CL-PKZ0 082881 XTPAXCL EATON ELECTRIC Current limiter, 3p, 63A, 400VAC/100kA, 690VAC/10kA View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

CL-PKZ0 082881 XTPAXCL EATON ELECTRIC Current limiter, 3p, 63A, 400VAC/100kA, 690VAC/10kA

CL-PKZ0

082881

XTPAXCL

EATON-MOELLER

Current limiter, 3p, 63A, 400VAC/100kA, 690VAC/10kA

More details


Low-voltage industrial components > Current limiter

Motor-protective circuit-breakers PKZ (Accessories)

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $48.26
Unit price: $48.26

Quantity Price
1+$48.26
2+$41.13
3+$37.44
4+$37.00
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Often bought together

More info



Current limiter, 3p, 63A, 400VAC/100kA, 690VAC/10kA
Current limiter 3pole, submountable with PKZM0-size circuit-breaker, PKZM4, PKZM01, Ue = 690 V, Iu = 63 A

General specifications
Product name
Eaton Moeller® series PKZ0 Current limiter
Part no.
CL-PKZ0
EAN
4015080828815
Product Length/Depth
56 millimetre
Product height
90 millimetre
Product width
45 millimetre
Product weight
0.201 kilogram
Certifications
UL File No.: E36332
CSA File No.: 165628
CSA-C22.2 No. 14
UL Category Control No.: NLRV
CE
CSA
UL 508
CSA Class No.: 3211-05
IEC/EN 60947-4-1
UL
Product Tradename
PKZ0
Product Type
Current limiter
Product Sub Type
None
Features & Functions
Functions
Short-circuit current limiter
Can be used for individual and group protection
General information
Mounting position
Next to or behind the motor protective circuit breaker
Overvoltage category
III
Pollution degree
3
Product category
Accessories
Rated impulse withstand voltage (Uimp)
6000 V AC
Type
Motor-protective circuit-breaker, non-auto-protected in order to increase switching capacity
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Electrical rating
Rated operational voltage
Max. 690 V
690 V AC
Rated uninterrupted current (Iu)
63 A
Short-circuit rating
Rated conditional short-circuit current (Iq)
0 kA
Design verification
Equipment heat dissipation, current-dependent Pvid
8.4 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
2.8 W
Rated operational current for specified heat dissipation (In)
63 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Current limiter (EC000239)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Current limiter (ecl@ss13-27-37-04-16 [AKF014018])
Max. apparent power
0 VA
Mounting method
DIN rail
Conditioned rated short-circuit current Iq
0 kA
Rated permanent current Iu
63 A
Short-circuit current limiter
Yes

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.