ES4P-221-DRXX1 111018 EATON MOELLER Safety relay, 24 V DC, 14DI, 4DO relays, easyNet View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

ES4P-221-DRXX1 111018 EATON MOELLER Safety relay, 24 V DC, 14DI, 4DO relays, easyNet

ES4P-221-DRXX1

111018

EATON - MOELLER

Available

Ship on today

Product on demand only, returns will not be accepted.

Safety relay, 24 V DC, 14DI, 4DO relays, easyNet

More details


Safety

ES4P easySafety - EATON - MOELLER

easySafety - ES4P - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$490.92
2+$484.43
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  Control relays for safety applications
Basic function
  easy800 with safety function blocks
Features
   
Safety functions
  Stopping in the event of an emergency
Protective door
OSSD input
ESPE with muting function
Two-hand control
Highest speed monitoring
Zero speed monitoring
Safety timing relay
Mode selection
Enabling switch
Feedback circuit
Display & keypad
  -
Mounting width
 mm107.5
Technical safety parameters:
   
Values according to EN ISO 13849-1
   
Performance level
according to EN ISO 13849 PL e
Category
according to EN ISO 13849 Kat. 4
Safety integrity level claim limit
in accordance with 62061 SILCL 3
Probability of failure per hour
PFHdx 10-104.26
Safety integrity level
In accordance with IEC 61508 SIL 3
Real time clock
  
General
Standards
  EN 50156-1:2013
EN 50178
EN 55011
EN 55022
IEC/EN 61000-4, IEC/EN 61000-6
IEC 60068-2-6
EN ISO 954‐1: 1996, Category 4
EN ISO 13849-1: 2008, PL e (Performance Level)
IEC/EN 61508, SIL3 (Safety Integrity Level)
IEC/EN 62061, SILCL 3 (Safety integrity level claim limit)+AC:2010
Dimensions (W x H x D)
 mm107.5 (6 TE) x 90 x 72
Weight
 kg0.38
Mounting
  Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Times
Inputs
   
Max. duration of external test pulde
 ms1
Semi-conductor output
   
Off test pulse
 ms< 1
Off-delay
 ms< 1
Terminal capacities
Solid
 mm20.2/4 (AWG 22 - 12)
Flexible with ferrule
 mm20.2/2.5 (AWG 22 - 12)
Standard screwdriver
 mm3.5 x 0.8
Max. tightening torque
 Nm0.6
Climatic environmental conditions
Operating ambient temperature
 °C-25 to + 55
cold as per IEC 60068-2-1
heat as per IEC 60068-2-2
Damp heat – constant to IEC 60068-2-78 – cyclical to ICE 60068-2-30
Condensation
  Take appropriate measures to prevent condensation
Ambient temperature
   
Storage
ϑ°C-40 - +70
relative humidity
 %5 - 95
in accordance with IEC 60068-2-30, IEC 60068-2-78
Non-condensing
Air pressure (operation)
 hPa795 - 1080
Ambient conditions, mechanical
Degree of protection
  IP20 (IEC/EN 60529, EN50178, VBG 4)
Constant amplitude 0.15 mm
 Hz 
constant amplitude
 Hz10 - 57 (0.15 mm)
constant acceleration
 Hz57 - 150 (2g)
Vibrations
 HzIn accordance with IEC 60068-2-6
Mechanical shock resistance
 g18 shocks
Sinusoidal 15 g/11 ms
according to IEC 60068-2-27
Drop to
Drop heightmm50
(IEC/EN 60068-2-31)
Free fall, packaged
 m0,3
(IEC/EN 61131-2)
Electromagnetic compatibility (EMC)
Electromagnetic compatibility
  As per ICE 62061, increased EMC requirements for safety-relevant functions
Overvoltage category/pollution degree
  III/2
Electrostatic discharge (ESD)
   
applied standard
  according to IEC EN 61000-4-2
Air discharge
 kV15
Contact discharge
 kV8
Electromagnetic fields (RFI)
 V/m30
to IEC EN 61000-4-3
Radio interference suppression
  EN 55011 Class B, EN 55022 Class B
Burst
 kVaccording to IEC/EN 61000-4-4
Supply cables: 4
Signal cables: 4
power pulses (Surge)
  2 kV (supply cables, symmetrical)
4 kV (semi-conductor outputs, symmetrical)
In accordance with IEC 62061
Immunity to line-conducted interference
 V20, in accordsnce with IEC/EN 61000-4-6
Insulation resistance
Clearance in air and creepage distances
  EN 50178, UL 508, CSA C22.2, No. 142, EN 60664-1:2003
Insulation resistance
  EN 50178
Back-up of real-time clock
Back-up of real-time clock
  
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA0
Heat dissipation per pole, current-dependent
PvidW0
Equipment heat dissipation, current-dependent
PvidW0
Static heat dissipation, non-current-dependent
PvsW6
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-25
Operating ambient temperature max.
 °C55
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Meets the product standard's requirements.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
PLC's (EG000024) / Logic module (EC001417)
Electric engineering, automation, process control engineering / Control / Programmable logic control (SPS) / Logic module ([email protected] [AKE539011])
Supply voltage AC 50 Hz
 V0 - 0
Supply voltage AC 60 Hz
 V0 - 0
Supply voltage DC
 V20.4 - 28.8
Voltage type of supply voltage
  DC
Switching current
 A8
Number of analogue inputs
  0
Number of analogue outputs
  4
Number of digital inputs
  14
Number of digital outputs
  4
With relay output
  Yes
Number of HW-interfaces industrial Ethernet
  0
Number of HW-interfaces PROFINET
  0
Number of HW-interfaces RS-232
  1
Number of HW-interfaces RS-422
  0
Number of HW-interfaces RS-485
  0
Number of HW-interfaces serial TTY
  0
Number of HW-interfaces USB
  0
Number of HW-interfaces parallel
  0
Number of HW-interfaces Wireless
  0
Number of HW-interfaces other
  3
With optical interface
  No
Supporting protocol for TCP/IP
  No
Supporting protocol for PROFIBUS
  No
Supporting protocol for CAN
  No
Supporting protocol for INTERBUS
  No
Supporting protocol for ASI
  No
Supporting protocol for KNX
  No
Supporting protocol for MODBUS
  No
Supporting protocol for Data-Highway
  No
Supporting protocol for DeviceNet
  No
Supporting protocol for SUCONET
  No
Supporting protocol for LON
  No
Supporting protocol for PROFINET IO
  No
Supporting protocol for PROFINET CBA
  No
Supporting protocol for SERCOS
  No
Supporting protocol for Foundation Fieldbus
  No
Supporting protocol for EtherNet/IP
  No
Supporting protocol for AS-Interface Safety at Work
  No
Supporting protocol for DeviceNet Safety
  No
Supporting protocol for INTERBUS-Safety
  No
Supporting protocol for PROFIsafe
  No
Supporting protocol for SafetyBUS p
  No
Supporting protocol for other bus systems
  Yes
Radio standard Bluetooth
  No
Radio standard WLAN 802.11
  No
Radio standard GPRS
  No
Radio standard GSM
  No
Radio standard UMTS
  No
IO link master
  No
Redundancy
  Yes
With display
  No
Degree of protection (IP)
  IP20
Basic device
  Yes
Expandable
  Yes
Expansion device
  No
With timer
  Yes
Rail mounting possible
  Yes
Wall mounting/direct mounting
  Yes
Front build in possible
  No
Rack-assembly possible
  No
Suitable for safety functions
  Yes
Category according to EN 954-1
  4
SIL according to IEC 61508
  None
Performance level acc. to EN ISO 13849-1
  Level e
Appendant operation agent (Ex ia)
  No
Appendant operation agent (Ex ib)
  No
Explosion safety category for gas
  None
Explosion safety category for dust
  None
Width
 mm107.5
Height
 mm90
Depth
 mm72
Approvals
Product Standards  IEC/EN see Technical Data; UL 508; CSA-C22.20.4-04; CSA-22.2 No. 142-MI1987; CE marking
UL File No.  CSA report applies to both US and Canada
UL Category Control No.  NRAQ
CSA File No.  012528
CSA Class No.  2252-81; 2252-01
North America Certification  CSA certified, certified by CSA for use in the US
Degree of Protection  IEC: IP20, UL/CSA Type: -
Characteristics
>PU05907001Z safety manual
Dimensions
IL05013002Z-EN instructional leaflet for easySafety ES4P safety relays
 
>
>
>
>
>>

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or