PSG480R24RM 172888 EATON MOELLER PSG480R24RM Redundancy module for PSG power supply units, 20 A View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PSG480R24RM 172888 EATON MOELLER PSG480R24RM Redundancy module for PSG power supply units, 20 A

PSG480R24RM

172888

EATON - MOELLER

Available

Ship on today

PSG480R24RM Redundancy module for PSG power supply units, 20 A

More details


* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  Power supplies PSG
Subrange
  Redundancy module
Description
  For decoupling power supplies of the same type that are connected in parallel on the output side for redundancy purposes
Input voltage range
  22 - 60 V DC
Nominal input voltage
  24 - 48 V DC
Rated output voltage
  Vin - 0.65 V
Rated output current
 A20
Technical data
Input characteristics
Nominal input voltage
  24 - 48 V DC
Input voltage range
 V24 - 48 V DC
Eingangsspannungsalarm_Relaiskontakt
  Relay contact closed OK if Vin1 & Vin2 > 18 V +/- 5% and < 30 V
 
   
Nominal current
InA(1+1) Redundanz : Nom. 2 x 12.5
(N+1) Redundanz : Nom. 2 x 10
Einfache Nutzung : Nom. 1 x 20
Back-up fuse
  3 x 10, 16 A (recommended)
Output characteristics
Rated output voltage
  Vin - 0.65 V
Nominal current
 Amax. 20
 
   
Derating from Tamb > +50 °C
  > 50 °C (2.5% / °C)
Heat dissipation
 W13
Efficiency
 %97 % norm.
Short-circuit current
  < 25 A, no damage
General characteristics
Housing
  Aluminium
Status indication
  Green LED for Vin1 OK & Vin2 OK

The LED lights up if Vin1 & Vin2 > 18 V +/- 5% and < 30 V
MTBF (mean time between failures)
  > 800,000 h
Height
 mm121
Width
 mm50
Depth
 mm122
Weight
 kg0.38
Terminations
  Screw connection
Stripping length
 mm7
Terminal capacity
   
flexible with ferrules/solid
 mm23.3 - 5.3 mm² (AWG 12 - 10)
Tightening torque
 Nm0.7
Ambient air temperature range
 °C 
Operation
 °C-40 - +80
damp heat
  < 95 % relative humidity at +25 °C, no condensation
Vibrations (IEC/EN 60068-2-6)
  10 - 500 Hz at 30 m/s² (3 G max ) for 60 min. in X-axis, Y-axis, Z-axis directions
Mechanical shock resistance (IEC 60068-2-27)
  30 g (300 m/s²) in all directions
Pollution degree
  2
Climatic class (IEC)
  3K3 according to EN 60721
Safety and safety features
Insulation voltage
   
Input/PE
  1.5 kV AC
 
   
Output/PE
  1.5 kV AC
Degree of Protection
  IP20
 
   
Protection class
  Class II with PE connection
Standards
 
  Electrical equipment of machines: IEC60204-1 (Overvoltage category III)
Electronic devices for use in electrical systems: EN 50178/IEC 62103
Safety extra-low voltage: PELV (EN 60204), SELV (EN 60950)
Protection against electric shock: DIN 57100-410
CE: In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
RoHS-compliant: RoHS Directive 2011/65/EU
ITE: EN 55022, EN 61000-3-2, EN 61000-3-3, EN 55024
Industrial: EN 55011
Mains harmonics limitation: EN 601000-3-2
Electrical safety (of IT equipment) : UL/c-UL recognized as per UL 60950-1 and CSA C22.2 No. 60950-1, SIQ BG as per EN 60950-1, CB test report as per IEC 60950-1 and CE
Industrial control equipment: UL/c-UL listed as per UL 508 and CSA C22.2
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA0
Heat dissipation per pole, current-dependent
PvidW0
Equipment heat dissipation, current-dependent
PvidW0
Static heat dissipation, non-current-dependent
PvsW13
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-40
Operating ambient temperature max.
 °C80
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Meets the product standard's requirements.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / DC-power supply (EC002540)
Electric engineering, automation, process control engineering / Power supply / Power supply (other) / DC-power supply ([email protected] [AFZ644012])
Voltage type of supply voltage
  DC
1st secondary output voltage
 V21.35 - 59.35
2nd secondary output voltage
 V0 - 0
3rd secondary output voltage
 V0 - 0
Max. output current 1
 A20
Max. output current 2
 A0
Max. output current 3
 A0
Secondary voltage adjustable
  No
Nominal value output voltage 1
 V24
Nominal value output voltage 2
 V0
Nominal value output voltage 3
 V0
Nominal value output current 1
 A20
Nominal value output current 2
 A0
Nominal value output current 3
 A0
Short-circuit-proof
  Yes
Rated supply voltage at AC 50 Hz
 V0 - 0
Rated supply voltage at AC 60 Hz
 V0 - 0
Rated supply voltage at DC
 V22 - 60
Output voltage stabilized
  No
Power consumption
 VA0
Power output
 W480
Stabilized
  No
Type of electric connection
  Screw connection
Rail mounting possible
  Yes
Wall mounting possible
  No
Modular version
  Yes
Width in number of modular spacings
  0
Built-in width
 mm50
Built-in height
 mm121
Direct mounting possible
  No
Width
 mm50
Height
 mm121
Depth
 mm122
Suitable for safety functions
  No
SIL according to IEC 61508
  None
Performance level acc. to EN ISO 13849-1
  None
Degree of protection (IP)
  IP20
Dimensions
IL125017EN Installation Instructions for PSG480R24RM REDUNDANCY MODULE
 
>>

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?