CMD(24VDC) 106170 CMDTD EATON ELECTRIC Contactor monitoring device, 24 V DC View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

CMD(24VDC) 106170 CMDTD EATON ELECTRIC Contactor monitoring device, 24 V DC

CMD(24VDC)

106170

CMDTD

EATON-MOELLER

Contactor monitoring device, 24 V DC

More details


Low-voltage industrial components > Contactor relay

KDIL Accessories

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Contactor monitoring device, 24 V DC
Contactor monitoring device for safe emergency stop applications up to performance level e. Monitors the power contactor's reliable switching. Reduces main power wiring effort., saves redundant contactor set-up

Technical data

General
Standards
IEC/EN 60947-5-1
UL
CSA
Lifespan, mechanicalDC operated [Operations]
3 x 106
Maximum operating frequencyMotor rating AC-1 500 V [Operations]
9000 x 106
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-5 - +50 °C
Ambient temperatureStorage
- 40 - 80 °C
Mounting position
As required
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msN/O contact
4 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msN/C contact
4 g
Degree of Protection
IP20
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Weight
0.13 kg
Terminal capacitiesSolid
1 x (0.5…2.5)
2 x (0.5…1.5) mm2
Terminal capacitiesFlexible with ferrule
1 x (0.5…2.5)
2 x (0.5…1.5) mm2
Terminal capacitiesSolid or stranded
Single 20 - 14/Double 20 - 16 AWG
Terminal capacitiesStripping length
6 mm
Terminal screw
M3.5
Pozidriv screwdriver
2 Size
Standard screwdriver
0.8 x 5.5
1 x 6 mm
Max. tightening torque
1.2 Nm
Contacts
Rated impulse withstand voltage [Uimp]
800 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
100 V AC
Rated operational voltage [Ue]
24 DC V
Short-circuit rating without weldingShort-circuit protection maximum fuse500 V
2 A gG/gL
Magnet systems
Voltage tolerancePick-up voltageAC operated[Pick-up]
0.85 - 1.1 x Uc
Voltage tolerancePick-up voltageDC operated [Pick-up][Pick-up]
0.85 - 1.1 x Uc
Power consumptionAC [Sealing]
4 W
Power consumptionDC operated [Pull-in = sealing]
4 W
duty factor
100 % DF
contact changeover timeCMD [ tu]
< 100 ± 20 % ms
Notes
Notes
For rated operational current: Making and breaking conditions to DC-13, L/R constant as stated
Max. fuses for short-circuit protection: Transparent overlay "Fuses" for time/current characteristics (please enquire)
For pick-up voltage, DC operated:Pure DC, AC bridge rectifier or smoothed double-wave rectification.

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
0 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
2.29 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-5 °C
Operating ambient temperature max.
+50 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Contactor relay (EC000196)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Contactor relay ([email protected] [AAB716014])
Rated control supply voltage Us at AC 50HZ
0 - 0 V
Rated control supply voltage Us at AC 60HZ
0 - 0 V
Rated control supply voltage Us at DC
24 - 24 V
Voltage type for actuating
DC
Rated operation current Ie, 400 V
0 A
Connection type auxiliary circuit
Screw connection
Mounting method
DIN rail
Interface
No
Number of auxiliary contacts as normally closed contact
1
Number of auxiliary contacts as normally open contact
1
Number of auxiliary contacts as normally closed contact, delayed switching
0
Number of auxiliary contacts as normally open contact, leading
0
With LED indication
Yes
Number of auxiliary contacts as change-over contact
0
Manual operation possible
No

Approvals

Product Standards
IEC/EN 60947-4-1; CSA-C22.2 No. 14-10; ANSI/UL 508; CE marking
CSA File No.
012528
CSA Class No.
3211-04, 3211-84 (Certified to US Standards)
North America Certification
CSA certified

Dimensions

250X003
CMD(...)

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.