General

Maximum transmission error≤ 0.1 % (of final value)
≤ 0.5 % (Without adjustment)
Maximum temperature coefficient< 0.01 %/K
Temperature coefficient, typical< 0.002 %/K
Setting range comparison± 300 mV
Electrical isolationBasic insulation according to EN 61010
Overvoltage categoryII
Degree of pollution2
Rated insulation voltage50 V AC/DC
Test voltage input/output1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Colorgreen
Housing materialPBT
Mounting positionany
Assembly instructionsThe T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC
Certificate of classificationDNV GL 14085-15HH
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Standards/regulationsEN 61000-4-2
DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
EN 61000-4-4
CommentsCriterion B
Standards/regulationsEN 61000-4-5
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Electrical isolationBasic insulation according to EN 61010
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.