Produto adicionado com sucesso ao seu carrinho de compras
S-PT-4-EX-24DC
2800036
PHOENIX_CONTACT
1
Dispositivo de proteção contra surtos
Proteção contra surtos de dois níveis para três ou quatro sinais de circuitos de sinal acionados sem potencial para o terra no módulo spin-on de classificação IP67 para cabeçotes de sensores, conexão M20 x 1,5. Testado de acordo com os tipos de proteção nas zonas Ex Ex d/Ex tD/Ex ia IIC/Ex iaD. Adequado para uso em sistemas de barramento de campo de acordo com o conceito FISCO (conceito de barramento intrinsecamente seguro), adequado para HART.
Two-stage surge protection for three or four signals of floating signal circuits in the screw-on module with IP67 degree of protection for sensor heads, connection: M20 x 1.5. Tested in accordance with the following types of protection in Ex areas: Ex d/Ex tD/Ex ia IIC/Ex iaD. Suitable for use in the fieldbus system in accordance with the FISCO concept, HART-compatible. Can be used in safety-related circuits up to SIL 3.
Aterramento, proteção contra raios e sobretensões > Combinação de pára-raios para tecnologia da informação/MCR
Trabtech (TT)
Produto novo em sua embalagem original com todas as garantias e certificações de PHOENIX_CONTACT
Obrigado pelo seu interesse nos nossos artigos, esperamos que o prazo indicado seja conveniente para si.
Durante a preparação do pedido pode seleccionar o tipo de envío que melhor se adapte ás suas necessidades: Aéreo Express 24Hrs, Terrestre Standard 48/72Hrs, etc.
| Product type | Surge protection for MCR technology |
| Product family | SURGETRAB |
| IEC test classification | C1 |
| C2 | |
| C3 | |
| D1 | |
| Type | Screw-in module |
| Number of positions | 4 |
| Data management status | |
| Article revision | 08 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Nominal voltage UN | 24 V DC |
| Connection method | Individual wires |
| Maximum inner capacitance Ci | 1.65 nF |
| Max. internal inductance Li | 1 µH |
| Max. input current Ii | 500 mA (T4 / ≤ 75 °C) |
| 500 mA (T5 / ≤ 75 °C) | |
| 500 mA (T6 / ≤ 60 °C) | |
| Max. input voltage Ui | 36 V DC |
| max. input power Pi | 3.00 W |
| Insulation voltage to ground | 500 V AC |
| Ambient temperature (operation) | -40 °C ... 75 °C (T4) |
| -40 °C ... 75 °C (T5) | |
| -40 °C ... 60 °C (T6) | |
| Operating temperature range | -40 °C ... 100 °C (T4) |
| -40 °C ... 75 °C (T5) | |
| -40 °C ... 60 °C (T6) | |
| Max. surface temperature | 135 °C (T4) |
| 100 °C (T5) | |
| 85 °C (T6) |
| Dimensional drawing | ![]() |
| Width | 28 mm |
| Height | 28 mm |
| Depth | 79 mm |
| Color | Steel/stainless steel color |
| Seal material | NBR |
| Housing material | Stainless steel 1.4404 |
| ASTM 316L |
| Mechanical data | |
| Open side panel | No |
| Direction of action | Line-Line & Line-Earth Ground |
| Maximum continuous voltage UC | 36 V DC |
| 25 V AC | |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In(8/20) µs (line-line) | 260 A |
| Nominal discharge current In(8/20) µs (line-ground) | 10 kA |
| Pulse discharge current Iimp(10/350) µs | 1 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Total discharge current Itotal(10/350) µs | 2 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 50 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 130 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 1.1 kV |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 60 V |
| Voltage protection level Up(line-line) | ≤ 65 V (C3 - 10 A) |
| Voltage protection level Up(line-earth) | ≤ 1.1 kV (C3 - 100 A) |
| ≤ 1.1 kV (C1 - 1 kV / 500 A) | |
| ≤ 1.2 kV (C2 - 10 kV / 5 kA) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.1 dB (30 MHz / 50 Ω) |
| typ. 0.1 dB (6 MHz / 150 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 50 Ω system | typ. 70 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ω system | typ. 40 MHz |
| Capacity (Core-Core) | typ. 20 pF |
| Capacity (Core-Earth) | typ. 5 pF |
| Surge protection fault message | none |
| Impulse durability (line-line) | C3 - 25 A |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 1 kA | |
| Alternating current carrying capacity (line-earth) | 10 A - 1 s |
| Ambient conditions | |
| Degree of protection | IP67 |
| Ambient temperature (operation) | -40 °C ... 80 °C (non-Ex) |
| Altitude | ≤ 2000 m (amsl) |
| Conformity/Approvals | |
| ATEX | II 1 G Ex ia IIC T4...T6 |
| II 2 G Ex d IIC T4...T6 | |
| II 1 D Ex iaD 20 IP6x T85 °C...135 °C | |
| II 2 D Ex tD A21 IP6x T85 °C...135 °C | |
| IECEx | Ga Ex ia IIC T4...T6 |
| Ex d IIC T4...T6 | |
| Ex iaD IP6x T85 °C...135 °C | |
| Ex tD A21 IP6x T85 °C...135 °C | |
| Air clearances and creepage distances | |
| Standards/regulations | IEC 60664-1 / IEC 60079-11 |
| Standards/specifications | EN 61643-21 |
| Note | A2:2013 |
| Standards/specifications | EN 60079-0 |
| Note | 2018 |
| Standards/specifications | EN 60079-1 |
| Note | 2007 |
| Standards/specifications | EN 60079-11 |
| Note | 2012 |
| Standards/specifications | EN 60079-31 |
| Note | 2009 |
| Standards/specifications | IEC 60079-0 |
| Note | 2017 |
| Standards/specifications | IEC 60079-1 |
| Note | 2007 |
| Standards/specifications | IEC 60079-11 |
| Note | 2011 |
| Standards/specifications | IEC 60079-31 |
| Note | 2008 |
| Mounting type | M20 |
| Título: | Tamanho: | Tipo: |
|---|---|---|
| PDF CATALOG PHOENIX PROTECTION EN .pdf | 27 Mbytes |
|
| PHOENIX CONTACT-2800036-S-PT-4-EX-24DC | 130 Kbytes |
![]() |
Não há comentários do produto ainda.
| Avaliação: |
|
| Nome: | |
| Email: | |
| Título: | |
| Opinión: | |
| Você recomendaria esse produto para comprar? | |
|
|
|
| Adicionar avaliação | |
Todas as classificações que recebemos a partir dos itens que oferecemos são reais e verificadas. Um pequeno gesto, mas muito valioso. Então, obrigado por esse minuto você gasta em deixar-nos a sua opinião e classificação de produtos, porque nos ajuda a continuar a melhorar e oferecer maior qualidade de serviço.